Plan Review Details - Permit 09080089
Plan Review Stops For Permit 09080089
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-10-19 Cont ID  
Sent By jwitmer Date 2009-10-19 Time 18:13 Rev Time 1.25
Received By jwitmer Date 2009-10-19 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 18:00 Rev Time 1.00
Received By jwitmer Date 2009-09-09 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-10 Cont ID  
Sent By jwitmer Date 2009-08-10 Time 13:14 Rev Time 4.50
Received By jwitmer Date 2009-08-07 Time 12:30 Sent To  
Notes
2009-08-10 13:19:27BUILDING PLAN REVIEW
 PERMIT: 09080089
 ADD: 550 S ROSEMARY SUITE# 236 "BB KING"
 CONT: WATLEE CONSTRUCTION
 TEL: (772)2230604
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: CRAIG MOSSEY P. A. (561)447-2911
  
 MEP: BUCHANAN P. E. CONSULTING, KAMAL AL HALABI P. E.
 (954)950-2232
 TNOTE4: SHEET A-0.0 ALTHOUGH THIS BUILDING IS
 CONSIDERED A THRESHOLD BUILDING UNDER 553.79 ,NO
 THRESHOLD INSPECTION REPORT NOR THRESHOLD INSPECTOR
 WILL BE REQUIRED. THE BUILDING OFFICIAL REVIEWED 553.79
 AND WITHIN THE LANGUAGE FOR A THRESHOLD BUILDING THE
 INSPECTION REPORT AND INSPECTOR ARE REQUIRED "WHEN
 CONSTRUCTING" NOT REMODELING.
  
 1ST REVIEW
 ACTION:
  
 1) SHEET LS-1.0 ROOM# 102:
 1A) THE OCCUPANT LOAD FOR THIS ROOM IS OFF, PLANS ARE
 INDICATED AS 32 WHERE AS THERE ARE 44 ACTUAL SEATS,
 PLEASE CORRECT.106.1.2 ADDITIONAL INFORMATION, THIS
 WILL EFFECT ONE OF THE EXIT WAYS WITH THE ADDITIONAL
 LLOADING.
  
 1B) COMPLIED.
  
 2) SHEET LS-1.0 TWO AREAS OF CONCERN FOR OCCUPANT
 LOADING IS THE BENCH SEATINGIS THE BENCH OR BOOTH STYLE
 SEATING IN BOTH ROOMS 110 AND 111 PLEASE PROVIDE A
 BREAK DOWN OF OCCUPANTS FOR THESE ROOM AS PEROCCUPANTS
 IN CHAIRS AND BENCH OR BOOTH TYPE SEATING. 1004.7.
 AGAIN THIS MAY EFFECT THE EXIT PATERNS FOR THESE AREAS.
  
 3A) SHEET LS-1.0 INDICATES ACCESSIBLE SEATING IN ROOM
 100, 102 AND 201. I DON'T BELIEVE THERE WERE ANY
 ACCESSIBLE SEATING INDICATED IN THE THEATER SECTION .
 11-2.2 EQUIVALENT FACILITATION. DEPARTURES FROM
 PARTICULAR TECHNICAL AND SCOPING REQUIREMENTS OF THIS
 CODE BY THE USE OF OTHER DESIGNS AND TECHNOLOGIES ARE
 PERMITTED WHERE THE ALTERNATIVE DESIGNS AND
 TECHNOLOGIES USED WILL PROVIDE SUBSTANTIALLY EQUIVALENT
 OR GREATER ACCESS TO AND USABILITY OF THE FACILITY.
  
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 3B) 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY
 REFERENCE SECTION 11-4.1 SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING
 REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
  
 4) SHEET LS-1.0 FIRE EXTINGUISHERS THREE ARE INDICATED
 ON THE PLANS LOCATED IN ROOMS 107, KITCHEN, 124 SERVICE
 AREA AND NEW SERVICE BAR BY DOOR 13. IT APPEARS THERE
 ARE NO EXTINGUISHERS BY TTHE EXISTING EXTERIOR DINING
 AREA 202OR NEW BAR 103. 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE. SHEET A-2.0 HAS A NOT ABOUT FIRE EXTINGUISHERS TO
 BE LOCATED MAXIMUM 75' BETWEEN FIRE EXTINUISHERS.
  
