Plan Review Details - Permit 09070199
Plan Review Stops For Permit 09070199
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-08 Cont ID  
Sent By jgomez Date 2009-10-08 Time 09:59 Rev Time 0.00
Received By jgomez Date 2009-10-08 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-09-29 Cont ID  
Sent By astelly Date 2009-09-29 Time 17:25 Rev Time 0.00
Received By jgomez Date 2009-09-29 Time 10:32 Sent To PC
Notes
2009-09-29 10:47:20RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 SECOND CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED TO GET APPROVAL FROM ZONING REGARDING THE
 BUILDING SETBACKS IN ORDER TO PASS THE BUILDING REVIEW.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 3- A) ENERGY CALCULATIONS FORM 1100B-08 SUBMITTED CAN'T
 BE USED IF THE BUILDING HAS A SINGLE ASSEMBLY
 ROOF/CEILING (FLAT ROOF). NEED TO PROVIDE FORM
 1100A-08.
 B) PREPARER AND OWNER/AGENT NEED TO SIGN AND DATE
 BOTTOM OF FORM.
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, ETC.
  
 4- REMAINDER: ANY ELECTRICAL, PLUMBING OR MECHANICAL
 WORK REQUIRES SEPARATE PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-14 Cont ID  
Sent By jgomez Date 2009-08-14 Time 08:50 Rev Time 0.00
Received By jgomez Date 2009-08-14 Time 08:50 Sent To  
Notes
2009-08-14 09:28:04RESIDENTIAL (R3) ALTERATION AND RENOVATION BUILDING
 REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CONVERSION OF ENCLOSED PORCH TO LIVING SPACE
 REQUIRES IMPACT FEES REVIEW. BRING PLANS TO PALM BEACH
 COUNTY (2300 N. JOG RD. (561)233-5120) TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED A TIME OF PERMIT PICK UP.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0.3 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL
 CODE. PLEASE MAKE SURE CORRECT FORM IS PROVIDED AND ALL
 THE INFORMATION AND SIGNATURES ARE PROVIDED ON THE
 FORM.
  
 4- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 UPDATE VALUATION TO INCLUDE ALL THE SCOPE OF WORK TO BE
 DONE AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 5- DRAWINGS SUBMITTED ARE MISSING THE FOLLOWING:
 A) SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. 401.4
 OF 2007 FLORIDA EXISTING CODE-EXISTING.
  
 B) CODE INFORMATION: SPECIFY BUILDING CODE, WIND LOAD,
 BUILDING EXPOSURE AND EXTERIOR DOORS AND WINDOWS DESIGN
 PRESSURES AS REQUIRED BY SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
 ***NOTE: ACCORDING TO 2009 REVISIONS TO THE 2007 FBC
 THIS BUILDING IS LOCATED ON EXPOSURE "C". TAKE THIS
 INTO CONSIDERATION WHEN CALCULATING THE DESIGN
 PRESSURES.
  
 C) COMPLETE WALL SECTION FOR EXTERIOR WALLS TO BE
 ENCLOSED AS REQUIRED BY SEC. 106.3.5.4(6) OF CITY
 AMENDMENTS TO FBC. NEED TO SPECIFY. STUDS FASTENING
 (TOP AND BOTTOM), PLYWOOD THICKNESS AND FASTENING,
 STUCCO THICKNESS AND 2 LAYERS OF WATER VAPOR BARRIER,
 INSULATION ETC.
  
 D) SPECIFY INSULATION ON CEILING AND EXTERIOR WALLS.
 COORDINATE WITH THE ENERGY CALCULATIONS PROVIDED.
  
 E) PROVIDE COMPLETE FRAMING DETAILS AND FASTENING FOR
 NEW CEILING RAFTERS ON MASTER BEDROOM AREA. ALSO,
 CLARIFY IF EXISTING MASTER BEDROOM IS GOING TO BE
 EXPANDED INTO THE GARAGE AREA. PROVIDE WALL
 SECTION/DETAIL AND SPECIFICATIONS.
  
 F) PLANS NEED TO BE DRAWN TO SCALE AND PROVIDE
 DIMENSIONS.
  
