Plan Review Details - Permit 09080160
Plan Review Stops For Permit 09080160 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-08-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-08-19 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-08-19 |
Time |
15:21 |
Sent To |
ENG |
|
Notes |
2009-08-19 15:21:40 | | | | | ** DENIED REVIEW ** | | | | 1) NOTE: PLEASE PROVIDE MINIMUM CLEARANCES FOR | | GENERATOR PER 110.26. THE PLANS INDICATE 2FT 6INCHES. | | PLEASE ALSO CHECK WITH THE MANUFACTURE AS THERE ARE | | MINIMUM CLEARANCE REQUIREMENTS ALSO FOR VENTILATION. | | 110.3,90.7 ETC | | | | 2) NOTE: MAY NOT SUBMIT PLANS DONE BY AN ENGINEER FOR | | PERMITTING AND RECORD PLANS UNLESS SIGNED, DATED AND | | SEALED BY SAID ENGINEER. | | FS 471.025 | | FAC61G15-23.002 | | | | 3) NOTE: PLEASE BE SURE TITLE BLOCK INCLUDES THE | | CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL | | FIRM. FS 481.221, FAC 61G1-16.004 | | | | 4) NOTE: PLEASE SEE PLANS ARE NOTING DESIGN PER 2004 | | FBC, ASCE-7-02, 90MPH, EXPOSURE *C*. | | PLEASE CHECK DESIGN. | | THE WIND ZONE IN THE CITY OF WEST PALM BEACH IS 140MPH, | | 3SEC GUST. | | PLEASE ALSO KNOW AS OF MARCH 1ST, 2009 THE STATE OF | | FLORIDA ADOPTED THE 2007 FBC WITH THE 2009 GLITCH | | AMENDMENTS. | | PLEASE KNOW THAT THERE WERE CHANGES IN EXPOSURE | | CATEGORIES. | | THIS JURISDICTION IS NOT REVIEWING FOR DESIGN OF FENCE | | MEETING MINIMUM CODE HOWEVER PLANS SUBMITTED FOR | | PERMITTING ARE REQUIRED TO CONTAIN CORRECT CODES. | | PLEASE BE SURE TO VERIFY FOR PUBLIX CORPORATE OFFICES | | FOR MINIMUM DESIGNS. | | | | 5) NOTE: PLEASE BE SURE TO COORDINATE PLANS. ELECTRICAL | | SHEETS STATE 10FT 6INCHES ON FENCE AND SHEET PVC5 | | STATES 10FT. | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2009-08-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-08-27 |
Time |
08:05 |
Rev Time |
|
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2009-08-27 08:06:10 | OK PER DL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-09-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-09-30 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-09-30 |
Time |
10:02 |
Sent To |
Z |
|
Notes |
2009-09-30 10:03:02 | SENT TO ZONING BOX. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-08-27 |
Time |
|
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-08-10 |
Time |
14:42 |
Sent To |
|
|
Notes |
2009-08-10 14:43:01 | IN ZONING |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2009-08-13 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2009-08-13 |
Time |
16:53 |
Sent To |
|
|
Notes |
2009-08-13 17:08:12 | ***LANDSCAPE REVIEW FAILED*** | | | | 1. PLEASE IDENTIFY THE PROPOSED PLANT MATERIAL BY NAME | | AND INDICATE THE QUANTITY, SIZE AND SPACING. | | | | 2. THE PLANT BED SHALL BE MULCHED AND IRRIGATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2009-08-13 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2009-08-13 |
Time |
16:33 |
Sent To |
E |
|
Notes |
2009-08-13 16:45:53 | PLANNING AND ZONING: **** FAILED **** | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | 2. PROVIDE LANDSCAPE INFORMATION, PURSUANT TO LANDSCAPE | | REVIEW. | | | | 3. THE LOCATION OF THE FENCE NEEDS TO MEET THE | | CLEARANCE REQUIREMENTS FOR THE GENERATOR, PURSUANT TO | | THE ELECTRICAL REVIEW. IF THE LOCATION IS DEEMED TO BE | | TOO CLOSE TO THE GENERATOR, THEN A DIFFERENT TYPE OF | | FENCE, SUCH AS A METAL LOUVERED FENCE MAY BE | | APPROPRIATE TO ALLOW FOR VENTILATION. PLEASE CONTACT ME | | FOR FURTHER DETAILS, IF NEEDED. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 822-1443 | | EMAIL: [email protected] |
|
|
|