 5A) SHEET A-2.0 INDICATES IN THE WALL LEGEND A WALL
 TYPE X1 WITH USE FOR A MECHANICAL PLATFORM ABOVE. SHEET
 M-1.0 INDICATES A MEZZANINE ABOVE THE STAIRWAY AND
 NOTE:
 ALL PENETRATIONSTHROUGH THE MEZZANINE SHALL HAVE A FIRE
 DAMPER. PLEASE PROVIDE ADDITIONAL INFORMATION ABOUT A
 MEZZANINE LEVEL, HOW YOU GAIN ACCESS AND WHERE IS ITS
 LOCATION?
 106.1.2. SHEET A-2.2 NEW WALLS SURROUNDING THE KITCHEN
 AND RESTROOMS APPEAR TO BE BUILT WITH THE DESINATION OF
 "A,B & H" WHAT WALL TYPE ARE THESE, THE WALL LEGEND ON
 A-2.0 DOES NOT INDICATE SUCH WALL TYPES?
  
 5) SHEET M-1.0 INDICATES WHAT APPEARS TO BE A DUCT THAT
 PASSES DOWN INTO THE RATED VERTICAL STAIRWELL EXIT?
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 6) SHEET M-1.0 DOES NOTE NEW ROOF TOP UNITS. PLEASE
 REVIEW 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
2009-08-08 11:02:58BUILDING PLAN REVIEW
 PERMIT: 09080089
 ADD: 550 S ROSEMARY SUITE# 236 "BB KING"
 CONT: WATLEE CONSTRUCTION
 TEL: (772)2230604
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: CRAIG MOSSEY P. A. (561)447-2911
  
 MEP: BUCHANAN P. E. CONSULTING, KAMAL AL HALABI P. E.
 (954)950-2232
 TNOTE4: SHEET A-0.0 ALTHOUGH THIS BUILDING IS
 CONSIDERED A THRESHOLD BUILDING UNDER 553.79 ,NO
 THRESHOLD INSPECTION REPORT NOR THRESHOLD INSPECTOR
 WILL BE REQUIRED. THE BUILDING OFFICIAL REVIEWED 553.79
 AND WITHIN THE LANGUAGE FOR A THRESHOLD BUILDING THE
 INSPECTION REPORT AND INSPECTOR ARE REQUIRED "WHEN
 CONSTRUCTING" NOT REMODELING.
  
 1ST REVIEW
 ACTION:
  
 1) SHEET LS-1.0 ROOM# 102:
 1A) THE OCCUPANT LOAD FOR THIS ROOM IS OFF, PLANS ARE
 INDICATED AS 32 WHERE AS THERE ARE 44 ACTUAL SEATS,
 PLEASE CORRECT.106.1.2 ADDITIONAL INFORMATION, THIS
 WILL EFFECT ONE OF THE EXIT WAYS WITH THE ADDITIONAL
 LLOADING.
  
 1B) FROM TTHE FARTHEST SEAT LEFT OF THE DOORWAY TO THE
 POINT WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS
 OF EGRESS EXCEEDS 30'.
 1014.4.3.3 TABLE AND SEATING AISLE ACCESSWAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A
 PERSON HAS A CHOICE OF TWO OR MORE PATHS OF EGRESS
 TRAVEL TO SEPARATE EXITS.
  
 2) SHEET LS-1.0 TWO AREAS OF CONCERN FOR OCCUPANT
 LOADING IS THE BENCH SEATINGIS THE BENCH OR BOOTH STYLE
 SEATING IN BOTH ROOMS 110 AND 111 PLEASE PROVIDE A
 BREAK DOWN OF OCCUPANTS FOR THESE ROOM AS PEROCCUPANTS
 IN CHAIRS AND BENCH OR BOOTH TYPE SEATING. 1004.7.
 AGAIN THIS MAY EFFECT THE EXIT PATERNS FOR THESE AREAS.
  
 3A) SHEET LS-1.0 INDICATES ACCESSIBLE SEATING IN ROOM
 100, 102 AND 201. I DON'T BELIEVE THERE WERE ANY
 ACCESSIBLE SEATING INDICATED IN THE THEATER SECTION .
 11-2.2 EQUIVALENT FACILITATION. DEPARTURES FROM
 PARTICULAR TECHNICAL AND SCOPING REQUIREMENTS OF THIS
 CODE BY THE USE OF OTHER DESIGNS AND TECHNOLOGIES ARE
 PERMITTED WHERE THE ALTERNATIVE DESIGNS AND
 TECHNOLOGIES USED WILL PROVIDE SUBSTANTIALLY EQUIVALENT
 OR GREATER ACCESS TO AND USABILITY OF THE FACILITY.
  
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 3B) 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY
 REFERENCE SECTION 11-4.1 SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING
 REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
  
 4) SHEET LS-1.0 FIRE EXTINGUISHERS THREE ARE INDICATED
 ON THE PLANS LOCATED IN ROOMS 107, KITCHEN, 124 SERVICE
 AREA AND NEW SERVICE BAR BY DOOR 13. IT APPEARS THERE
 ARE NO EXTINGUISHERS BY TTHE EXISTING EXTERIOR DINING
 AREA 202OR NEW BAR 103. 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE. SHEET A-2.0 HAS A NOT ABOUT FIRE EXTINGUISHERS TO
 BE LOCATED MAXIMUM 75' BETWEEN FIRE EXTINUISHERS.
  
