Plan Review Details - Permit 09070384
Plan Review Stops For Permit 09070384
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-24 Cont ID  
Sent By btrobaug Date 2009-08-24 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2009-08-24 Time 15:26 Sent To  
Notes
2009-08-24 15:50:45ELECTRIC PERMIT # 09020014./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-08-06 Cont ID  
Sent By mcarsill Date 2009-08-06 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2009-08-06 Time 13:35 Sent To  
Notes
2009-08-06 13:38:082175 PALM BEACH LAKES BLVD.
 INSTALL 60" LONG EXHAUST HOOD
  
 1. THE ENTIRE HOOD AND DUCT IS TO BE INSTALLED IN
 ACCORDANCE WITH NFPA 96.
  
 2. ALL APPLIANCES SHALL SHUNT TO THE OFF POSITION WHEN
 THE FIRE SUPPRESSION SYSTEM HAS ACTIVATED.
  
 3. THE ENTIRE HOOD AND DUCT IS TO BE INSPECTED AFTER
 INSTALLATION.
  
 4. INSTALLATION IS SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-05 Cont ID  
Sent By dpalmer Date 2009-10-05 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 10:13 Sent To M
Notes
2009-10-05 10:13:37TO RR'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 10:39 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 10:39 Sent To  
Notes
2009-08-27 10:39:24GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-24 Cont ID  
Sent By btrobaug Date 2009-08-24 Time 15:51 Rev Time 0.00
Received By btrobaug Date 2009-07-17 Time 10:41 Sent To  
Notes
2009-07-17 10:42:05SENT TO C-38

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-10-07 Cont ID  
Sent By rregueir Date 2009-10-07 Time 15:52 Rev Time 0.00
Received By rregueir Date 2009-10-07 Time 15:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-09-16 Cont ID  
Sent By rregueir Date 2009-09-16 Time 16:38 Rev Time 0.00
Received By rregueir Date 2009-09-01 Time 14:11 Sent To  
Notes
2009-09-16 16:37:25RESUBMITTED PLANS WERE HELD AT EXPEDITER'S REQUEST TO
 ALLOW TIME TO PROVIDE MISSING INFORMATION. TO THIS
 DATE, REQUESTED INFORMATION WAS NOT PROVIDED AND
 PREVIOUS REVIEW COMMENTS REMAIN UNADDRESSED.
  
 1. PROVIDE SITE PLAN SHOWING LOCATION OF EXHAUST FAN
 AND MAKEUP AIR INTAKE TO DEMONSTRATE COMPLIANCE WITH
 FBC-M 401.4.1, FBC-M 506.3.12 AND FBC-M 508.1.
 NOTE: IT APPEARS LIKELY THAT A SIDEWALL MAKEUP AIR
 INTAKE WILL BE WITHIN 10' OF DRIVEWAY IN VIOLATION OF
 FBC-M 401.4.1.
  
 2. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE
 CAPABILITIES OF EXHAUST FAN IN ACCORDANCE WITH FBC-M
 301.12.
  
 3. PLAN SHOWS LOUVER AT MAKEUP AIR INTAKE. PROVIDE
 PRODUCT APPROVAL FOR PROPOSED LOUVER IN ACCORDANCE WITH
 FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By rregueir Date 2009-08-14 Time 14:55 Rev Time 0.00
Received By rregueir Date 2009-08-14 Time 14:40 Sent To  
Notes
2009-08-14 14:55:101. PROVIDE SITE PLAN SHOWING LOCATION OF EXHAUST FAN
 AND MAKEUP AIR INTAKE TO DEMONSTRATE COMPLIANCE WITH
 FBC-M 401.4.1, FBC-M 506.3.12 AND FBC-M 508.1.
 NOTE: IT APPEARS LIKELY THAT A SIDEWALL MAKEUP AIR
 INTAKE WILL BE WITHIN 10' OF DRIVEWAY IN VIOLATION OF
 FBC-M 401.4.1.
  
 2. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE
 CAPABILITIES OF EXHAUST FAN IN ACCORDANCE WITH FBC-M
 301.12.
  
 3. PLAN SHOWS LOUVER AT MAKEUP AIR INTAKE. PROVIDE
 PRODUCT APPROVAL FOR PROPOSED LOUVER IN ACCORDANCE WITH
 FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 12:02 Rev Time 0.00
Received By kstevens Date 2009-08-10 Time 12:02 Sent To  
Notes
2009-08-10 12:03:42A GREASE INTERCEPTOR MAY BE REQUIRED AS THERE ARE
 FRYERS & GRIDDLES BEING INSTALLED.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-29 Cont ID  
Sent By astelly Date 2009-07-29 Time 14:19 Rev Time 0.00
Received By astelly Date 2009-07-29 Time 14:19 Sent To  
Notes
***NONE***