Plan Review Details - Permit 09060761
Plan Review Stops For Permit 09060761
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-01-13 Cont ID  
Sent By jwitmer Date 2010-01-13 Time 11:04 Rev Time 1.00
Received By jwitmer Date 2010-01-13 Time 11:04 Sent To  
Notes
2010-01-13 11:08:29PRODUCT APPROVALS:
 NOA 08-0731.08
 PITTSBURG CORNING CORP
 GLASS BLOCK +/- 80 PSF
 FIREDOOR
 8080 HMD-1L OUTSWING LOUVER
 NOA 06-0222.10
 +/- 75

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 15:01 Rev Time 2.22
Received By jwitmer Date 2009-12-09 Time 15:01 Sent To  
Notes
2009-12-09 15:26:04BUILDING PLAN REVIEW
 PERMIT: 09060761
 ADD: 2400 N FLAGLER DRIVE
 CONT: OCEAN GATE G.C.
 TEL: (561)644-7446
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REST ROOMS:
 1) BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS REPORT.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 2) BUILDING PROVISO: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 A) TRUSS ANCHORS
 B) GLASS BLOCK
 C) LOUVERS
 D) EXTERIOR SWING DOORS
 E) ROOFING ASSEMBLIES
 F) ROOF TOP VENT
  
 3) BUILDING PROVISO: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FOUND ON C1.1 THERE IS A ACCESSIBLE RAMP THAT PROVIDES
 ACCESS TO THE RESTROOMS, THE DESIGN INDICATED IS TO THE
 FDOT STANDARD, NO SECTIONS ARE PROVIDED FOR THIS ACCESS
 RAMP, NO BOTTOM LANDING. THE PLANS SHALL BE DESIGNED TO
 THE FLORIDA BUILDING CODE CHAPTER 11, SECTION 8.1
 THROUGH 8.8. THERE ARE NO DETAILS FOUND ON ANY
 ARCHITECTURAL PLANS.
  
 BUILDING PROVISO: FLOOD ZONE A5: MIN ELEVATION: 7'-6".
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED
 AFTER MONOLITHIC POUR..
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-11-16 Cont ID  
Sent By jwitmer Date 2009-11-16 Time 10:27 Rev Time 1.50
Received By jwitmer Date 2009-11-16 Time 10:27 Sent To  
Notes
2009-11-16 11:23:11BUILDING PLAN REVIEW
 PERMIT: 09060761
 ADD: 2400 N FLAGLER DRIVE
 CONT: OCEAN GATE G.C.
 TEL: (561)644-7446
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE AND REPLACEANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, THE ONLY REFERENCE TO
 THE 2007 FBC IS FOUND ON A6 IN REFERENCE TO WIND
 DESIGN, NOWHERE IS FOUND THE 2009 SUPPLEMENTS.
  
 2) SECOND REQUEST, NO PLANS WERE SUBMITTED FOR THE
 STRUCTURAL DESIGN OF THE PICNIC NOR TENNIS SHELTER.THE
 PERMIT APPLICATION INDICATES "WITH SELECTED SITE
 IMPROVEMENTS, IS THIS INCLUDED??????
 PLANS ARE NOT CLEAR AS TO THE NATURE OF WORK. FOR
 EXAMPLE THE PERMIT APPLICATION INDICATES PICNIC
 SHELTERS AND TENNIS SHELTERS.
 SHEET LS-3 INDICATES POLIGON SHELTERS 20'X20' OR
 22'X22'
 SHEET LD-2 INDICATES A 16'-8" X 16'-8" SHELTERS
 ARE BOTH OF THESE TO BE PICNIC SHELTERS? THERE IS NO
 DESIGN CRITERIA PROVIDED AT THIS TIME THE PLANS
 INDICATE "SUBJECT TO ONGOING DESIGN REVIEW.
  
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3)SECOND REQUEST, NO PLANS WERE SUBMITTED FOR THE
 STRUCTURAL DESIGN OF THE PICNIC NOR TENNIS SHELTER. THE
 PERMIT APPLICATION INDICATES "WITH SELECTED SITE
 IMPROVEMENTS, IS THIS INCLUDED??????
  