 5A) SHEET A-2.0 INDICATES IN THE WALL LEGEND A WALL
 TYPE X1 WITH USE FOR A MECHANICAL PLATFORM ABOVE. SHEET
 M-1.0 INDICATES A MEZZANINE ABOVE THE STAIRWAY AND
 NOTE:
 ALL PENETRATIONSTHROUGH THE MEZZANINE SHALL HAVE A FIRE
 DAMPER. PLEASE PROVIDE ADDITIONAL INFORMATION ABOUT A
 MEZZANINE LEVEL, HOW YOU GAIN ACCESS AND WHERE IS ITS
 LOCATION?
 106.1.2. SHEET A-2.2 NEW WALLS SURROUNDING THE KITCHEN
 AND RESTROOMS APPEAR TO BE BUILT WITH THE DESINATION OF
 "A,B & H" WHAT WALL TYPE ARE THESE, THE WALL LEGEND ON
 A-2.0 DOES NOT INDICATE SUCH WALL TYPES?
  
 5) SHEET M-1.0 INDICATES WHAT APPEARS TO BE A DUCT THAT
 PASSES DOWN INTO THE RATED VERTICAL STAIRWELL EXIT?
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 6) SHEET M-1.0 DOES NOTE NEW ROOF TOP UNITS. PLEASE
 REVIEW 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-16 Cont ID  
Sent By dpalmer Date 2009-10-16 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2009-10-16 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-11 Cont ID  
Sent By dpalmer Date 2009-09-11 Time 12:16 Rev Time 0.00
Received By dpalmer Date 2009-09-11 Time 12:16 Sent To  
Notes
2009-09-11 12:17:03** REDLINED PLANS **
  
  
 1) NOTE: OLD PREVIOUSLY SUBMITTED FORM B WAS STILL
 ATTACHED TO PLANS. THESE HAVE BEEN STAMPED *VOID*.
  
 2) NOTE: THE 250AMP BREAKER NOTED ON HVPP SHALL BE
 VERIFIED IN FIELD.
  
 3) NOTE: REDLINED ELECTRICAL PLANS TO SEE SHEET A5-5
 FOR NEW RATED ROOM FOR 150 KVA TRANSFORMER.
  
 4) NOTE: NO GROSS ERRORS ON LIGHTING PERFORMANCE
 CALCULATIONS PER 13-103.3
  
 5) NOTE: WENT OVER TENANT MAINS WITH JAKE LEAHY. ALL
 LABELING SHALL BE CLEAR, CONTRASTING BACK GROUNDS WITH
 MINIMUM OF 1 INCH LETTERING. ALL SIGNS SHALL BE
 PERMANENT.
  
 6) NOTE: ALL LIGHTING SHALL MEET MINIMUM LEVELS FOR
 LIFE SAFETY. NO EGRESS LIGHTING SHALL DIM BELOW MINIMUM
 LIGHTING LEVELS. ALL LEVELS SHALL BE VERIFIED BEFORE
 OCCUPANCY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-19 Cont ID  
Sent By dpalmer Date 2009-08-19 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2009-08-19 Time 19:34 Sent To  
Notes
2009-08-19 19:34:36 
  
  
  
  
  
 ** DENIED REVIEW **
  
 ** PLANS ARE MISSING INFORMATION NOT YET SHOWN. THERE
 ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM
 CODE COMPLIANCE AT THIS TIME. THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 POSSIBLY BE MADE AT THIS TIME> SEE NOTES.
  
 1) NOTE: PLEASE SEE THAT SOME OF THE CODE INFORMATION
 FOR MINIMUM DESIGNS LISTED ON COVER SHEET IS NOT
 CORRECT.
 PLANS INDICATE 2004 FBC FOR CHAPTER 11. HOWEVER AS OF
 MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE 2007
 FBC W/ 2009 SUPPLEMENTS. THIS INCLUDES CHAPTER 11 UNDER
 THE 2007 FBC.
 THE PLANS STATE THE 2004 FLORIDA FIRE PREVENTION CODE
 HOWEVER AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED THE
 2007 FFPC. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 69A-60
 PLEASE ALSO SEE THE SECTIONS 69A-60.003 AND .004 AS THE
 FOLLOWING NFPA-1 AND NFPA-101 ( LIFE SAFETY CODE ) IS
 ACTUALLY THE 2006 EDITIONS. PLANS STATE THE 2003
 EDITION OF NFPA-101.
  
