Plan Review Details - Permit 09080073
Plan Review Stops For Permit 09080073
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-08-10 Cont ID  
Sent By efabian Date 2009-08-10 Time 14:42 Rev Time 1.00
Received By efabian Date 2009-08-10 Time 15:00 Sent To  
Notes
2009-08-10 14:59:47PASSED WITH (3) PROVISOS:
  
 1. PROVIDE DOCUMENTATION TO CONFIRM ADEQUATE PRESSURE
 EXISTS FROM RECENT FLOW TEST IN EXISTING 4 INCH WATER
 MAIN IN THE ALLEY TO THE SYSTEM.
  
 2. PROVIDE DRAWING OF PROPOSED CROSS CONNECTIONS
 THROUGH THE ALLEY BETWEEN THE 4 INCH WATER MAIN AND THE
 BUILDING, INCLUDING BY-PASS OF EXISTING UTILITIES IN
 THE ALLEY.
  
 3. PROVIDE THE LOCATION OF THE D.D.C.V. IS BEHIND THE
 BUILDING AND ACCESSIBLE.
  
  
 PLEASE CONTACT THE REVIEWER WITH ANY QUESTIONS OR
 COMMENTS:
  
 EMERY P. FABIAN, PROJECT COORDINATOR
 CITY OF WEST PALM BEACH
  ENGINEERING SERVICES DEPARTMENT
  401 CLEMATIS STREET, 4TH FLOOR
  WEST PALM BEACH FL 33401
 (561)-494-1048 OFFICE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-08-05 Cont ID  
Sent By mcarsill Date 2009-08-05 Time 15:14 Rev Time 0.00
Received By mcarsill Date 2009-08-05 Time 14:55 Sent To ENG
Notes
2009-08-17 11:46:57*****FIRE-STAMPED W/PROVISO
  
  
 PLAN SHEETS FP-1 AND FP-2 WERE FIRE-STAMPED ACCORDINGLY
 WITH ATTACHED PROVISO FROM BOTH FIRE AND ENGINEERING;
 READY FOR PERMIT ISSUANCE.
2009-08-05 15:13:59313 CLEMATIS STREET
 INSTALL NEW FIRE SPRINKLER SYSTEM IN EXISTING BUILDING
  
 1. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 EQUIPPED WITH KNOX LOCKING CAPS TO PREVENT VANDALISM OR
 THEFT.
  
 2. A CHAIN AND LOCK IS REQUIRED ON THE BACKFLOW DEVICE.
  
 3. THE ENTIRE BUILDING IS REQUIRED TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THE INSTALLATION IS TO COMPLY
 WITH NFPA 13, THE STANDARD FOR THE INSTALLATION OF
 AUTOMATIC FIRE SPRINKLERS.
  
 4. A SPARE SPRINKLER BOX, SPARE SPRINKLERS, AND WRENCH
 IS TO BE PROVIDED.
  
 5. A GUAGE IS TO BE PROVIDED ON THE RISER.
  
 6. THE ENTIRE FIRE SPRINKLER SYSTEM IS TO BE PRESSURE
 TESTED AT 200 PSIG FOR A MINIMUM OF AT LEAST TWO HOURS.
  
 7. THE FIRE DEPARTMENT CONNECTION IS TO BE WITHIN 150
 FEET OF A FIRE HYDRANT.
  
 8. A FLOW TEST IS TO BE SCHEDULED AS SOON AS SOON
 POSSIBLE TO VERIFY STATIC AND RESIDENTIAL READINGS.
  
 9. PLEASE SUBMIT CUT-SHEETS ON THE QUICK RESPONSE
 SPRINKLER HEADS PLANNED FOR USE.
  
 10. ENSURE THAT HYDRAULIC CALCULATION PLATES AND VALVE
 SIGNS ARE INSTALLED.
  
  
 APPROVED PROVISO
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OFFIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX