Plan Review Details - Permit 09070170
Plan Review Stops For Permit 09070170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By jwitmer Date 2009-08-03 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2009-08-03 Time 12:39 Sent To  
Notes
2009-08-03 13:07:02BUILDING PLAN REVIEW
 PERMIT: 09070170
 ADD: 4047 OKEECHOBEE RD
 CONT:"PRE-INSPECT"
 TEL: (561)723-7842 CHARLES GRISKY
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE OR CHAPTER 9 FOR
 CHANGE OF OCCUPANCY.
  
 1B) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) ON THE PERMIT APPLICATION AND FROM THE PRE-INSPECT
 AT THIS TIME IT IS NOT PSSIBLE TO KNOW WHAT TYPE OF
 OCCUPANCY TO CLASSIFY THIS OCCUPANCY. A BEAUTY SALON
 WOULD BE CLASSIFIED
 AS A BUSSINESS OCCUPANCY (304.1). THE PERMIT
 APPLICATION INDICATES A COMMUNITY OUTREACH CENTER,
 SUMMER CAMP AND AFTER SCHOOL TUTORING. THIS OCCUPANCY
 LOOKS LIKE IT MAY BE A MIXED USE OCCUPANCY, A A-3 AS A
 COMMUNITY CENTER, SUMMER CAMP COULD ALSO BE CLASSIFIED
 AS DAY CARE CENTER (313) AND DEPENDING ON THE AGE OF
 THE CLIENT BEING TUTERED EITHER A SCHOOL OR BUSSINESS.
 PLEASE PROVIDE THE ABOVE INFORMATION ON THE PLANS
 INDICATING THE USAGE OF THE FACILITY.
  
 3) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
 COMMERCIAL BUILDINGS:
 BUILDING:
  
 1.OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 2.MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503). PLANS INDICATE TYPE III , IS IT A TYPE
 III-A OR III-B?
  
 3) PLANS INDICATE THE BUILDING IS FIRE SPRINKLERED,
 PLEASE PROVIDE THE LAYOUT OF EXISTING SPRINKLERS PLUS
 ANY NEW HEADS OR HEADS THAT NEED TO BE MOVED.
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE
 SPRINKLERS
  
 4) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
 5.OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
  
 6)ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE
 DRINKING FOUNTAINS
  
 7) NTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-10 Cont ID  
Sent By tmoore Date 2009-07-10 Time 10:41 Rev Time 0.00
Received By tmoore Date 2009-07-10 Time 10:37 Sent To  
Notes
2009-07-10 10:41:13CHANGING OCCUPANCY FROM "B", TO "A"-3. PLANS WILL BE
 REQUIRED FOR PROPOSED ALTERATIONS.
 MADE THIS CLEAR TO CHURCH REPRESENTATIVE ON SITE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-18 Cont ID  
Sent By dpalmer Date 2009-08-18 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2009-08-18 Time 12:02 Sent To  
Notes
2009-08-18 12:02:47 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT PLANS CONTAINING MINIMUM DESIGNS
 FOR THE NEW USE AND OCCUPANCY OF THE LOCATION. THE
 SUBMITTED LAYOUT DOES NOT INCLUDE ANY INFORMATION ON
 OCCUPANCY OF ALL LOCATIONS, DESIGN CODES, RATINGS,
 LIGHTING ETC.
 PLEASE BE SURE TO SEE FBC 2007 W/2009 REVISIONS.
 PLEASE SEE NFPA-70 2005
 PLEASE SEE NFPA-101 2006 LIFE SAFETY CODE.
  
 2) NOTE: PLEASE COMPLY WITH THE REQUIREMENTS CHANGE IN
 OCCUPANCY UNDER FBC CHAPTER 13. PLEASE SEE 13-101.3,
 13-415.AB.1.1,.1.2, .1.3, 13-415.AB.5, 13-415.B ETC
  
 3) NOTE: PLEASE BE SURE TO SHOW ALL CIRCUITING FOR
 NEW/EXISTING ELECTRICAL WITH ELECTRICAL PANELS,
 EQUIPMENT, SERVICE MEETING CURRENT CODES OR BEING
 BROUGHT UP TO CODE.
 PLEASE SEE NEC, 220,310,300,408,110.26.
 ALL CODES AND SECTIONS GIVEN IN GENERAL AS PLANS DO NOT
 SHOW ENOUGH INFORMATION FOR REVIEW FOR CODE COMPLIANCE.
  
