Plan Review Details - Permit 09070565
Plan Review Stops For Permit 09070565
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 15:49 Rev Time 0.00
Received By shill Date 2009-07-22 Time 15:49 Sent To  
Notes
2009-07-22 15:51:22****PASSED W/PROVISO****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 REVISION IS REQUIRED
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72. THE EVALUATION REPORT WAS SUBMITTED WITHOUT
 THE COVER PAGE FROM THE WEBSITE
 WWW.FLORIDABUILDING.ORG. PLEASE SUBMIT. PLEASE BE SURE
 THAT THE PRODUCT APPROVAL SUBMITTED IS FOR "2007" CODE
 (NOT 2004).