Plan Review Details - Permit 09080099
Plan Review Stops For Permit 09080099
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-25 Cont ID  
Sent By kstevens Date 2010-02-25 Time 09:21 Rev Time 0.00
Received By kstevens Date 2010-02-25 Time 09:21 Sent To  
Notes
2010-02-25 09:22:02SENT TO PLMG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 08:33 Rev Time 0.00
Received By kstevens Date 2009-08-06 Time 09:10 Sent To  
Notes
2009-08-06 09:10:53IN PLUMBING BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-03-23 Cont ID  
Sent By lwagner Date 2010-03-23 Time 14:25 Rev Time 0.00
Received By lwagner Date 2010-03-23 Time 14:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-03-01 Cont ID  
Sent By kstevens Date 2010-03-01 Time 13:12 Rev Time 0.00
Received By kstevens Date 2010-03-01 Time 13:12 Sent To  
Notes
2010-03-01 13:32:15DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CONSTRUCTION INDUSTRY LICENSING BOARD OF PALM BEACH
 COUNTY
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLANS WERE SUBMITTED BY THE GENERAL CONTRACTOR.
 ACCORDING TO THE STANDARDS FOR CERTIFIED CATEGORIES PE
 CHAPTER 67-1876 AS AMENDED; GENERAL CONTRACTORS: SHALL
 SUBCONTRACT TO A QUALIFIED CONTRACTOR ALL WORK WHICH IS
 THE EXCLUSIVE WORK OF PLUMBING UNLESS SUCH CONTRACTOR
 ALSO HOLDS A CERTIFICATE OF COMPETENCY OF THE
 RESPECTIVE TRADE CATEGORY, PROVIDED, THAT ON NEW SITE
 DEVELOPMENT WORK, SITE REDEVELOPMENT WORK, MOBILE HOME
 PARKS, COMMERCIAL PROPERTIES AND UTILITY WORK WITHIN
 PUBLIC RIGHT-OF-WAY AND DESIGNATED EASEMENTS, THE
 OBLIGATION TO SUBCONTRACT SHALL NOT PROHIBIT THE
 GENERAL CONTRACTOR FROM CONSTRUCTING THE MAIN SANITARY
 SEWER COLLECTION SYSTEM AND THE MAIN WATER DISTRIBUTION
 SYSTEM INCLUDING THE CONTINUATION OF UTILITY LINES FROM
 THE MAINS TO A DESIGNATED TERMINATION POINT IN THE
 RIGHT-OF WAY OR EASEMENT, AFTER WHICH UTILITY LINES
 SHALL BE CONSTRUCTED BY PLUMBING CONTRACTORS. -- AN
 IRRIGATION CONTRACTOR IS REQUIRED TO DO THE IRRIGATION
 WORK.
 ****NO RESPONSE, SEE NEW COMMENT.
  
 2. PLANS SUBMITTED FOR REVIEW HAVE IN THE TITLE BLOCKS
 A DISCLAIMER WHICH STATES: "ALL DRAWINGS,
 SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHT
 PROPERTY OF THE LANDSCAPE ARCHITECT AND MUST BE
 RETURNED UPON REQUEST. REPRODUCTION OF DRAWINGS,
 SPECIFICATION AND RELATED DOCUMENTS IN PART OR WHOLE IS
 FORBIDDEN WITHOUT THE LANDSCAPE ARCHITECTS WRITTEN
 PERMISSION. -- PLEASE PROVIDE THE WRITTEN PERMISSION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. PLANS SUBMITTED ONLY SHOW THE MASTER IRRIGATION PLAN
 FOR THE PROJECT. THE IRRIGATION FOR BUILDING 9 IS NOT
 INDICATED. PLEASE SUBMIT THE PLANS FOR BUILDING 9 WITH
 THE MASTER IRRIGATION PLAN. THE MASTER PLAN SHALL ALSO
 SHOW THE CONTROLLER AND RAIN SENSOR AS REQUIRED IN
 APPENDIX F PART II (J) AND FS 373.62.
 ****NO RESPONSE, CONTROLLER & RAIN SENSOR NOT SHOWN.
  
