Plan Review Details - Permit 09080218
Plan Review Stops For Permit 09080218
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-01 Cont ID  
Sent By jwitmer Date 2009-09-01 Time 12:29 Rev Time 0.50
Received By jwitmer Date 2009-09-01 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-17 Cont ID  
Sent By jwitmer Date 2009-08-17 Time 13:00 Rev Time 0.50
Received By jwitmer Date 2009-08-17 Time 12:30 Sent To  
Notes
2009-08-17 13:19:21BUILDING PLAN REVIEW
 PERMIT: 09080218
 ADD: 100 S DIXIE HWY # 100
 CONT: GERRARD CONTRACTING
 TEL: (561)281-5225
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE SEE DISCREPANCY BETWEEN THE ADDRESS ON THE
 PERMIT APPLICATION AND TITLEBLOCK OF PLANS.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. 106.1.1.
  
 1B) PLANS INDICATE TWO 1.0A SHEETS WITH DIFFERENT PLANS
 ON EACH PLEASE CORECT. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. 106.1.1.
  
 2) THE FIRST 1.0A PLAN INDICATES (2) DOORS EACH A
 NUMBER 5 IN BOTH CASES THESE DOORS ARE INDICATED TO
 HAVE A LEVER KEYSET AND NOT A PASSAGE LOCK. BOTH OF
 THESE DOORS ARE PART OF A MEANS OF EGRESS WHICH WOULD
 REQUIRE PASSAGE LOCKS. 1003.6 MEANS OF EGRESS
 CONTINUITY.
  
 3) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 2007 EXISTING BUILDING CODE SECTION 401.4 A DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-02 Cont ID  
Sent By btrobaug Date 2009-09-02 Time 12:24 Rev Time 0.00
Received By btrobaug Date 2009-09-02 Time 12:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-18 Cont ID  
Sent By btrobaug Date 2009-08-18 Time 15:44 Rev Time 0.00
Received By btrobaug Date 2009-08-18 Time 12:37 Sent To  
Notes
2009-08-18 15:27:44 
 PROVISO
 THE ADDRESS ON THE APPLICATION IS NOT THE SAME AS ON
 THE PLAN, CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-01 Cont ID  
Sent By mawillia Date 2009-09-01 Time 14:39 Rev Time 0.00
Received By mawillia Date 2009-09-01 Time 13:49 Sent To  
Notes
2009-09-01 14:38:58*****APPROVED*****
  
 PLAN SHEETS 1.1A AND 2.0E WERE STAMPED, INITIALED, AND
 DATED. IN ADDITION, SINCE THERE IS NO FIRE ALARM SYSTEM
 FOR THE BUILDING, THE HORN STROBE DEVICE SHOWN ON THE
 LIFE SAFETY PLAN (SHEET 1.1A) AND THE POWER PLAN (SHEET
 2.1E) WERE RED X'ED AND INITIALED
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-20 Cont ID  
Sent By mawillia Date 2009-08-20 Time 11:50 Rev Time 0.00
Received By mawillia Date 2009-08-20 Time 11:14 Sent To  
Notes
2009-08-20 11:50:16*****DENIED*****
  
 1. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2. ON THE COVER SHEET (C1), THE DRAWING INDEX INDICATES
 THAT SHEET 1.1A IS THE LIFE SAFETY / REFECTED CEILING
 PLAN; HOWEVER A SECOND 1.0A SHEET IS IN THE SUBMITTED
 PLAN SET.
  
 3. PROVIDE DIRECTIONAL INDICATOR FOR THE LAYOUT OF THE
 PROJECT FLOOR PLAN.
  
 4. IT IS INDICATED ON THE LIFE SAFETY PLAN AND THE
 POWER PLAN OF HORN STROBE NEAR A DOOR. DOES THIS
 BUILDING HAVE A FIRE ALARM SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 09:56 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 09:56 Sent To  
Notes
2009-08-27 10:01:08B-3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-24 Time   Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 13:40 Sent To  
Notes
2009-08-11 13:40:33B-20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-01 Cont ID  
Sent By rregueir Date 2009-09-01 Time 13:14 Rev Time 0.00
Received By rregueir Date 2009-09-01 Time 13:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By rregueir Date 2009-08-24 Time 17:34 Rev Time 0.00
Received By rregueir Date 2009-08-24 Time 17:34 Sent To  
Notes
2009-08-24 17:36:12MECHANICAL SCOPE WAS REVIEWED FOR CODE COMPLIANCE AND
 PASSED. REVIEW WILL REMAIN IN FAIL STATUS PENDING
 RESUBMISSION OF M PAGE WITH CORRECTED ADDRESS AND
 CORRECTED PLUMBING ISSUES TO ASSURE REVISED PLAN IS
 ROUTED TO MECHANICAL FOR STAMPING UPON RESUBMISSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-27 Cont ID  
Sent By kstevens Date 2009-08-27 Time 11:17 Rev Time 0.00
Received By kstevens Date 2009-08-27 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By kstevens Date 2009-08-14 Time 14:41 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 14:41 Sent To  
Notes
2009-08-14 14:53:01DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. THE ADDRESS ON THE APPLICATION IS INDICATED AS 100 S
 DIXIE HWY, BUT THE TITLE BLOCK OF EACH SHEET INDICATES
 THE ADDRESS AS 340 DIXIE HWY. PLEASE CORRELATE THE
 ADDRESS IN THE TITLE BLOCKS WITH THE ADDRESS OF RECORD
 FOR THE PCN NUMBER. SECTION 106.1.1.
  
 2. INDICATE THE USE OF THE ROOM WITH THE SINK
 INSTALLED. SECTION 106.1.2, (MORE INFORMATION
 REQUIRED). IF SINK IS REQUIRED TO BE ACCESSIBLE, THEN
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS.
  
 3. A DRINKING FOUNTAIN IS REQUIRED. TABLE 403.1. SHOW
 THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN.
  
 4. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULITY BENDING OR STOOPING.
  
 5. SHT3.0M SANITARY RISER DIAGRAM. A CHECK VALVE AND A
 FULL OPEN VALVE ON THE DISCHARGE SIDE OF THE CHECK
 VALVE SHALL BE INSTALLED IN THE PUMP OR EJECTOR
 DISCHARGE PIPING BETWEEN THE PUMP OR EJECTOR AND THE
 GRAVITY DRAINAGE SYSTEM. SECTION 712.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-08-20 Cont ID  
Sent By aaponte Date 2009-08-20 Time 08:22 Rev Time 0.00
Received By aaponte Date 2009-08-20 Time 08:22 Sent To  
Notes
2009-08-20 08:23:18ALL INTERIOR RENOVATION.