Plan Review Stops For Permit 09070342 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2009-08-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-08-11 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2009-08-11 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-07-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-07-24 |
Time |
17:59 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2009-07-24 |
Time |
17:30 |
Sent To |
|
|
Notes |
2009-07-24 17:51:07 | BUILDING PLAN REVIEW | | PERMIT: 09070342 | | ADD: 2475 MERCER AV | | CONT: GARLAND C BROWN | | TEL: (561)262-7412 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | JULY 24/2009 | | 1ST REVIEW | | ACTION: DENIED | | | | 1) ARCHITECTURAL SHEETS APPEAR TO BE CODE COMPLIANT, | | THE ISSUE IS WITH THE ENERGY CALCULATIONS. THE FORM | | SUBMITTED IS FORM 400A-2008 FOR WHOLE BUILDING METHOD, | | WHILE THIS IS A SINGLE TENANT SPACE. PLEASE REVIEW | | 13-400.0 B | | FROM THE (2009 SUPPLEMENTS) | | 13-400.0.B METHOD B, THE BUILDING PRESCRIPTIVE METHOD. | | THIS IS A PRESCRIPTIVE METHODOLOGY THAT IS ALLOWED FOR | | SHELL BUILDINGS, RENOVATIONS, CHANGE OF OCCUPANCY, | | LIMITED OR SPECIAL USE BUILDINGS, AND BUILDING SYSTEM | | CHANGEOUTS. THE BUILDING ENVELOPE COMPLIES WITH THE | | STANDARD IF THE PROPOSED BUILDING MEETS OR EXCEEDS THE | | MANDATORY REQUIREMENTS AND ALL RELEVANT CRITERIA ON | | FORM 400B OR THEENERGYGAUGE SUMMIT FLA/COM 2008 | | COMPUTER PRINTOUT. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | SURVEY: | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2009-08-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-08-12 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-08-12 |
Time |
08:57 |
Sent To |
|
|
Notes |
2009-08-12 09:00:21 | REDLINED PLANS. | | PLANS INDICATE A DESIGN WATTAGE HIGHER THAN ALLOWANCE. | | HOWEVER THE SUBMITTED FLA COM INDICATES A DESIGN LOWER | | THAN ALLOWANCE. SQ FT ON FLA COM IS HIGHER THAN WHAT | | CALCULAITONS INDICATES ON PLANS. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-07-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-07-24 |
Time |
19:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-07-24 |
Time |
19:21 |
Sent To |
|
|
Notes |
2009-07-24 19:21:51 | | | ** DENIED ** | | | | 1) NOTE: PLEASE COORDINATE ALL PLANS SUBMITTED. PLEASE | | SEE THAT TWO SET OF PLANS SUBMITTED CONTAIN ELECTRICAL | | AND PLUMBING PLANS FROM TWO DIFFERENT SUITES OR UNITS. | | FOR EXAMPLE ONE SET CONTAINS ELECTRICAL SHEETS FOR UNIT | | 104-B AND THE OTHER FOR SUITE 205. | | AS THE PERMIT APPLICATION IS APPLYING FOR WORK IN UNIT | | 205 THE ELECTRICAL REVIEW WILL BE DONE FOR 205. | | | | | | 2) NOTE: PLEASE SEE THAT THE SUBMITTED WHOLE BUILDING | | METHOD A CALCULATIONS MAY NOT BE USED. THIS IS A TENANT | | BUILDING OUT AND NOT A WHOLE BUILDING BY THE | | DEFINITIONS SET FORTH IN CHAPTER 13 SECTION 202 OR | | CHAPTER 2 OF THE FBC. | | PLEASE SEE 13-415.AB.5. | | THE PLANS SUBMITTED ALSO CONTAIN LIGHTING CALCULATIONS | | PER SECTIONS STATED FROM THE 2004 FBC. . | | IT IS ALSO NOT PERMISSIBLE TO USE TWO DIFFERENT METHODS | | OF CALCULATIONS. | | PLEASE SEE TABLE ON SHEETS AS HALL AREA STATES A | | WATTAGE TOTAL OF 116 YET BASED ON THE WATTAGE OF THE | | FIXTURES ON THE IDR OF THE SUBMITTED ENERGY | | CALCULATIONS THIS IS NOT POSSIBLE. THE IDR STATES 2-64 | | WATT FIXTURES WHICH WOULD BE 128WATTS AND NOT THE 