 ** LIGHTING CONTROLS STATES TO MEET THE FBC WITH 2006
 SUPPLEMENTS. AS NOTED ABOVE THE 2006 SUPPLEMENTS WOULD
 BE UNDER THE 2004 FBC. NOT THE CURRENT 2007 FBC WITH
 2009 SUPPLEMENTS.
  
 2) NOTE: PLEASE PROVIDE SIGNED CONTRACTS OR ADJUST
 VALUE FOR COMPLETE SCOPE OF WORK AS THE APPLIED VALUE
 IS LOW. THE APPLIED VALUE SHALL INCLUDE ALL LABOR,
 MATERIALS, PERMANENTLY INSTALLED EQUIPMENT, DESIGN COST
 ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED.
 FBC 108.3
 THE APPLIED VALUE OF $200K FOR THE ENTIRE PROJECT IS
 LOW.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW BEING INSTALLED ALONG WITH
 EXISTING. PLEASE SEE 13-415.AB.5, 13-415.B. THE
 SUBMITTED SINGLE FORM B IS NOT ACCEPTABLE FOR SCOPE OF
 WORK AS SHOWN. FORM 400B IS PERMITTED HOWEVER THIS
 WOULD REQUIRE THIS SAME FOR EACH AND EVERY SPACE IN THE
 TENANT SPACE.
 PLEASE SEE 13-400.0.B.4 WHEN NOT MEETING THE DEFINITION
 OF *RENOVATION* OF A BUILDING THEN ALL NEW INSTALLED
 MUST MEET PRESCRIPTIVE REQUIREMENTS. SEE SECTIONS NOTED
 AND SEE SECTION 202 FOR DEFINITIONS.
 THE SUBMITTED INFORMATION ON PLANS IS OVER THE LIGHTING
 ALLOWANCES PERMITTED. PLEASE KNOW THE SPACE BY SPACE IS
 JUST THAT. SPACE BY SPACE ALLOWANCES MAY NOT USE FAMILY
 DINING ALLOWANCES FOR THE BATHROOMS, STORAGE ROOMS,
 ETC. THE BAR LOUNGE ALLOWANCES MAY NOT BE USED FOR THE
 OTHER TYPES OF AREAS. ALL SEPARATE SPACE MUST BE
 DESIGNATED.
 PLEASE ALSO KNOW THAT THAT LIGHTING ALLOWANCE WATTAGE
 SHOWN ON LIGHTING CONTROL PANELS ON SHEET E-5.0 IS
 HIGHER THAN THE DESIGN ON SHEET E-4.0.
 PLEASE KNOW AT THIS TIME DESIGN IS SUBSTANTIALLY OVER
 THE MAXIMUM ALLOWANCES PERMITTED BY THE ENERGY CODE.
 THIS IS BASED ON THE INFORMATION STATED AND SHOWN ON
 PLANS.
 ** FIXTURE WATTAGES ARE NOT BASED ON LIGHT BULBS, IT
 MUST BE FIGURED PER FIXTURE. * FIXTURE O FOR ONLY ONE
 EXAMPLE*
  
 ** IF THERE ARE QUESTIONS, IT IS RECOMMENDED TO CONTACT
 REVIEWER.
  
 4) NOTE: PLEASE SEE NFPA-101 7.10.8.3.1, .2. ANY EXIT
 WHICH COULD BE MISTAKEN FOR AN EXIT IN AN EMERGENCY
 SHALL BE IDENTIFIED WITH SIGNS PER SECTIONS NOTED.
 PLEASE PLACE NOTES ON ELECTRICAL PLANS ALONG WITH LIFE
 SAFETY PLANS FOR WORDS OF NO EXIT IN MINIMUM SIZE
 REQUIREMENTS.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR ALL
 DESIGNATED EGRESS PATHS UNDER NORMAL AND EMERGENCY
 CONDITIONS. PLEASE KEEP IN MIND THAT NO LIGHTING
 CONTROL OR DIMMING SYSTEM IS PERMITTED TO DIMINISH
 LIGHTING LEVELS BELOW THE MINIMUM. THIS SHALL BE SET
 AND SHALL NOT BE OVER RIDDEN. PLEASE SEE THAT ALL STAIR
 AREAS/STEPS SHALL CONTAIN THE MINIMUM OF 10FT CANDLES
 UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT CANDLE
 UNDER AN EMERGENCY.
 PLEASE SEE 7.8.1.3, 7.9.1.2, .2.2. PLEASE ALSO SEE
 7.8.1.2.2 FOR ANY REQUIRED EGRESS LIGHTING ON OCCUPANCY
 CONTROLS WHICH SHALL FAIL SAFE *ON*.
  