 G) SPECIFY SAFETY GLASS FOR WINDOW REPLACEMENT ON
 MASTER BATHROOM AND FOR WINDOWS ADJACENT TO EXTERIOR
 WALL ON PORCH WALL TO BE ENCLOSED. SEC. R308.4 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 H) COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR NEW
 WINDOWS AND DOORS OPENINGS. SPECIFY ALL FRAMING MEMBERS
 AND FASTENING.
  
 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SHUTTERS FOR DOORS AND WINDOWS THAT HAVE NOT IMPACT
 GLASS.
 ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE (SEE
 ATTACHED SAMPLE). AND, CLEARLY MARK ON SHUTTERS
 DRAWINGS SPECIFIC MOUNTING CONDITIONS (EX: WALL
 MOUNTED, BUILT OUT, ETC) AND SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED.
  
 B) WINDOW MULLIONS. AND, CLEARLY MARK SPECIFIC MULLION
 SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED DESIGN
 PRESSURES.
  
 C) EXTERIOR SWING DOOR NOA 08-0516.07 SUBMITTED EXPIRED
 ON JULY 12, 2009. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 7- NEED TO PROVIDE EMERGENCY EGRESS FROM MASTER BEDROOM
 THAT COMPLIES WITH SEC. 310 OF 2007 FLORIDA RESIDENTIAL
 CODE. 39"X37" SINGLE HUNG WINDOW DOESN'T COMPLY WITH
 THIS SECTION. EGRESS WAS CHANGED WHEN ENCLOSING PORCH
 TO CREATE NEW LIVING AREA.
  
 8- DESIGNER RESPONSIBLE FOR THE DRAWINGS TO REVIEW AND
 APPROVE IN WRITING ALL PRODUCT APPROVALS AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 9- ANY ELECTRICAL, PLUMBING OR MECHANICAL WORK REQUIRES
 SEPARATE PERMIT. PLANS NO SUBMITTED AT THIS TIME.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-10 Cont ID  
Sent By tmoore Date 2009-07-10 Time 14:04 Rev Time 0.00
Received By tmoore Date 2009-07-10 Time 14:00 Sent To  
Notes
2009-07-10 14:04:06DENIED APPLICATION FOR STUCCO. NEW EXTERIOR WOOD
 FRAMING AND LATH WORK PERFORMED. NO PERMITS, NO
 INSPECTIONS.
 4XFEE ATTCHED FOR ELEC., PLUMBING, AND BUILDING WITH
 OUT PERMITS FOR INSIDE WORK.
 PLANS AND PRODUCT APPROVALS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 18:06 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 18:06 Sent To  
Notes
2009-09-15 18:06:55SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-14 Cont ID  
Sent By jgomez Date 2009-08-14 Time 10:55 Rev Time 0.00
Received By jgomez Date 2009-07-28 Time 16:56 Sent To  
Notes
2009-07-28 16:56:42SENT TO ZONING BOX.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-09-29 Cont ID  
Sent By jgomez Date 2009-09-29 Time 10:29 Rev Time 0.00
Received By jgomez Date 2009-09-29 Time 10:29 Sent To  
Notes
2009-09-29 10:31:53NO FEES DUE. PLANS STAMPED ON 8/18/09 . SEE FLOOR
 PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-29 Cont ID  
Sent By astelly Date 2009-09-24 Time 17:42 Rev Time 0.00
Received By astelly Date 2009-09-29 Time 17:24 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-06 Cont ID  
Sent By mcruz Date 2009-08-06 Time 15:13 Rev Time 0.00
Received By mcruz Date 2009-08-06 Time 15:10 Sent To B
Notes
2009-08-06 15:13:47PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. SHOW THE LOCATION OF THE PATIO ON THE SURVEY. BASED
 ON THE FLOOR PLAN THAT WAS SUBMITTED THE PATIO/PORCH
 SEEMS TO BE LOCATED IN THE REAR OF THE PROPERTY. I SEE
 ON THE AERIAL THAT THERE IS AN EXISTING STRUCTURE IN
 THE REAR. IS THIS STRUCTURE ACCESSORY TO HOME OR IS IT
 ALL ATTACHED? PLEASE ADVISE AND INDICATE ON SURVEY.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 ROUTED TO TMOORE