Plan Review Details - Permit 09080161
Plan Review Stops For Permit 09080161
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-28 Cont ID  
Sent By dpalmer Date 2009-10-28 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2009-10-28 Time 14:34 Sent To Z
Notes
2009-10-28 14:34:58NEW SHEETS INSERTED INTO SETS BY PLAN REVIEW. SENT TO
 ZONING AS NEW SHEETS NEED STAMPS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-10-23 Cont ID  
Sent By dpalmer Date 2009-10-23 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2009-10-23 Time 14:33 Sent To  
Notes
2009-10-28 14:33:15SHEETS SUBMITTED DO NOT SHOW ANY SET BACKS FOR FENCE OR
 CLEARENCES. CALLED AND SPOKE TO ENGINEER AND NEW SHEETS
 WILL BE SENT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-10-08 Cont ID  
Sent By dpalmer Date 2009-10-08 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 09:58 Sent To  
Notes
2009-10-08 09:58:47 
 ** TEMPORARY FAILED**
  
 ** WAITING FOR THE FOLLOWING INFORMATION.
  
 1) NOTE: CALL WAS PLACED TO PUBLIX CORPORATE OFFICE TO
 OBTAIN COPY OF CONTRACT FOR SCOPE OF WORK TO VERIFY
 VALUE.
 FBC 108.3
  
 2) NOTE: NEW REVISED ELECTRICAL/GENERATOR SITE PLANS
 WERE SUBMITTED. THE ENGINEER AS SIGNED AND SEALED ON
 SHEETS IS NOT THE ENGINEER AS LISTED ON TITLE BLOCKS AS
 THE RESPONSIBLE DESIGNER OF RECORD. A CALL WAS PLACED
 TO THE ENGINEER'S PHONE NUMBER AS LISTED ON TITLE BLOCK
 HOWEVER THIS NUMBER IS NO LONGER THE NUMBER OF THE
 ENGINEER OF RECORD.
 FS 471.025, FAC 61G15-23.002
  
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-27 Cont ID  
Sent By dpalmer Date 2009-08-27 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2009-08-20 Time 16:02 Sent To PC
Notes
2009-08-27 08:08:37 
 ** DENIED REVIEW **
  
 ** SPOKE TO PUBLIX MAIN OFFICE AND ALL FENCES AROUND
 GENERATORS WILL BE RE-REVIEWED BY THE CORPORATE OFFICE.
 PLANS WILL ALL NEED TO BE REVISED FOR MOST PROJECTS.
  
 1) NOTE: PLEASE PROVIDE MINIMUM CLEARANCES FOR
 GENERATOR PER 110.26. THE PLANS INDICATE 1FT 2INCHES.
 PLEASE ALSO CHECK WITH THE MANUFACTURE AS THERE ARE
 MINIMUM CLEARANCE REQUIREMENTS ALSO FOR VENTILATION.
 110.3,90.7 ETC
  
 2) NOTE: MAY NOT SUBMIT PLANS DONE BY AN ENGINEER FOR
 PERMITTING AND RECORD PLANS UNLESS SIGNED, DATED AND
 SEALED BY SAID ENGINEER.
 FS 471.025
 FAC61G15-23.002
  
 3) NOTE: PLEASE BE SURE TITLE BLOCK INCLUDES THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL
 FIRM. FS 481.221, FAC 61G1-16.004
  
 4) NOTE: PLEASE SEE PLANS ARE NOTING DESIGN PER 2004
 FBC, ASCE-7-02, 90MPH, EXPOSURE *C*.
 PLEASE CHECK DESIGN.
 THE WIND ZONE IN THE CITY OF WEST PALM BEACH IS 140MPH,
 3SEC GUST.
 PLEASE ALSO KNOW AS OF MARCH 1ST, 2009 THE STATE OF
 FLORIDA ADOPTED THE 2007 FBC WITH THE 2009 GLITCH
 AMENDMENTS.
 PLEASE KNOW THAT THERE WERE CHANGES IN EXPOSURE
 CATEGORIES.
 THIS JURISDICTION IS NOT REVIEWING FOR DESIGN OF FENCE
 MEETING MINIMUM CODE HOWEVER PLANS SUBMITTED FOR
 PERMITTING ARE REQUIRED TO CONTAIN CORRECT CODES.
 PLEASE BE SURE TO VERIFY FOR PUBLIX CORPORATE OFFICES
 FOR MINIMUM DESIGNS.
  
 5) NOTE: PLEASE BE SURE TO COORDINATE PLANS. ELECTRICAL
 SHEETS STATE 10FT 6INCHES ON FENCE AND SHEET PVC5
 STATES 10FT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2009-08-20 16:03:08GAVE TO DEWEY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-08-20 Cont ID  
Sent By dlauderm Date 2009-08-20 Time 11:46 Rev Time 0.25
Received By dlauderm Date 2009-08-20 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-27 Time   Rev Time 0.00
Received By lmartine Date 2009-08-10 Time 14:44 Sent To  
Notes
2009-08-10 14:43:50IN ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2009-11-02 Cont ID  
Sent By kdfreema Date 2009-11-02 Time 09:42 Rev Time 0.00
Received By kdfreema Date 2009-11-02 Time 09:42 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-07 Cont ID  
Sent By kdfreema Date 2009-10-07 Time 14:15 Rev Time 0.00
Received By kdfreema Date 2009-10-07 Time 14:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-14 Cont ID  
Sent By kdfreema Date 2009-08-14 Time 11:49 Rev Time 0.00
Received By kdfreema Date 2009-08-14 Time 11:49 Sent To  
Notes
***NONE***