Plan Review Details - Permit 09080250
Plan Review Stops For Permit 09080250
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-16 Cont ID  
Sent By jwitmer Date 2009-09-16 Time 10:47 Rev Time 0.77
Received By jwitmer Date 2009-09-16 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-17 Cont ID  
Sent By jwitmer Date 2009-08-17 Time 14:58 Rev Time 1.00
Received By jwitmer Date 2009-08-17 Time 14:30 Sent To  
Notes
2009-08-17 15:22:53RESIDENTIAL BUILDING PLAN REVIEW
 PERMIT: 09080250
 ADD: 810 30TH ST
 CONT: GLADES ROOFING
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLANS DO NOT INDICATE ANY WIND DESIGN DRITERIA:
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) NEITHER THE PLANS NOR NOA INDICATE IF THESE WINDOWS
 ARE TO BE FASTEND THROUGH WOOD BUCKS, THE NOA SUBMITTED
 IS FOR FLANGED TYPE INSTALATION, THE CONCERN IS THE
 REQUIRED SEPERATION FROM GLASS TO SHUTTER IS 2 5/8 TO 3
 5/8 INCHES PLEASE INDICATE CODE COMPLIANCE FOR BOTH
 ISSUES. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-16 Cont ID  
Sent By jwitmer Date 2009-09-16 Time 14:40 Rev Time 1.25
Received By jwitmer Date 2009-09-16 Time 14:40 Sent To  
Notes
2009-09-16 15:04:07PROVISO:
 2007 FBC RESIDENTIAL R313.2.1
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED.
 EXCEPTIONS:
 INTERCONNECTION AND HARD-WIRING OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE THE
 ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF
 INTERIOR WALL OR CEILING FINISHES EXPOSING THE
 STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR
 BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD
 WIRING AND INTERCONNECTION
  
  
 SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL NEED TO
 BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE ALARMS AND
 SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20 FT)
 HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 SERVICE OUTLETS FOR A/C EQUIPMENT.210.52(E), 210.8(3)
 OUTDOORS 210.63 .
  
 REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3
 210.8A1
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By jwitmer Date 2009-08-13 Time 13:59 Rev Time 1.50
Received By jwitmer Date 2009-08-13 Time 11:32 Sent To  
Notes
2009-08-13 16:57:09RESIDENTIAL ELECTRICAL PLAN REVIEW
 PERMIT: 09080250
 ADD: 810 30TH ST
 CONT: JMA ELECTRIC/ 09080258
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
 2005 NEC
  
 NOTE THE PERMIT APPLICATION INDICATES THAT THE
 ELECTRICAL UPGRADE TO "CODE"
  
 1A) PLANS FAIL TO IDENTIFY THE CODE CYCLE THAT THE
 PLANS ARE TO BE DESIGNED TO:
 2007 FBC/ 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE/ 2009 SUPPLEMENTS
 2005 NEC
  
 1B) EXISTING BUILDING CODE: 401.4 A DESIGN PROFESSIONAL
 OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE.
  
 2) PLEASE REVIEW THE ELECTRICAL PLANS VERSES THE
 MECHANICAL PLAN, THE UTILITY ROOM APPLIANCES AND A/C
 EQUIPMENT ARE LOCATED IN DIFFERENT LOCATION, PLEASE
 CORRELATE PLANS TO THE SAME LOCATION FOR ALL TRADES.
 106.1.2.
  
 3) SHEET 1 ALSO NEEDS TO CORRELATE THE PANEL SCHEDULE
 AND FLOOR PLAN TO REFLECT THE SAME CIRCUITRY IN THE
 PANEL SCHEDULEAS FLOOR PLAN. EXAMPLES ARE THE FLOOR
 PLAN INDICATES THE A/C CONDENSORS ON CIRCUIT 24-26WHERE
 AS THE PANEL SCHEDULE INDICATE 24-25. A/C HANDLER ON
 THE FLOOR PLAN ON CIRCUITS 2&4 IN PANEL SCHEDULE 2 IS
 GENERAL LIGHTING AND 4 IS RECEPTACLES.
 THERE ARE MORE THAN THESE DISCREPANCIES PLEASE REVIEW
 AND CORRECT. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 106.1.1.
  
 4) THE AIR COMPRESSORS ELECTRICAL SYSMBOL IS ACTUALLY
 DRAWN IN AS A 240 OULET NOT AS A REQUIRED DISCONNECT
 PLEASE CORRECT.
 440.11 GENERAL. THE PROVISIONS OF PART II ARE INTENDED
 TO REQUIRE DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIRCONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTORCOMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. PLEASE INDICATE A TRUE DISCONNECT.
  
