Plan Review Details - Permit 09080160
Plan Review Stops For Permit 09080160
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-19 Cont ID  
Sent By dpalmer Date 2009-08-19 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2009-08-19 Time 15:21 Sent To ENG
Notes
2009-08-19 15:21:40 
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE PROVIDE MINIMUM CLEARANCES FOR
 GENERATOR PER 110.26. THE PLANS INDICATE 2FT 6INCHES.
 PLEASE ALSO CHECK WITH THE MANUFACTURE AS THERE ARE
 MINIMUM CLEARANCE REQUIREMENTS ALSO FOR VENTILATION.
 110.3,90.7 ETC
  
 2) NOTE: MAY NOT SUBMIT PLANS DONE BY AN ENGINEER FOR
 PERMITTING AND RECORD PLANS UNLESS SIGNED, DATED AND
 SEALED BY SAID ENGINEER.
 FS 471.025
 FAC61G15-23.002
  
 3) NOTE: PLEASE BE SURE TITLE BLOCK INCLUDES THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL
 FIRM. FS 481.221, FAC 61G1-16.004
  
 4) NOTE: PLEASE SEE PLANS ARE NOTING DESIGN PER 2004
 FBC, ASCE-7-02, 90MPH, EXPOSURE *C*.
 PLEASE CHECK DESIGN.
 THE WIND ZONE IN THE CITY OF WEST PALM BEACH IS 140MPH,
 3SEC GUST.
 PLEASE ALSO KNOW AS OF MARCH 1ST, 2009 THE STATE OF
 FLORIDA ADOPTED THE 2007 FBC WITH THE 2009 GLITCH
 AMENDMENTS.
 PLEASE KNOW THAT THERE WERE CHANGES IN EXPOSURE
 CATEGORIES.
 THIS JURISDICTION IS NOT REVIEWING FOR DESIGN OF FENCE
 MEETING MINIMUM CODE HOWEVER PLANS SUBMITTED FOR
 PERMITTING ARE REQUIRED TO CONTAIN CORRECT CODES.
 PLEASE BE SURE TO VERIFY FOR PUBLIX CORPORATE OFFICES
 FOR MINIMUM DESIGNS.
  
 5) NOTE: PLEASE BE SURE TO COORDINATE PLANS. ELECTRICAL
 SHEETS STATE 10FT 6INCHES ON FENCE AND SHEET PVC5
 STATES 10FT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-08-27 Cont ID  
Sent By dpalmer Date 2009-08-27 Time 08:05 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-08-27 08:06:10OK PER DL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-30 Cont ID  
Sent By jgomez Date 2009-09-30 Time 10:02 Rev Time 0.00
Received By jgomez Date 2009-09-30 Time 10:02 Sent To Z
Notes
2009-09-30 10:03:02SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-27 Time   Rev Time 0.00
Received By lmartine Date 2009-08-10 Time 14:42 Sent To  
Notes
2009-08-10 14:43:01IN ZONING

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By rkussner Date 2009-08-13 Time 16:53 Rev Time 0.00
Received By rkussner Date 2009-08-13 Time 16:53 Sent To  
Notes
2009-08-13 17:08:12***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE IDENTIFY THE PROPOSED PLANT MATERIAL BY NAME
 AND INDICATE THE QUANTITY, SIZE AND SPACING.
  
 2. THE PLANT BED SHALL BE MULCHED AND IRRIGATED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By lfranco Date 2009-08-13 Time 16:33 Rev Time 0.00
Received By lfranco Date 2009-08-13 Time 16:33 Sent To E
Notes
2009-08-13 16:45:53PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE LANDSCAPE INFORMATION, PURSUANT TO LANDSCAPE
 REVIEW.
  
 3. THE LOCATION OF THE FENCE NEEDS TO MEET THE
 CLEARANCE REQUIREMENTS FOR THE GENERATOR, PURSUANT TO
 THE ELECTRICAL REVIEW. IF THE LOCATION IS DEEMED TO BE
 TOO CLOSE TO THE GENERATOR, THEN A DIFFERENT TYPE OF
 FENCE, SUCH AS A METAL LOUVERED FENCE MAY BE
 APPROPRIATE TO ALLOW FOR VENTILATION. PLEASE CONTACT ME
 FOR FURTHER DETAILS, IF NEEDED.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 822-1443
 EMAIL: [email protected]