Plan Review Details - Permit 09080173
Plan Review Stops For Permit 09080173
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-11 Cont ID  
Sent By kconrad Date 2009-08-11 Time 08:41 Rev Time 0.00
Received By kconrad Date 2009-08-11 Time 08:40 Sent To  
Notes
2009-08-17 08:59:10PERFORMED A PRELIMINARY INSPECTION ON THE LOW SLOPE
 ROOF AT THE GARAGE:
  
 1) THE CEILING DRYWALL WAS SATURATED WITHIN THE GARAGE
 AND WAS COLLAPSING: 3' X 3' SECTION.
  
 2) INSPECTED THE EXISTING CONDITION OF THE ROOF AND
 OBSERVED THAT THE OLD ROOFING SYSTEM WAS INFILTRATED
 WITH MOISTURE. ALSO, IT APPEARED THAT THERE WAS
 PREVIOUS REPAIRS UNDERTAKEN: MODIFIED CAP SHEETS OVER
 EXISTING MODIFIED MEMBRANE.
  
 3) DUE TO THE EXISTING CONDITIONS, A REROOF IS
 NECESSARY PURSUANT TO THE FLORIDA EXISTING BUILDING
 CODE, SECTION 611.3 (1),(5).