 6) NOTE: THE RISER, LOAD CALCULATIONS AND PANEL
 SCHEDULES SUBMITTED ALL NEED TO BE COMPLETE WITH THE
 FOLLOWING INFORMATION FOR REVIEW.
 FOR EXAMPLE:
  
 A) PLEASE SEE RISER ON SHEET E-7.0 WHICH CLEARLY
 INDICATES PANEL *HVPP* FEEDING 150KVA TRANSFORMER WITH
 A 250AMP BREAKER. HOWEVER PANEL SCHEDULE FOR THIS SAME
 *HVPP* DOES NOT LIST ANY SUCH BREAKER OR FEED TO THE
 TRANSFORMER.???
  
 B) PLEASE PROVIDE INFORMATION FOR WHERE *LVMDP* IS
 BEING FED FROM.
  
 C) PLEASE SEE *HVPP* WHICH DOES NOT INCLUDE ANY OF THE
 LOADS FOR THE LVMDP SUCH AS LIGHTING.
  
 D) THERE IS NO INFORMATION ON WHERE PANELS *H1 OR H2*
 ARE BEING FED FROM. ARE THESE FROM OTHER SERVICES? ARE
 THESE FROM MULTIPLE TENANT METERS?
 ARE MAINS GROUPED? LABELED? BONDED SERVICES? ETC
  
 E) RISER INDICATES #3 AWG AS THE SIZE OF THE NEW
 FEEDERS TO THE NEW PANEL *C* YET *LVMDP* INDICATES
 *3/0*AWG. THIS IS SUBSTANTIALLY DIFFERENT.
 PLEASE COORDINATE.
  
 F) RISER INDICATES THAT PANEL K IS BEING FED FROM THE
 TRANSFORMER AND PANEL H1. HOWEVER PANEL H1 STATES A
 FEED TO PANEL *P* NOT TO PANEL *K*.
  
 G) PANEL *P* IS SHOWN WITH FEED-THRU LUGS ON SCHEDULE
 HOWEVER THIS PANEL IS NOT SHOWN ON RISER FEEDING THRU
 TO ANY OTHER PANEL. IS THIS THE CASE?
  
 H) TRACK LIGHTING LOADS ARE NOT SHOWN PER 220.43B
  
 I) SHOW WINDOW LOADS NOT SHOWN PER 220.43A
  
 J) SHOW LOCATIONS OF ALL TRANSFORMERS ON
 PLANS.450.13,450.21,240.21, 310.16 ETC TO BE REVIEWED
 ALONG WITH 110.26, 450.9.
 RISER INDICATES THE 150KVA TRANSFORMER WHICH FEEDS FROM
 HVPP TO LVMDP, YET THE PLANS DOES NOT INDICATE THIS
 TRANSFORMER ANYWHERE NEAR THE PROXIMITY OF EITHER OF
 THESE. SEE 240.21 FOR TAPPED CONDUCTORS.
  
 K) PLEASE PROVIDE ALL CONDUCTORS ON THE SECONDARY SIDE
 OF THE TRANSFORMERS. SEE 240.21,310.16,240.4.
  
 *** PLEASE COORDINATE ALL OF THE ELECTRICAL SYSTEMS AND
 SUBMIT A COMPLETE RISER WITH LOAD CALCULATIONS AND
 SIZES FOR ALL SYSTEMS.
 SEVERAL EXAMPLES ARE GIVEN ABOVE TO SOME OF THE ITEMS
 WHICH ARE NOT COORDINATED OR PROVIDED. THERE ARE MANY
 ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM CODE
 COMPLIANCE AT THIS TIME. THESE ARE SOME EXAMPLES ONLY
 AND ARE IN NO WAY ALL.
  
 PLEASE SEE 220, 230.70, 230.71,230.72, 230.2E,310.16,
 240.21 ETC. THERE ARE TOO MANY SECTIONS TO NOTE.
 FBC 106.1.1,106.1.2,106.3.5.1.2 FOR CLARITY,
 COORDINATION OF RECORD PLANS.
  
 7) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR
 LIGHTING CONTROLS. PLEASE SEE SECTION 13-415.AB.1.3
 SPECIFICALLY FOR CONTROLS.
 ALSO SEE ITEMS LIKE THE FAN LIGHTS WHICH ARE SHOWN ON
 FAN CONTROLS.
 OTHER FIXTURES SUCH AS FIXTURES F AND OTHER LOCATIONS
 WHICH INDICATE OVER RIDES AS STANDARD SINGLE POLE
 SWITCH PER SYMBOL LEGEND WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING
 CONTROLS.
  