116 | | AS STATED ON PLANS. THIS WOULD NOT COORDINATE WITH THE | | FIXTURES NOTES. | | PLEASE SEE OTHER ROOMS AND AREAS AND THE ALLOWANCES | | UNDER THE 2007 FBC WITH THE 2009 REVISIONS. | | THE IDR ALSO INDICATES MANUAL ON/OFF WHICH IS NOT WHAT | | IS ON PLANS. | | | | 3) NOTE: THE PLANS STATE THE 2007 FBC HOWEVER AS | | ADOPTED THE 2007 FBC WITH THE 2009 REVISIONS HAS | | SUBSTANTIAL CHANGES OVER THE 2007 FBC. | | | | *** AS PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER | | THE NEW BUILDING DIRECTOR, ONCE CORRECTIONS ARE MADE | | INSERTION OF NEW SHEETS AND DOCUMENTS WILL NEED TO TAKE | | PLACE IN THIS DEPARTMENT. | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-08-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-08-12 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-08-12 |
Time |
14:55 |
Sent To |
|
|
Notes |
2009-08-12 15:08:30 | *****APPROVED***** | | | | | | PLAN SHEETS A1.1, A-2.1, AND E-1.1WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2009-08-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-08-05 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-08-05 |
Time |
06:59 |
Sent To |
|
|
Notes |
2009-08-05 07:01:00 | INTERIOR TENANT IMPROVEMENT | | | | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER REMODEL. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | SYSTEM ADDITIONS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-08-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-08-07 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-08-07 |
Time |
15:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-08-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-08-05 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-07-15 |
Time |
16:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2009-08-01 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-08-01 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-08-01 |
Time |
17:35 |
Sent To |
|
|
Notes |
2009-08-01 17:36:21 | METHOD A CALCULATIONS NOT REVIEWED AS PART OF THIS | | PROJECT. COMPLIANCE WITH PRESCRIPTIVE MECHANICAL | | REQUIREMENTS DEMONSTRATED ON PLANS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2009-08-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-08-14 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-08-14 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-08-05 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-08-05 |
Time |
16:27 |
Sent To |
|
|
Notes |
2009-08-05 16:37:06 | DENIED | | REFERENCE: | | FBC-2007 W/2009 SUPPLEMENTS | | FBC-2007 PLUMBING | | FBC-2007 CHAPTER 11 | | | | 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | INDICATE LOCATION ON THE FLOOR PLAN. | | | | 2. SHT P-1 TITLE BLOCK INDICATES SUITE 104-B WHERE AS | | THE APPLICATION AND SYSTEM INDICATE THE SUITE NUMBER AS | | 205. ALSO THE FLOOR PLAN DOES NOT REFLECT THE FLOOR | | PLAN SHOWN ON THE ARCHITECTURAL SHEETS. PLEASE | | CORRELATE. SECTION 106.1.1. | | | | 3. SHT A-1 FLOOR PLAN. SHOW THE CLEAR FLOOR SPACE AND | | TURNING AREA REQUIRED BY SECTIONS 11-4.16.2, 11-4.19.3 | | & 11-4.22.3. IT APPEARS THAT THE DOOR MAY SWING INTO | | THE CLEAR FLOOR SPACE OF THE W/C. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2009-08-19 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-08-19 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-08-19 |
Time |
09:40 |
Sent To |
|
|
Notes |
|
|