 5) FLOOR PLAN INDICATES (2) SUB-PANELS LABELED "B"
 WHERE AS THE RISER DIAGRAM ONLY INDICATES A SINGLE
 PANEL, AGAIN PLEASE IDENTIFY WHICH PANEL IS WHERE,
 PANEL A AND PANEL B.
  
 6) THE OTHER ISSUE IS THE NEW 200 AMP DISCONNECT
 BREAKER, IS MISSING THE A/C RATING. 110.9 INTERRUPTING
 RATING. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING
 SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND THE
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 OTHER THAN
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT
 NOMINAL CIRCUIT VOLTAGE SUFFICIENT FOR THE CURRENT THAT
 MUST BE INTERRUPTED .
  
 7A) FLOOR PLAN ALSO INDICATES THE UTILITY ROOM PANEL
 JUST THE WIDTH OF THE PANEL PLEASE REVIEW: 408.4
 CIRCUIT DICTIONARY. ALL CIRCUITS AND CIRCUIT
 MODIFICATINS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE
 OR USE ON A CIRCUIT DIRECTORY LOCATED ON THE FACE OR
 INSIDE OF THE PANEL DOOR IN THE CASE OF A PANEL OARD,
 AND AT EACH SWITCH ON A SWITCHBOARD. NOTE IDENTIFY
 CIRCUITS BY ROOM NOT GENERAL LIGHTING OR RECEPTACLES.
  
 7B) PANEL LOCATIONS NEED TO COMPLY WITH: 110.26 (1)
 DEPTH OF WORKING SPACE, (2) WIDTH OF WORKING SPACE &
 (3) HEIGTH OF WORKING SPACE. FOR BOTH PANEL LOCATIONS.
 THE DEDICATED ELECTRICAL SPACE MUST BE CLEAR OF ANY
 PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT
 FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING,
 HEATING, VENTILATION, AND
 AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE
 INSTALLED OUTSIDE THE WIDTH AND DEPTH ZONE.
  
 8) NOTE THE PANEL SCHEDULE DOES NOT INCLUDE THE RANGE,
 WATER HEATER NOR DRYER SYMBOL INDICATING ELECTRICAL
 CONNECTIONS, IT IS UNKNOWN IF THESE APPLIANCES ARE
 ELECTRIC OR GAS, IF GAS THE SMOKE ALARMS WILL ALSO NEED
 TO BE CARBON MONOXIDE DETECTORS ALSOFL S S 553.885.
  
 9) THE BACK REAR BEDROOM DOES INDICATE A SMOKE ALARM
 WITHIN THE UNIT BUT NOT ONE OUTSIDE OF THE BEDROOM THIS
 ALSO HOLDS TRUE FOR THE MASTER BEDROOM FBC RESIDENTIAL
 313.2(2) AND NFPA 72.
  
 10) THE SMOKE ALARMS LOCATED WWITHIN 20' OF COOKING
 WILL NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE
 ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20
 FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE
 EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
  
 11) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS
 REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH
 CIRCUIT.
  
 12) BEDROOMS MISSING OUTLETS ON PLANS, PLEASE PROVIDE
 ARC FAULT OUTLET CIRCUIT PER 210.12(B) DWELLING UNIT
 BEDROOMS.210.52OUTLET SPACING.
  
 13)LIGHTING NOT SHOWN ON PLANS SWITCH LOCATIONS
 210.70.INTERIOR LOCATIONS
  
 14) EXTERIOR EXIT LIGHTS NOT SHOWN NOR SWITCH LOCATIONS
 210.70.
  
 15) REQUIRED SERVICE OUTLETS FOR A/C
 EQUIPMENT.210.52(E), 210.8(3) OUTDOORS 210.63 .
  
 16) THERMOSTATS ARE NOT SHOWN.
  
 17) 2ND AIR HANDLIER NOT SHOWN ON PANEL SCHEDULE.
  
 18) THE ELECTRIC RISER IS MISSING GROUND ROD LENGTH,
 250.66 & TABLE 250.66.
  