  
 9) NOTE: PLEASE SEE 210.8B2 FOR WET BAR AND KITCHEN
 AREA GFI PROTECTION REQUIRED.
  
 10) NOTE: PLEASE SEE NOTES ON E-4.0 WHICH INDICATE CODE
 SECTIONS FROM PREVIOUS FLORIDA BUILDING CODE. SUCH AS
 SECTIONS NOTED: 13-415.1.ABC.3.
  
 11) NOTE: PLEASE SHOW ALL DEVICES FOR FIRE ALARM HORNS,
 STROBES, ETC MEETING ADA PER FBC CHAPTER 11. EVEN AS
 THE FA SYSTEM/SCOPE IS UNDER SEPARATE PERMIT, PER FS
 633 MINIMUM DESIGN FOR FIRE AND LIFE SAFETY SHALL BE ON
 BASE PLANS. PLEASE SEE FBC 11-4.28.1,.2 AND .3.
  
 AS NOTED ABOVE, THERE ARE SEVERAL ITEMS IN NEED OF
 COORDINATION AND INFORMATION TO BE SUBMITTED FOR
 REVIEW. THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW.
  
 ** PER BUILDING OFFICIAL PLANS ARE NO LONGER RELEASED.
 ALL SHEETS TO BE REVISED OR CHANGED OUT IN THIS OFFICE.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 14:37 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 14:17 Sent To  
Notes
2009-10-26 14:37:28*****REVISION #3, DATED 10/09/2009, APPROVED*****
  
  
 REVISED SHEETS LS-1, A-2.1, A-3.1, A-5.1, AND E-2.0
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-10 Cont ID  
Sent By mcarsill Date 2009-09-10 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2009-09-10 Time 14:04 Sent To  
Notes
2009-09-11 10:58:27*****FIRE-STAMPED*****
  
 BASED UPON FIRE MARSHAL CARSILLO'S PLAN REVIEW APPROVAL
 OF 9/10/2009, SHEETS LS-1, A-2.0, A-3.1, A-5.1, A-7.1,
 E-2.0, AND FA-1.0 & FA-2.0 WERE STAMPED, INITIALED, AND
 DATED.
2009-09-10 14:10:29550 SOUTH ROSEMARY AVENUE
 0908080089
  
 1. CROWD MANAGEMENT CERTIFICATES ARE REQUIRES TO BE
 SUBMITTED TO THE FIRE MARSHAL'S OFFICE. ONE TRAINED
 CROWD MANAGER IS REQUIRED FOR EVERY 250 PERSONS.
 RESPONSE TO COMMENTS NARRATIVE INDICATES THAT CROWD
 MANAGEMENT TRAINING HAS ALREADY BEEN COMPLETED BY THE
 PROPOSED TENANT.
  
 2. A SEPARATE FIRE ALARM CONTROL PANEL IS NOT REQUIRED
 FOR THIS TENANT SPACE. THE DESIRED ARRANGMENT IS TO
 CONNECT THE TENANT IMPROVEMENT SYSTEM TO THE MAIN FIRE
 ALARM CONTROL PANEL FOR THE BUILDING. THIS SYSTEM DOES
 NOT NEED TO BE PROPRIETARY TO THE TENANT SPACE.
 SEPARATE PLANS AND PERMITS REQUIRED PRIOR TO THE
 INSTALLATION.
  
 3. THE UNISEX 115 RESTROOM IS MISSING A FIRE ALARM
 STROBE DEVICE.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-20 Cont ID  
Sent By mcarsill Date 2009-08-20 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2009-08-20 Time 14:28 Sent To  
Notes
2009-08-20 14:45:18550 SOUTH ROSEMARY AVENUE
 PERMIT # 09080089
 INTERIOR BUILD-OUT OF EXISTING RESTAURANT. BUILD-OUT IS
 PROVIDED PER PROVIDED PLANS.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO
 COMPLY WITH NFPA 241.
  
 2. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE.
  
 3. DERBIS IS TO BE REMOVED FROM THE SITE DAILY.
  
 4. CHAIRS APPEAR TO BE TOO CLOSE TOGETHER IN BAR AND
 DINING SEATING, SECTION 110.
  
 5. IS THE EXISTING OUTSIDE COVERED RESTARAUNT AREA FIRE
 SPRINKLER PROTECTED, SECTION 201.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT LOCATIONS.
  
 7. NO STORAGE OR ACCESS PERMITTED UNDER THE PLATFORM.
  
 8. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL NEW HANDRAILS AND GUARDRAILS.
  
