Plan Review Details - Permit 09070567
Plan Review Stops For Permit 09070567
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-18 Cont ID  
Sent By shill Date 2009-08-18 Time 13:47 Rev Time 0.00
Received By shill Date 2009-08-18 Time 13:47 Sent To  
Notes
2009-08-18 13:48:30PROVISO - AT INSPECTION
 PROVIDE LIGHT FIXTURE & LIGHT POLE CALCS & SHOPS
 MIN 140MPH EXPOSURE C
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-17 Cont ID  
Sent By dpalmer Date 2009-08-17 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2009-08-17 Time 08:59 Sent To B
Notes
2009-08-17 08:59:59 
 ** DENIED REVIEW **
  
 1) NOTE: PLANS HAVE NOT BEEN SUBMITTED UNDER LICENSED
 CONTRACTOR FOR PERMIT APPLICATION.
 PERMIT APPLICATION MAY NOT BE ISSUED UNTIL A LICENSED
 CONTRACTOR HAS APPLIED AND FILLED OUT PERMIT
 APPLICATION.
  
 2) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT INCLUDING MAIN. 110.9
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5, 13-415.B.2.2
  
 4) NOTE: PLANS HAS NOTES WHICH MENTIONS AMENDMENTS AS
 OF 6/01/09 HOWEVER THERE ARE NO KNOWN AMENDMENTS
 ADOPTED BY THE STATE ON THIS DATE.
 ALL PERMIT APPLICATIONS MADE AFTER MARCH 1ST, 2009
 PLACES ALL MINIMUM DESIGNS UNDER 2007 FBC W/ 2009
 SUPPLEMENTS. THE EDITION OF THE NEC/ NFPA-70 AS OF THIS
 MARCH DATE IS THE 2005.
 ** PLEASE EXPLAIN THE DATE NOTED.
  
 5) NOTE: PLEASE BE SURE TO INDICATE THE TYPE OF TIME
 CLOCK MEETING 13-415.AB.1.4. THE TIME CLOCK MUST BE
 ASTRONOMICAL WITH A MINIMUM OF 10HR BACK UP FOR
 PROGRAMMING.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-18 Cont ID  
Sent By shill Date 2009-08-18 Time 13:49 Rev Time 0.00
Received By shill Date 2009-07-24 Time 08:14 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-07 Cont ID  
Sent By shill Date 2009-08-18 Time 13:49 Rev Time 0.00
Received By aaponte Date 2009-08-07 Time 14:42 Sent To  
Notes
2009-08-07 14:44:32PLEASE INDICATE THE PROPERTY LINE IN THE DRAWINGS TO
 DEMONSTRATE COMPLIANCE WITH REGULATION REGARDING
 ILLUMINATION AS FOLLOWS: ANY SOURCE OF ILLUMINATION
 LOCATED WITHIN A COMMERCIAL OR INDUSTRIAL PLANNED
 DEVELOPMENT DISTRICT SHALL NOT EXCEED ONE FOOTCANDLE AT
 OR BEYOND THE BONDARIES OF SUCH DEVELOPMENT.