 19) LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2 &
 220.52.3
  
 20) MISSING EQUIPMENT GROUND BETWEEN MAIN AND PANEL
 250.122
  
 21) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D),
 21011.C.3 210.8A1
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-09 Cont ID  
Sent By shill Date 2009-09-09 Time 14:40 Rev Time 0.00
Received By shill Date 2009-09-09 Time 14:40 Sent To  
Notes
2009-09-09 14:40:56TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-26 Cont ID  
Sent By mcruz Date 2009-08-26 Time 13:22 Rev Time 0.00
Received By mcruz Date 2009-08-11 Time 10:01 Sent To  
Notes
2009-08-11 10:02:05R-20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-16 Cont ID  
Sent By jwitmer Date 2009-09-16 Time 14:11 Rev Time 0.77
Received By jwitmer Date 2009-09-16 Time 10:48 Sent To  
Notes
2009-09-16 14:27:09PROVISO: 2007 RESIDENTIAL M1602.4
 TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-17 Cont ID  
Sent By jwitmer Date 2009-08-17 Time 15:44 Rev Time 0.50
Received By jwitmer Date 2009-08-17 Time 15:44 Sent To  
Notes
2009-08-17 15:53:07RESIDENTIAL MECHANICAL PLAN REVIEW
 PERMIT: 09080250
 ADD: 810 30TH ST
 CONT: GLADES ROOFING
 TEL: (561)GLADES ROOFING CGC 954-593-5917
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET 2OF 2 INDICATES PLENUM RRETURNS ABOVE THE
 CEILING WITH A R-30 VALUE FOR INSULATION. IF THE AIR
 HANDLIERS ARE AS SHOWN AS A VERTICAL UNIT WITH THE
 RETURN AIR BEING LOCATED AT THE BOTTOM OF THE UNIT WHY
 DOES THE PLAN CALL FOR A PLENUN RETURN LOCATED WITHIN
 THE ATTIC? M1601.9 CAVITIES OF THE BUILDING
 STRUCTURE.EXCEPTION: SURFACES BETWEEN THE PLENUM AND
 CONDITIONED SPACES FROM WHICH THE RETURN/MIXED AIR IS
 DRAWN.
 BUILDING CAVITIES BENEATH A ROOF DECK THAT WILL BE USED
 AS RETURN AIR PLENUMS SHALL HAVE AN INSULATED ROOF WITH
 THE INSULATION HAVING AN R-VALUE OF AT LEAST R-19.
  
 3) RETURN AIR TRANSFER DUCTS & GRILLS;
 3A) PLANS INDICATE BEDROOMS 1,2 & 3 ALL HAVING FLEX
 RETURN TRANSFER DUCTS SIZE NOT PROVIDED AND EACH HAVING
 A 8X8 INCH RETURN AIR GRILL TRANSFERING INTO A SINGLE
 RETURN WITH A SINGLE 8X8 INCH TRANSFER GRILLE. PLEASE
 SHOW COMPLIANCE WITH :
 M1602.4 TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  
 3B) SHEET 2 OF 2 INDICATES THE AIR HANDLER LOCATED IN A
 CLOSET WITH A RETURN AIR GRILLE LOCATED IN THE DOOR,
 PLEASE PROVIDE SIZE OF RETURN AIR GRILLE. M1602.4
 BALANCED RETURN AIR. RESTRICTED RETURN AIR OCCURS IN
 BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND
 CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN
 GRILL OR WHEN CEILING SPACES ARE USED AS RETURN PLENUMS
 AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE PORTION
 OF THE RETURN PLENUM TO ANOTHER. PROVISIONS SHALL BE
 MADE IN RESIDENTIAL BUILDINGS TO AVOID UNBALANCED AIR
 FLOWS AND PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED
 RETURN AIR.
 TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (4.6 MM)
 (OF GRILLE AREA) TO 100 CFM (0.05 M3/S) (OF SUPPLY AIR)
 FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING
 AN UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 4) THE BATHROOM IS LOCATED WIWTHIN THE INTERIOR OF THE
 RESIDENCE REQUIRING A EXHAUST FAN PLANS DO NOT INDICATE
 SUCH FAN PLEASE REVIEW M1507.3 VENTILATION RATE/ TABLE
 M1507.3
 BATHROOMS/ TOILET ROOMS MECHANICAL EXHAUST CAPACITY OF
 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS.
  
 5) THE BACK BEDROOM TRANSFER DUCT NOR GRILLE SIZE IS
 NOT INDICATED. M1602.4.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-08-17 Cont ID  
Sent By jwitmer Date 2009-08-17 Time 15:23 Rev Time 0.00
Received By jwitmer Date 2009-08-17 Time 15:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-14 Cont ID  
Sent By astelly Date 2009-09-14 Time 09:55 Rev Time 0.00
Received By astelly Date 2009-09-14 Time 09:55 Sent To B
Notes
2009-09-14 12:23:07AMY F. STELLY
 PLANNING AND ZONING
 561.822.1442
  
 ZONING REVIEW PASSED PER ANGELLA JONES-VANN.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-26 Cont ID  
Sent By mcruz Date 2009-08-26 Time 13:22 Rev Time 0.00
Received By mcruz Date 2009-08-26 Time 13:11 Sent To  
Notes
2009-08-26 13:21:55PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
 WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN
 18 INCHES INTO A REQUIRED SIDE SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  