 9. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THE
 FACILITY. ONE CROWD MANAGER IS REQUIRED FOR EVERY 250
 PERSONS. PLEASE GO TO MARYLAND STATE FIRE MARSHALS
 WEB-SITE AND CLICK ON THE ICON FOR ON-LINE CROWD
 MANAGEMENT TRAINING. PLEASE WATCH THE VIDEO, TAKE THE
 TEST, AND SUBMIT COPIES OF THE CERTIFICATE TO THIS
 OFFICE.
  
 10. ALL EXISTING HOODS SHALL COMPLY WITH NFPA 96.
  
 11. NEW FABRIC CANOPY SHOWN ON PAGE A-4.0 SHALL BE FIRE
 RETARDANT.
  
 12. PLEASE INDICATE ON DRAWINGS THE LOCATIONS OF ALL
 FIRE ALARM SIGNALING AND INITIATING DEVICES. PLEASE
 INDICATE ANY NEW OR EXISTING DEVICES.
  
 13. ALL DOORS THAT COULD BE CONFUSED AS EXITS SHOULD BE
 MARKED "NO EXIT".
  
 14. PROPER LIGHTING LEVELS ARE REQUIRED FOR STAIR
 LOCATIONS.
  
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 14:18 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 14:18 Sent To  
Notes
2009-09-15 14:20:12THE SIZE OF THE SHUT OFF VALVES PER RED LINES INDICATED
 ON SHT P-3 GAS RISER ISOMETRIC. -- DELETE UNION
 UPSTREAM OF THE MANUAL SHUT OFF VALVE FOR THE AUTOMATIC
 SHUT OFF.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 12:50 Rev Time 0.00
Received By kstevens Date 2009-08-10 Time 12:50 Sent To  
Notes
2009-09-15 12:51:50DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. SHT P-3 THE FOLLOWING INFORMATION IS REQUIRED FOR
 THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- ISOMETRIC SHOWS THE
 MANUAL DOWNSTREAM OF THE EMERGENCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-05-19 Cont ID  
Sent By lmartine Date 2010-05-19 Time 15:20 Rev Time 0.00
Received By lmartine Date 2010-05-19 Time 15:20 Sent To  
Notes
2010-05-19 15:21:13*****************EXPEDITED****************
 GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-13 Cont ID  
Sent By lmartine Date 2009-10-13 Time 09:38 Rev Time 0.00
Received By lmartine Date 2009-10-13 Time 09:38 Sent To  
Notes
2009-10-13 10:08:24***********EXPEDITED****************
 C--2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 11:17 Sent To  
Notes
2009-09-08 11:18:229-03-09 TO C-25 9-08-09 EXPEDITED REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-20 Time   Rev Time 0.00
Received By lmartine Date 2009-08-06 Time 17:53 Sent To  
Notes
2009-08-06 17:54:04C-2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-11 Cont ID  
Sent By dpalmer Date 2009-09-11 Time 11:11 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-10-27 Cont ID  
Sent By rregueir Date 2009-10-27 Time 18:23 Rev Time 0.00
Received By rregueir Date 2009-10-27 Time 18:23 Sent To  
Notes
2009-10-27 18:24:17REVISED M-1.0, M-2.0 DELTA 2
 ELIMINATED NEW RTU #3, ADJUSTED VENTILATION SCHEDULE
 FOR EX. RTU #1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-10 Cont ID  
Sent By rregueir Date 2009-09-09 Time 17:45 Rev Time 0.00
Received By rregueir Date 2009-09-09 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-15 Cont ID  
Sent By rregueir Date 2009-08-15 Time 15:04 Rev Time 0.00
Received By rregueir Date 2009-08-10 Time 20:46 Sent To  
Notes
2009-08-10 21:00:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2.0: PROVIDE SPACE BY SPACE VENTILATION
 CALCULATIONS BASED ON FLOOR PLAN AND USE OF INDIVIDUAL
 SPACES. EXAMPLE: FLOOR PLAN SHOWS MULTIPLE
 DINING/RESTAURANT AREAS AND BAR AREAS. THE OCCUPANT
 LOADS FOR BAR AREAS ARE CALCULATED AT A HIGHER RATE
 THAN FOR THE DINING AREAS. PROVIDE SPACE BY SPACE
 CALCULATIONS FOR BAR AREAS, DINING AREAS, STAGE AREAS,
 DANCE FLOOR AREAS IN ACCORDANCE WITH ASHRAE 62.1-2004
 TABLE 6-1.
  
 2. PAGE M-1.0: FLOOR PLAN SHOWS WHAT APPEARS TO BE A
 ROOF-MOUNTED EXHAUST FAN ABOVE WOMENS RESTROOM 139.
 THIS HAS NO LABEL ON PLANS. PLEASE IDENTIFY THIS AND
 ALL EQUIPMENT IN ACCORDANCE WITH FBC-M 304.11.
  
