Plan Review Details - Permit 09080231
Plan Review Stops For Permit 09080231
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-17 Cont ID  
Sent By jwitmer Date 2009-12-17 Time 13:47 Rev Time 0.55
Received By jwitmer Date 2009-12-17 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-19 Cont ID  
Sent By jwitmer Date 2009-08-19 Time 14:41 Rev Time 1.50
Received By jwitmer Date 2009-08-19 Time 13:05 Sent To  
Notes
2009-08-19 14:40:55BUILDING PLAN REVIEW
 PERMIT: 09080231
 ADD: 6501 N JOG RD
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL. SHEET A-001 & A-002 INDICATE A MAINTENANCE
 SHOP FIRST FLOOR AND WHAT APPEARS TO BE A MEZZANINE
 LEVEL ABOVE. THE PLANS DO NOT INDICATE THE SQUARE
 FOOTAGE OF THE ROOM ( FIRST FLOOR) TO DETERMINE IF THIS
 AREA IS A TRUE MEZZANINE, PLEASE REVIEW SECTION 505.2
 AREA LIMITATIONS ON MEZZANINES.
  
 3) THE SECOND ISSUE WHICH CAN NOT BE ANSWERED AT THIS
 TIME IS THE OPENNESS REQUIREMENTS (505.4) FOR MEZZANNE
 IT APPEARS EXCEPTION# 1MAY APPLY BUT WITH NOT KNOWING
 THE FLOOR AREA BELOW AND IF TTHE EXISTING OFFICE AND
 CONFERENCE ROOM ARE CONSIDERED PART OF TTHE ENCLOSED
 MEZZANINE THE OCCUPANT LOAD MAY THEN RISE ABOVE 10.
  
 4A) WITH ONLY SHOWING A PORTION OF THE BUILDING THE
 NEXT ISSUE IT APPEARS THIS BUILDING IS TO BE CONSIDERED
 A MIXED OCCUPANCY OR DOES THE MAINTENCE SHOP MEET THE
 REQUIREMENT 508.3.1 ACCESSORY OCCUPANCIES BETWEEN THE
 MAINTENANCE SHOP AND THE BUSINESS OCCUPANCY. IF NOT
 PLEASE PROVIDE OCCUPANCY SEPERATION AND OPENING
 PROTECTIVES.
 TABLE 508.3.3 AND 715 OPENING PROTECTIVES.
  
 4B) IF OCCUPANCY SEPERATION IS DETERMINED TO BE NEEDED
 PLEASE SEE REVIEW CUT SECTIONS OF WALLS THAT WILL NEED
 TO EXTEND TO THE DECK ABOVE TO OBTAIN A IFE RATING.
 708.4 CONTINUITY.
  
  
 5) SHEET A.003 WALL SECTION DETAILS ALSO INDICATES THE
 R-30 BATT INSULATION LAYING ON TOP OF THE DROP IN
 CEILING PANELS. 13-404.AB.1 ROOF INSULATION SHALL NOT
 BE INSTALLED ON A SUSPENDED CEILINGWITH REMOVABLE
 PANELS.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-14 Cont ID  
Sent By btrobaug Date 2009-12-14 Time 12:27 Rev Time 0.00
Received By btrobaug Date 2009-12-14 Time 12:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By btrobaug Date 2009-08-24 Time 14:00 Rev Time 0.00
Received By btrobaug Date 2009-08-24 Time 13:30 Sent To  
Notes
2009-08-24 14:00:50 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1THIS CAN BE DEMONSTRATED ON THE PLANS
 INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR
 THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 2} 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED BY
 CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE
 READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE
 THE CONTROLLED LIGHTING. A. A CONTROL DEVICE SHALL BE
 INSTALLED THAT AUTOMATICALLY TURNS LIGHTING OFF WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, EXCEPT
 SPACES WITH MULTI-SCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS)
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By mawillia Date 2009-12-21 Time 13:42 Rev Time 0.00
Received By mawillia Date 2009-12-21 Time 12:51 Sent To  
Notes
2009-12-21 13:31:27*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS FX-001, FX-002, FX-003, AND
 LS-101 & LS-102 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-27 Cont ID  
Sent By mcarsill Date 2009-08-27 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2009-08-27 Time 13:07 Sent To  
Notes
2009-08-27 13:12:586501 NORTH JOG ROAD
 PERMIT NUMBER 09080231
  