 THE SAME IS TRUE FOR THE TENNIS SHELTERS FOUND ON SHEET
 LD-1" SUBJECT TO ONGOING DESIGN REVIEW". INFORMATIONAL
 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4)THE SAME ELECTRIC SHEETS ARE IN PLANS, 2ND REQUEST..
 SHEET E-5 INDICATES THE LIGHT POLES TO BE USED ON THE
 PROJECT, THE WIND INFORMATION IS PROVIDED FOR 140 MPH
 BUT THE EXPOSURE IS NOT PROVEDED. THIS LOCATION SHALL
 BE CONSIDERED A "C" ZONE HAS THAT EXPOSURE FACTOR BEEN
 INCLUDED INTO THE POLE AND LIGHT FIXTURE DESIGN. ASCE
 7-05.
  
 5) THE SAME ELECTRIC SHEETS ARE IN PLANS. SHEET E-6
 DOES INDICATE LIGHT POLE FIXTURE TYPES BUT THE EPA FOR
 FIXTURE TYPE WAS NOT PROVIDED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED./ ASCE 7-05.
  
 6) 2ND REQUEST. SHEET LS-3 INDICATES THERE TO BE A
 NAUTICAL PLAYGROND. PLEASE REVIEW THE "GUIDE TO ADA
 ACCESSIBILITY GUIDELINES FOR PLAY AREAS" FOR ACCESSIBLE
 ROUTE, PLAY COMPONENTS, GROUND LEVEL AND ELEVATED PLAY
 COMPONENTS BASED ON TABLE 15.6.2.2.
  
 7) NEW RESTROOM BUILDING:
 7.1-7.4 COMPLIED.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL. THE ELEVATION NOR SHEET A6 INDICATE THE
 PRESSURES FOR WALL OPENINGS NOR WIND PRESSURES FOR
 ZONES 1,2 & 3.
  
 8) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS
 REPORT. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 9) COMPLIED.
  
 10) COMPLIED
  
 11)BUILDING PROVISO: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 11A) TRUSS ANCHORS
 11B) GLASS BLOCK
 11C) LOUVERS
 11D) EXTERIOR SWING DOORS
 11E) ROOFING ASSEMBLIES
 111F) ROOF TOP VENT
  
 12) BUILDING PROVISO: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) ONCE SQ FT AREAS OF PAVILIONS ARE KNOWN STATE RADON
 FEES WILL BE ASSESSED.
  
 NEW COMMENT: FOUND ON C1.1 THERE IS A ACCESSIBLE RAMP
 THAT PROVIDES ACCESS TO THE RESTROOMS, THE DESIGN
 INDICATED IS TO THE FDOT STANDARD, NO SECTIONS ARE
 PROVIDED FOR THIS ACCESS RAMP, NO BOTTOM LANDING. THE
 PLANS SHALL BE DESIGNED TO THE FLORIDA BUILDING CODE
 CHAPTER 11, SECTION 8.1 THROUGH 8.8. THERE ARE NO
 DETAILS FOUND ON ANY ARCHITECTURAL PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-17 Cont ID  
Sent By jwitmer Date 2009-07-17 Time 16:40 Rev Time 1.50
Received By jwitmer Date 2009-07-17 Time 15:20 Sent To  
Notes
2009-07-17 16:56:00BUILDING PLAN REVIEW
 PERMIT: 09060761
 ADD: 2400 N FLAGLER DRIVE
 CONT: "PLAN REVIEW"
 TEL: (561)644-7446
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) PLANS ARE NOT CLEAR AS TO THE NATURE OF WORK. FOR
 EXAMPLE THE PERMIT APPLICATION INDICATES PICNIC
 SHELTERS AND TENNIS SHELTERS.
 SHEET LS-3 INDICATES POLIGON SHELTERS 20'X20' OR
 22'X22'
 SHEET LD-2 INDICATES A 16'-8" X 16'-8" SHELTERS
 ARE BOTH OF THESE TO BE PICNIC SHELTERS? THERE IS NO
 DESIGN CRITERIA PROVIDED AT THIS TIME THE PLANS
 INDICATE "SUBJECT TO ONGOING DESIGN REVIEW.
  
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) THE SAME IS TRUE FOR THE TENNIS SHELTERS FOUND ON
 SHEET LD-1" SUBJECT TO ONGOING DESIGN REVIEW".
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES .CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4) SHEET E-5 INDICATES THE LIGHT POLES TO BE USED ON
 THE PROJECT, THE WIND INFORMATION IS PROVIDED FOR 140
 MPH BUT THE EXPOSURE IS NOT PROVEDED. THIS LOCATION
 SHALL BE CONSIDERED A "C" ZONE HAS THAT EXPOSURE FACTOR
 BEEN INCLUDED INTO THE POLE AND LIGHT FIXTURE DESIGN.
 ASCE 7-05.
  