 3. PAGE M-1.0: PROVIDE THE CFM OF EACH EXHAUST GRILL IN
 WOMENS RESTROOM 139 TO DEMONSTRATE COMPLIANCE WITH
 ASHRAE 62.1-2004 TABLE 6-4.
  
 4. PAGE M-2.0: DUCT SMOKE DETECTOR SHALL BE CONNECTED
 TO THE BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH
 FBC-M 606.4.1.
  
 5, PAGE M-2.0: NEW RTU SHALL BE PROVIDED WITH AUXILIARY
 DRAIN PROTECTION VIA WATER LEVEL DETECTION DEVICE
 INSTALLED INTERNALLY ON THE PRIMARY DRAIN PAN IN
 ACCORDANCE WITH FBC-M 607.3.2.1.
  
 6. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE
 CAPABILITIES OF PROPOSED NEW ROOFTOP EXHAUST FANS IN
 ACCORDANCE WITH FBC-M 301.12. ALSO, NO INSTALLATION
 DETAIL WAS PROVIDED FOR ROOFTOP EXHAUST FANS. PROVIDE
 ENGINEERED ATTACHMENT DETAIL FOR FANS AND RELATED CURBS
 OR MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE
 PART OF THE WIND RESISTANCE CERTIFICATION.
  
 7. PROVIDE MANUFACTURER'S DATA FOR WIND RESTSTANCE
 CAPABILITIES OF PROPOSED NEW ROOFTOP PACKAGE UNIT IN
 ACCORDANCE WITH FBC-M 301.12. ALSO, PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS IF THEY ARE
 PART OF THE WIND RESISTANCE CERTIFICATION.
  
 8. PAGE M-1.0: NOTE AT RATED STAIR ENCLOSURE CALLS FOR
 FIRE DAMPERS TO BE INSTALLED AT ALL "PENETRATIONS THRU
 MEZZANINE." PLEASE CLARIFY DESIGN IN THIS AREA AS NO
 MEZZANINE OR FIRE RATED ASSEMBLY ASSOCIATED WITH A
 MEZZANINE IS INDICATED ON PLANS. THE NOTE APPEARS
 INSIDE A RATED STAIR EXIT ENCLOSURE. NO PENETRATIONS OF
 EXIT ENCLOSURES ARE PERMITTED IN ACCORDANCE WITH FBC-B
 1020.1.2. ALSO, IF ANY FIRE DAMPERS ARE REQUIRED TO BE
 INSTALLED IN RELATION TO THIS PROJECT, THEY MUST BE
 SHOWN AND CLEARLY IDENTIFIED ON PLANS IN ACCORDANCE
 WITH FBC-M 607.8.
  
 9. A TEST AND BALANCE REPORT SHALL BE PROVIDED TO THE
 FIELD INSPECTOR AT TIME OF FINAL INSPECTION TO VERIFY
 REQUIRED VENTILATION RATES ARE BEING PROVIDED IN
 ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-10-20 Cont ID  
Sent By kstevens Date 2009-10-20 Time 06:38 Rev Time 0.00
Received By kstevens Date 2009-10-20 Time 06:37 Sent To  
Notes
2009-10-20 06:38:46REVISIONS OK -- SHTS P-1, P-2, P-3 & P-4.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 12:52 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 12:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 18:10 Rev Time 0.00
Received By kstevens Date 2009-08-06 Time 18:57 Sent To  
Notes
2009-08-10 18:21:04DENIED
 REFERENCE:
 FBC-2007 CHAPTER 11
 FBC-2007 FUEL GAS
  
 A. SHTS A-2.1 & A-5.0 WOMENS TOILET ROOM. WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION TO THE STALL
 COMPLYING WITH SECTION 11-4.17.3, AT LEAST ONE STALL
 36" WIDE WITH AN OUTWARD SWINGING SELF CLOSING DOOR &
 PARALLEL GRAB BARS COMPLYING WITH FIGURE 30D & SECTION
 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN SUCH STALLS
 SHALL COMPLY WITH SECTION 11-4.16.
  
 B. SHT P-3 THE FOLLOWING INFORMATION IS REQUIRED FOR
 THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- ISOMETRIC SHOWS THE
 MANUAL DOWNSTREAM OF THE EMERGENCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2009-10-13 Cont ID  
Sent By lmartine Date 2009-09-15 Time 09:38 Rev Time 0.00
Received By lmartine Date 2009-09-15 Time 14:16 Sent To  
Notes
2009-09-15 14:16:37RESTAMP OK PER E.S.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-12 Cont ID  
Sent By eschneid Date 2009-08-12 Time 19:56 Rev Time 0.25
Received By eschneid Date 2009-08-12 Time 19:56 Sent To  
Notes
***NONE***