 4) NOTE: PLEASE BE SURE TO SEE CHAPTER 11 OF THE FBC
 FOR ADA COMPLIANCE FOR ANY ITEMS SUCH AS FIRE ALARM
 DEVICES, CONTROLS, SIGNALS ETC
 SEE 11-4.27.1, .2 AND .3
  
 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9 FOR EGRESS
 LIGHTING MINIMUMS. PLEASE BE SURE TO SEE NEC 700.12F
 FOR CIRCUITING TO LOCAL LIGHTING BRANCH CIRCUIT(S).
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By mcarsill Date 2009-08-13 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2009-08-13 Time 14:30 Sent To  
Notes
2009-08-13 14:36:2709070170
 4047 OKEECHOBEE BLVD., SUITE 230
 "PRE-INSPECT, CHANGE OF OCCUPANCY"
  
 1. PLEASE DECLARE NEW OCCUPANCY TYPE.
  
 2. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 3. PLEASE DECLARE ALL DOOR HARDWARE AND ANY LOCKING
 DEVICES ON EXIT DOORS.
  
 4. PLEASE PROVIDE AN OCCUPANT LOAD FOR SUITE 230.
  
 5. NO DETAIL FOR WALL CONSTRUCTION.
  
 6. PLEASE PROVIDE DETAILS FOR KIDS ROOM, AGE OF
 CHILDREN, HOURS OF OPERATION, AND SUPERVISION.
  
 7. PLEASE INDICATE LOCATIONS OF FIRE EXTINGUISHERS.
  
 8. PLEASE PROVIDE INFORMATION ON EXIT DOOR THAT SWINGS
 INWARD TO LOBBY.
  
 9. PLEASE PROVIDE DETAILS REGARDING EXISTING FIRE
 SPRINKLER SYSTEM. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL.
  
 10. PLANS DO NOT ILLUSTRATE ANY MECHANICAL, ELECTRICAL,
 OR PLUMBING CONTAINED WITHIN BUILDING.,
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2009-07-31 Time 13:55 Sent To  
Notes
2009-07-31 14:04:21 
  
 C-12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-06 Cont ID  
Sent By rregueir Date 2009-08-06 Time 11:39 Rev Time 0.00
Received By rregueir Date 2009-08-06 Time 10:08 Sent To  
Notes
2009-08-06 11:39:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE PROPOSED NEW OCCUPANCY APPEARS TO BE A MIXED
 USE, INCLUDING A-3 AND POSSIBLY DAYCARE OR E. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL , THE INTENT OF THE
 RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS
 SHALL BE COMPLIED WITH FOR THE NEW OCCUPANCY IN
 ACCORDANCE WITH FBC-EB SECTION 909.1.
  
 2. SHOW COMPLIANCE WITH FBC-M SECTION 403 VENTILATION
 REQUIREMENTS FOR THE PROPOSED NEW OCCUPANCY AS WELL AS
 ANY NEW RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB
 SECTION 709.1. NO MECHANICAL SCOPE OF WORK IS SHOWN ON
 PLANS AT THIS TIME.
  
 3. BUILDINGS HAVING A CHANGE OF OCCUPANCY THAT WERE
 PERMITTED AFTER MARCH 15, 1979, SHALL COMPLY WITH THE
 REQUIREMENTS OF SUBCHAPTER 13-4 FOR COMMERCIAL
 APPLICATIONS IN ACCORDANCE WITH FBC-B SECTION
 13-101.3.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-11 Cont ID  
Sent By kstevens Date 2009-08-11 Time 09:51 Rev Time 0.00
Received By kstevens Date 2009-08-11 Time 09:51 Sent To  
Notes
2009-08-11 10:02:07DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1 (ADMIN)
  
  
 1. PLEASE INDICATE THE OCCUPANCY, OCCUPANCY LOAD AND
 ACCESSIBILITY OF THE SPACE. SECTION
 106.3.5.1.1(2)(7)(10) & SECTION 906.1.
  
 2. SUBMIT CALCULATIONS FOR MINIMUM FIXTURE FACILITIES
 PER TABLES 1004.1.1 (BLDG) & 403.1 (PLMG).
  
 3. WHEN ADDITIONAL INFORMATION IS SUBMITTED, MAY
 COMMENTS MAY BE FORTHCOMING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-18 Cont ID  
Sent By kdfreema Date 2009-08-18 Time 14:14 Rev Time 0.00
Received By kdfreema Date 2009-08-18 Time 14:14 Sent To  
Notes
2009-08-18 14:22:48***FAILED***
  
 THE USE OF THIS PROPERTY AS A COMMUNITY CENTER COMPLIES
 WITH THE ZONING REGULATIONS, HOWEVER, OUTSTANDING
 ISSUES EXIST WITH AN ILLEGAL SUBDIVISION EXIST ON THIS
 PROPERTY. ZONING WILL BE UNABLE TO APPROVE ANY CHANGE
 OF OCCUPANCY IN THIS SPACE UNTIL THE SUBDIVISION ISSUE
 HAS BEEN RESOLVED. PLEASE CONTACT KELLY FREEMAN,
 PLANNER, AT 561-822-1458 OR [email protected] WITH
 QUESTIONS.