Plan Review Details - Permit 09080027
Plan Review Stops For Permit 09080027
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-05 Cont ID  
Sent By rmcdouga Date 2009-08-05 Time 12:23 Rev Time 0.00
Received By rmcdouga Date 2009-08-05 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-05 Cont ID  
Sent By rmcdouga Date 2009-08-05 Time 12:29 Rev Time 0.00
Received By rmcdouga Date 2009-08-05 Time 12:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-08-05 Cont ID  
Sent By rmcdouga Date 2009-08-05 Time 12:24 Rev Time 0.00
Received By rmcdouga Date 2009-08-05 Time 12:24 Sent To  
Notes
2009-08-05 12:29:14SEPARATE PERMIT AND PLANS ARE REQUIRED FOR 400,000 BTU
 GAS HEATER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-06 Cont ID  
Sent By rmcdouga Date 2009-08-06 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2009-08-04 Time 11:04 Sent To  
Notes
2009-08-04 11:05:50EXPEDITED PLAN REVIEW / SENT TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-11 Cont ID  
Sent By lwagner Date 2009-08-11 Time 13:04 Rev Time 0.00
Received By lwagner Date 2009-08-11 Time 12:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-06 Cont ID  
Sent By rmcdouga Date 2009-08-06 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2009-08-06 Time 07:39 Sent To  
Notes
2009-08-06 08:06:302007 FBC W/2007 REVISIONS
 NEW POOL/SPA
  
 DENIED BY PLUMBING
  
 1) SHOW COMPLIANCE WITH R4101.6.3 WATER VELOCITY. POOL
 PIPING SHALL BE DESIGNED SO THE WATER VELOCITY WILL NOT
 EXCEED 10 FEET PER SECOND (3048 MM/S) FOR PRESSURE
 PIPING AND 8 FEET PER SECOND (2438 MM/S) FOR SUCTION
 PIPING, EXCEPT THAT THE WATER VELOCITY SHALL NOT EXCEED
 8 FEET PER SECOND (2438 MM/S) IN COPPER TUBING. MAIN
 SUCTION OUTLET VELOCITY MUST COMPLY WITH ANSI/APSP 7.
 SUBMIT CALCULATIONS FOR MAXIMUM SYSTEM FLOW RATE. SEE
 ANSI/APSP-7 2006 SECTIONS 4.4 AND 4.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-04 Cont ID  
Sent By mcruz Date 2009-08-04 Time 11:33 Rev Time 0.00
Received By mcruz Date 2009-08-04 Time 11:30 Sent To B
Notes
2009-08-04 11:33:43ROUTED TO RMC