 4. AS THE PROPERTIES ARE FEE SIMPLE TOWNHOUSES, THE
 IRRIGATION PIPING IS SHOWN CROSSING ACROSS PROPERTY
 LINES. PLEASE INDICATE IF THESE ARE UTILITY EASEMENTS,
 OR INDICATE HOW THE IRRIGATION LINES ARE ALLOWED TO
 CROSS PROPERTY LINES.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ******NEW COMMENTS******
  
 1B. PER FS 489.113(D) THE GENERAL CONTRACTOR IS NOT
 ALLOWED TO INSTALLATION THE CONTINUATION OF UTILITY
 LINES FROM THE MAINS TO THE BUILDINGS.
  
 2B. SEPARATE PERMITS ARE REQUIRED FOR EACH INDIVIDUAL
 FEE SIMPLE TOWNHOUSE. PERMIT SUBMITTED IS FOR THE
 BUILDING.
  
 3B. NEW PLANS SUBMITTED SHOW THE IRRIGATION CROSSING
 ACROSS PROPERTY LINES. THIS IS NOT APPROVED. SEE
 COMMENT 4 ABOVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 08:33 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 08:33 Sent To  
Notes
2009-08-07 09:38:45DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CONSTRUCTION INDUSTRY LICENSING BOARD OF PALM BEACH
 COUNTY
  
 1. PLANS WERE SUBMITTED BY THE GENERAL CONTRACTOR.
 ACCORDING TO THE STANDARDS FOR CERTIFIED CATEGORIES PE
 CHAPTER 67-1876 AS AMENDED; GENERAL CONTRACTORS: SHALL
 SUBCONTRACT TO A QUALIFIED CONTRACTOR ALL WORK WHICH IS
 THE EXCLUSIVE WORK OF PLUMBING UNLESS SUCH CONTRACTOR
 ALSO HOLDS A CERTIFICATE OF COMPETENCY OF THE
 RESPECTIVE TRADE CATEGORY, PROVIDED, THAT ON NEW SITE
 DEVELOPMENT WORK, SITE REDEVELOPMENT WORK, MOBILE HOME
 PARKS, COMMERCIAL PROPERTIES AND UTILITY WORK WITHIN
 PUBLIC RIGHT-OF-WAY AND DESIGNATED EASEMENTS, THE
 OBLIGATION TO SUBCONTRACT SHALL NOT PROHIBIT THE
 GENERAL CONTRACTOR FROM CONSTRUCTING THE MAIN SANITARY
 SEWER COLLECTION SYSTEM AND THE MAIN WATER DISTRIBUTION
 SYSTEM INCLUDING THE CONTINUATION OF UTILITY LINES FROM
 THE MAINS TO A DESIGNATED TERMINATION POINT IN THE
 RIGHT-OF WAY OR EASEMENT, AFTER WHICH UTILITY LINES
 SHALL BE CONSTRUCTED BY PLUMBING CONTRACTORS. -- AN
 IRRIGATION CONTRACTOR IS REQUIRED TO DO THE IRRIGATION
 WORK.
  
 2. PLANS SUBMITTED FOR REVIEW HAVE IN THE TITLE BLOCKS
 A DISCLAIMER WHICH STATES: "ALL DRAWINGS,
 SPECIFICATIONS AND RELATED DOCUMENTS ARE THE COPYRIGHT
 PROPERTY OF THE LANDSCAPE ARCHITECT AND MUST BE
 RETURNED UPON REQUEST. REPRODUCTION OF DRAWINGS,
 SPECIFICATION AND RELATED DOCUMENTS IN PART OR WHOLE IS
 FORBIDDEN WITHOUT THE LANDSCAPE ARCHITECTS WRITTEN
 PERMISSION. -- PLEASE PROVIDE THE WRITTEN PERMISSION.
  
 3. PLANS SUBMITTED ONLY SHOW THE MASTER IRRIGATION PLAN
 FOR THE PROJECT. THE IRRIGATION FOR BUILDING 9 IS NOT
 INDICATED. PLEASE SUBMIT THE PLANS FOR BUILDING 9 WITH
 THE MASTER IRRIGATION PLAN. THE MASTER PLAN SHALL ALSO
 SHOW THE CONTROLLER AND RAIN SENSOR AS REQUIRED IN
 APPENDIX F PART II (J) AND FS 373.62.
  
 4. AS THE PROPERTIES ARE FEE SIMPLE TOWNHOUSES, THE
 IRRIGATION PIPING IS SHOWN CROSSING ACROSS PROPERTY
 LINES. PLEASE INDICATE IF THESE ARE UTILITY EASEMENTS,
 OR INDICATE HOW THE IRRIGATION LINES ARE ALLOWED TO
 CROSS PROPERTY LINES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  