Plan Review Details - Permit 09070279
Plan Review Stops For Permit 09070279
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-03 Cont ID  
Sent By shill Date 2009-08-03 Time 10:54 Rev Time 0.00
Received By shill Date 2009-08-03 Time 10:54 Sent To  
Notes
2009-08-03 10:55:41REVISED INSTALLATION SCHEDULE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-20 Cont ID  
Sent By shill Date 2009-07-20 Time 17:21 Rev Time 0.00
Received By shill Date 2009-07-20 Time 17:21 Sent To  
Notes
2009-07-20 17:26:46****PROVISO****
  
 REVISION REQUIRED BEFORE INSPECTION
  
 1. ALL OPENINGS, FLOOR CONNECTION, REQUIRE8.5" SPACING
 FOR SPANS 5' - 8'6", SPANS 8'6-MAX ALLOWED REQUIRE 6"
 ANCHOR SPACING. INSTALLATION SCHEDULE ANCHOR SPACING
 COLUMN IS TO BE REVISED TO REFLECT CORRECT REQUIRED
 ANCHOR SPACING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-24 Cont ID  
Sent By rregueir Date 2009-07-24 Time 16:43 Rev Time 0.00
Received By rregueir Date 2009-07-24 Time 16:43 Sent To B
Notes
2009-07-24 16:43:48TO SHILL DESK