 1. WRONG LIFE SAFETY CODE REFERENCED ON COVER SHEET.
 SHOULD READ NFPA 101, 2006 EDITION.
  
 2. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 3. PLEASE ILLUSTRATE ALL ILLUMINATED EXIT SIGNS,
 EMERGENCY LIGHTS, FIRE ALARM EQUIPMENT AND EXIT DOORS.
  
 4. PLEASE INDICATE FIRE SEPARATION BETWEEN MAINTENANCE
 SHOP AND GENERAL OFFICE AREA.
  
 5. PLEASE INDICATE THE LOCATION OF ANY FIRE DOORS.
  
 6. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 REPLACED CEILING AREA.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER REMODEL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2009-12-09 Time 13:35 Sent To  
Notes
2009-12-09 13:36:17RESUB TO BOX: B-5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-31 Time   Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 13:26 Sent To  
Notes
2009-08-11 13:28:58B-7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-01-05 Cont ID  
Sent By rregueir Date 2010-01-05 Time 14:39 Rev Time 0.00
Received By rregueir Date 2009-12-23 Time 12:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 09:58 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 09:41 Sent To  
Notes
2009-12-21 09:58:24REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. **NOT ADDRESSED** THE PROPOSED SCOPE OF WORK SHOWS
 AN INCREASE IN THE CONDITIONED SPACE WITHIN THIS
 BUILDING. AN EXTENSION OR INCREASE IN CONDITIONED FLOOR
 AREA OF A BUILDING IS CONSIDERED AN ADDITION PER FBC-B
 13-202. ADDITIONS TO EXISTING COMMERCIAL BUILDINGS ARE
 CONSIDERED NEW BUILDING CONSTRUCTION AND SHALL COMPLY
 WITH METHOD A OF SUBCHAPTER 13-4 OF THIS CODE AS
 ALLOWED IN SECTION 13-101.1.1. PROVIDE A METHOD A CODE
 COMPLIANCE FORM AND AN APTTACHED COOLING LOAD
 CALCULATION IN ACCORDANCE WITH THIS SECTION AND FBC-B
 13-407.AB.1.
  
 2. OK
  
 3. **NEED ENERGY CALCULATIONS** AN AIR BARRIER IS
 REQUIRED BETWEEN THE CONDITIONED AND UNCONDITIONED
 SPACE AT THE BUILDING THERMAL ENVELOPE. A DROPPED T-BAR
 TYPE CEILING CAN NOT SERVE THIS PURPOSE. AIR BARRIERS
 SHALL BE IN ACCORDANCE WITH FBC-B 13-406.AB. THIS
 APPLIES TO EXTERIOR WALLS AND ROOF/CEILINGS.
  
 4. OK
 NOTE: A TEST AND BALANCE REPORT WILL BE REQUIRED AT
 FINAL INSPECTION TO CONFIRM VENTILATION RATES IN
 ACCORDANCE WITH FBC-M 403.3.4.
  
