Plan Review Details - Permit 09070265
Plan Review Stops For Permit 09070265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-12 Cont ID  
Sent By dpalmer Date 2009-08-12 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2009-08-12 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-15 Cont ID  
Sent By dpalmer Date 2009-07-15 Time 12:16 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-07-15 12:16:29UNDER E REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-12 Cont ID  
Sent By dpalmer Date 2009-08-12 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2009-08-12 Time 13:32 Sent To P
Notes
2009-08-12 13:33:17ROUTED TO KS FOR THE GAS REVIEW. B,M, E OK AND STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-15 Cont ID  
Sent By dpalmer Date 2009-07-15 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2009-07-15 Time 12:15 Sent To Z
Notes
2009-07-15 12:15:59 
 ** DENIED **
  
 1) NOTE: PLEASE SHOW DIMENSIONS ON ELECTRICAL SITE
 PLANS FOR CLEARANCES FROM HOUSE. THE LOCATIONS ARE
 NOTED HOWEVER SITE/SURVEY FINAL PLANS NEED TO SHOW A
 RECORD OF THE EXACT LOCATION UNIT WILL BE PLACED.
 110.26, NFPA_37
  
 2) NOTE: PLAN SUBMITTED FOR SLAB DETAIL IS A PHOTO-COPY
 OF AN ENGINEER PLAN. PLEASE KNOW THAT THE TITLE BLOCK,
 SIGNATURE, DATE AND SEAL WOULD BE REQUIRED FROM THAT
 ENGINEER WHEN USING THEIR PLAN OR DETAIL. FS
 471.025,FAC 61G15-23.002
 WHEN MEETING EXCEPTIONS DESIGN MAY BE UNDER FS 489.
  
 3) NOTE: PLEASE SHOW OR PROVIDE INFORMATION OF THE LOAD
 SHEDDING OF HEAT STRIPS ON THE STAND-BY SYSTEM. PLANS
 STATE THE ASSUMED LOAD FOR A/C CONDENSING UNITS,
 HOWEVER IF AUTOMATIC TRANSFER IS TAKING PLACE. THE LOAD
 FOR HEAT MUST ALSO BE FIGURED UNLESS LOAD SHEDDING.
 702.5
 PLANS DO MENTION LOAD SHEDDING OF NON-ESSENTIAL LOADS
 HOWEVER UNCLEAR HOW HEAT ON A/C SYSTEM IS UNDER THIS.
  
 4) NOTE: WHEN MEETING 702.11 THEN SIGNAGE IS REQUIRED
 AT THE SERVICE LOCATION AS WELL AS MAIN HOUSE SERVICE
 LOCATION AS TO THE DISCONNECTING MEANS FOR THE STAND-BY
 POWER.
 225.37, 230.2E
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 16:17 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 16:17 Sent To  
Notes
2009-09-16 16:18:24REVISION OK -- GAS RISER DIAGRAM ADDED POOL HEATER
 (EXISTING) AND NEW ROUTING FOR EXISTING DRYER.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-08-14 Cont ID  
Sent By kstevens Date 2009-08-14 Time 11:25 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 11:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-08-13 Cont ID  
Sent By kstevens Date 2009-08-13 Time 14:14 Rev Time 0.00
Received By kstevens Date 2009-08-13 Time 14:14 Sent To  
Notes
2009-08-13 14:25:55DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE EXISTING PIPING OUT OF THE
 METER AND LOCATION OF THE TEE TO THE EXISTING
 APPLIANCES, PIPE SIZE AS WELL AS PIPE MATERIAL SHALL BE
 SHOWN ON THE ISOMETRIC.
 ****RESPONSE NOTED, BUT PLEASE INDICATE WHAT GRC PIPE
 IS. SUBMIT MANUF SPECIFICATIONS FOR THE MATERIAL TO
 VERIFY APPROVAL OF THE MATERIAL. SECTION G2414.
  
 2. TYPE OF GAS, (LP OR NATURAL). -- PLANS INDICATE
 NATURAL GAS, BUT THE APPLICATION STATES "INSTALLATION
 OF GAS TANK". PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, APPLICATION STILL INDICATES GAS TANK,
 BUT PLANS STATE NATURAL GAS. PLEASE CLARIFY.
  
 5. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, APPLICATION STILL INDICATES GAS TANK,
 BUT PLANS STATE NATURAL GAS. PLEASE CLARIFY.
  
 ********NEW COMMENT********
  
 1B. PIPING DIAGRAM SHOWS A REGULATOR AT THE NEW
 GENERATOR, BUT IS NOT INDICATED AT THE DRYER OR WATER
 HEATER. PLEASE INDICATE WHERE THE REGULATOR(S) ARE FOR
 THE EXISTING APPLIANCES. A LISTED SHUT OFF VALVE SHALL
 BE INSTALLED IMMEDIATLY AHEAD OF EACH REGULATOR.
 SECTION G2420.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By kstevens Date 2009-07-20 Time 10:45 Rev Time 0.00
Received By kstevens Date 2009-07-20 Time 10:45 Sent To Z
Notes
2009-07-20 11:39:17DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE EXISTING PIPING OUT OF THE
 METER AND LOCATION OF THE TEE TO THE EXISTING
 APPLIANCES, PIPE SIZE AS WELL AS PIPE MATERIAL SHALL BE
 SHOWN ON THE ISOMETRIC.
  
 2. TYPE OF GAS, (LP OR NATURAL). -- PLANS INDICATE
 NATURAL GAS, BUT THE APPLICATION STATES "INSTALLATION
 OF GAS TANK". PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- THE DISTANCE TO THE
 MOST REMOTE FROM THE METER TO THE EXISTING SHALL BE
 INDICATED.
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 5. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 16:01 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 16:01 Sent To  
Notes
2009-09-15 16:01:48SENT TO KSTEVENS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 15:26 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 15:26 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-12 Cont ID  
Sent By dpalmer Date 2009-08-12 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2009-08-12 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-15 Cont ID  
Sent By dpalmer Date 2009-07-15 Time 12:16 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-07-15 12:16:53UNDER E REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2009-07-30 Cont ID  
Sent By mcruz Date 2009-07-30 Time 11:26 Rev Time 0.00
Received By mcruz Date 2009-07-30 Time 11:25 Sent To  
Notes
***NONE***