Plan Review Details - Permit 09070184
Plan Review Stops For Permit 09070184
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-31 Cont ID  
Sent By shill Date 2009-07-31 Time 15:51 Rev Time 0.00
Received By shill Date 2009-07-31 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By dpalmer Date 2009-07-27 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2009-07-27 Time 10:08 Sent To B
Notes
2009-07-27 10:08:35 
 ** DENIED REVIEW. **
  
 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST, INSTALLATION ETC EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. THE APPLIED VALUE FOR THE
 COMPLETE SCOPE OF WORK AT $1,250.00 IS LOW.
 FBC 108.3.
 PLEASE PROVIDE COPY OF SIGNED CONTRACTS FOR ALL OF THE
 ABOVE.
  
 ** PER BUILDING OFFICIAL. PLANS AND PERMIT APPLICATIONS
 ARE NO LONGER RELEASED AND SHALL REMAIN ON FILE.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-31 Cont ID  
Sent By shill Date 2009-07-31 Time 15:52 Rev Time 0.00
Received By shill Date 2009-07-10 Time 09:16 Sent To  
Notes
2009-07-10 09:16:45IN ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By lfranco Date 2009-07-27 Time 17:11 Rev Time 0.00
Received By lfranco Date 2009-07-27 Time 17:11 Sent To  
Notes
2009-07-27 17:34:07PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS PART OF THE METROCENTRE COMMERCIAL
 PLANNED DEVELOPMENT (" CPD"), AN APPLICATION FOR A
 MINOR AMENDMENT TO THE CPD SHOWING THE PROPOSED SIGNAGE
 WILL BE REQUIRED TO BE FILED TO THE PLANNING AND ZONING
 DEPARTMENT AND APPROVED PRIOR TO THE BUILDING PERMIT
 BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 THE FOLLOWING, BUT NOT LIMITED TO THE FOLLOWING ITEMS
 SHALL BE SHOWN ON THE PLANS SUBMITTED:
  
 THE TOTAL SQUARE FOOTAGE OF ALL SIGNAGE SHALL BE SHOWN
 ON A SITE DATA IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR"). REFER TO THE ZLDR FOR
 SIGNAGE REGULATIONS, UNDER THE GENERAL COMMERCIAL (GC)
 ZONING DISTRICT. ADDITIONALLY, AN APPROVAL LETTER FROM
 THE METROCENTRE ARCHITECTURAL REVIEW BOARD SHALL BE
 SUBMITTED ALONG WITH THE MINOR PD AMENDMENT
 APPLICATION.
  
 3. PROVIDE THE TOTAL AMOUNT OF SIGNS THAT EXIST AND ARE
 PROPOSED FOR ALL FACADES OF THE EXISTING MARRIOTT
 RESIDENCE INN HOTEL. PURSUANT TO SECTION 94-408(D)(1)D,
 THE MAXIMUM NUMBER OF WALL-MOUNTED SIGNS FOR THE
 BUILDING IS THREE (3). IF THE SIGNAGE EXCEEDS THE
 ALLOWABLE AMOUNT OF SIGNS, THEN CONTACT ME ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  