 5. OK
  
 6. **NOT ADDRESSED** PAGE M-501 SHOWS CONDENSATE FROM
 NEW AHU DISCHARGING INTO FLOOR DRAIN. IS THIS FLOOR
 DRAIN PART OF A SANITARY SEWER SYSTEM? CONDENSATE SHALL
 NOT DISCHARGE INTO SANITARY SEWER SYSTEMS PER CITY
 ORDINANCE. CONDENSATE SHALL DISCHARGE OUTDOORS AT AN
 APPROVED LOCATION IN ACCORDANCE WITH FBC-M 307.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-31 Cont ID  
Sent By rregueir Date 2009-08-31 Time 12:33 Rev Time 0.00
Received By rregueir Date 2009-08-31 Time 11:00 Sent To  
Notes
2009-08-31 12:33:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE PROPOSED SCOPE OF WORK SHOWS AN INCREASE IN THE
 CONDITIONED SPACE WITHIN THIS BUILDING. AN EXTENSION OR
 INCREASE IN CONDITIONED FLOOR AREA OF A BUILDING IS
 CONSIDERED AN ADDITION PER FBC-B 13-202. ADDITIONS TO
 EXISTING COMMERCIAL BUILDINGS ARE CONSIDERED NEW
 BUILDING CONSTRUCTION AND SHALL COMPLY WITH METHOD A OF
 SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED IN SECTION
 13-101.1.1. PROVIDE A METHOD A CODE COMPLIANCE FORM AND
 AN APTTACHED COOLING LOAD CALCULATION IN ACCORDANCE
 WITH THIS SECTION AND FBC-B 13-407.AB.1.
  
 2. PAGE A-003 SHOWS BATT INSULATION BEING INSTALLED
 ABOVE A SUSPENDED CEILING. ROOF INSULATION SHALL NOT BE
 INSTALLED ON A SUSPENDED CEILING WITH REMOVABLE CEILING
 PANELS IN ACCORDANCE WITH FBC-B 13-404.AB.1.
  
 3. AN AIR BARRIER IS REQUIRED BETWEEN THE CONDITIONED
 AND UNCONDITIONED SPACE AT THE BUILDING THERMAL
 ENVELOPE. A DROPPED T-BAR TYPE CEILING CAN NOT SERVE
 THIS PURPOSE. AIR BARRIERS SHALL BE IN ACCORDANCE WITH
 FBC-B 13-406.AB. THIS APPLIES TO EXTERIOR WALLS AND
 ROOF/CEILINGS.
  
 4. SCHEDULE ON M-001 SHOWS A VENTILATION RATE OF 300
 CFM. VENTILATION RATE NOTE CALLS FOR A VENTILATION RATE
 OF 20 CFM PER PERSON. THIS WOULD ACOMMODATE AN OCCUPANT
 LOAD OF 15 PERSONS IN THE AREA SERVED BY THIS AHU. THE
 OCCUPANT LOAD FOR THE OFFICES, RECEPTION/LOBBY AND
 CONFERENCE ROOMS WOULD EXCEED 15 PERSONS BASED ON FBC-M
 TABLE 403.3. PROVIDE SPACE-BY-SPACE VENTILATION
 CALCULATIONS TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION.
 NOTE: A TEST AND BALANCE REPORT WILL BE REQUIRED AT
 FINAL INSPECTION TO CONFIRM VENTILATION RATES IN
 ACCORDANCE WITH FBC-M 403.3.4.
  
 5. PAGES M-102 AND M-501 SHOW THE DUCT MOUNTED SMOKE
 DETECTOR ON THE RETURN AIR DUCT. SMOKE DETECTORS SHALL
 BE INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM, IN THE SUPPLY AIR DUCT
 PER FBC-M 606.2.1.
  
 6. PAGE M-501 SHOWS CONDENSATE FROM NEW AHU DISCHARGING
 INTO FLOOR DRAIN. IS THIS FLOOR DRAIN PART OF A
 SANITARY SEWER SYSTEM? CONDENSATE SHALL NOT DISCHARGE
 INTO SANITARY SEWER SYSTEMS PER CITY ORDINANCE.
 CONDENSATE SHALL DISCHARGE OUTDOORS AT AN APPROVED
 LOCATION IN ACCORDANCE WITH FBC-M 307.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-08-11 Cont ID  
Sent By eschneid Date 2009-08-11 Time 18:55 Rev Time 0.15
Received By eschneid Date 2009-08-11 Time 18:55 Sent To  
Notes
***NONE***