 5) SHEET E-6 DOES INDICATE LIGHT POLE FIXTURE TYPES BUT
 THE EPA FOR FIXTURE TYPE WAS NOT PROVIDED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED./ ASCE 7-05.
  
 6) SHEET LS-3 INDICATES THERE TO BE A NAUTICAL
 PLAYGROND. PLEASE REVIEW THE "GUIDE TO ADA
 ACCESSIBILITY GUIDELINES FOR PLAY AREAS" FOR ACCESSIBLE
 ROUTE, PLAY COMPONENTS, GROUND LEVEL AND ELEVATED PLAY
 COMPONENTS BASED ON TABLE 15.6.2.2.
  
 7) NEW RESTROOM BUILDING:
 7A) MISSING WIND DESIGN CRITERIA:2007 FBC 1609.1.1 &
 CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE 7-05 .
 ALSO 1603.1.4 WIND DESIGN DATA.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 8) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED SOILS
 REPORT. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 9) SHEET A-1.0 DOES NOT INDICATE COMPLIANCE WITH 1816.1
 TERMITE PROTECTION.
  
 10) PLEASE REVIEW 1203.2 WITH THE REQUIREMENT OF 50 %
 OF REQUIRED VENTILATION IN THE UPPER PORTION OF ROOF.
  
 11)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 11A) TRUSS ANCHORS
 11B) GLASS BLOCK
 11C) LOUVERS
 11D) EXTERIOR SWING DOORS
 11E) ROOFING ASSEMBLIES
  
 12) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) ONCE SQ FT AREAS OF PAVILIONS ARE KNOWN STATE RADON
 FEES WILL BE ASSESSED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date   Cont ID  
Sent By dpalmer Date   Time   Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-11-16 Cont ID  
Sent By dpalmer Date 2009-11-16 Time 09:34 Rev Time 0.00
Received By dpalmer Date 2009-11-16 Time 09:10 Sent To  
Notes
2009-11-16 09:13:10** DENIED **
  
 1) NOTE: THE SAME ELECTRICAL PLANS IN SETS. NO NEW
 SHEETS INSERTED INTO SETS.
 ONLY ONE OLD SET WITH NO NEW SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 12:06 Sent To  
Notes
2009-07-05 12:06:22** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS ARE SUBMITTED ONLY FOR PLAN REVIEW ONLY,
 NO PERMIT APPLICATION HAS BEEN MADE. PLEASE ALSO SEE
 THAT THE PERMIT DESCRIPTION STATED ON THE 2400 N
 FLAGLER DR PROJECT IS THE SAME FOR PHIPPS PARK. IN FACT
 THE CURRIE PARK APPLICATION STATES * OTHER: CURRIE PARK
 RENOVATION*.
  
 IT APPEARS THE DESCRIPTION OF WORK NEEDS TO BE REVISED
 AND LOCATIONS COORDINATED.
  
 EACH APPLICATION DOES NOT NEED TO MENTION THE OTHER
 LOCATIONS. THESE ARE SEPARATE PROJECTS WITH SEPARATE
 PLANS AND APPLICATIONS.
  
 2) NOTE: PLEASE SEE FS 481.219 FOR LANDSCAPE FIRM WHICH
 REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER. SEE FAC
 61G1-16.004, 61G10 FOR REQUIRED TITLE BLOCK
 INFORMATION.
 NO COMPANY PHONE NUMBER.
 NO COMPANY LICENSE NUMBER.
  
 3) NOTE: SOME SHEETS SUBMITTED DO NOT CONTAIN ANY
 SIGNATURE, DATE OR SEAL FROM THE RESPONSIBLE DESIGN
 PROFESSIONAL. SEE EP1.0, A6.0 FOR EXAMPLES.
 481.221, 471.025
  
 4) NOTE: SHEET E-7 STATES 2004 FBC WITH 2007 REVISIONS.
 AS OF MARCH 1ST, 2009 ALL PERMIT APPLICATIONS SHALL BE
 UNDER THE 2007 FBC WITH THE 2009 REVISIONS.
 THIS SAME SHEETS MAKES REFERENCE TO THE 2003 NFPA-101.
 PLEASE SEE FAC 69A-60.004 AS OF DECEMBER 31ST, 2008 THE
 REVISED ADOPTED CODE IS 2006 NFPA-101.
  
 5) NOTE: PLEASE SUBMIT PRESCRIPTIVE LIGHTING
 PERFORMANCE CALCULATIONS FOR NEW RESTROOM BUILDING. SEE
 13-415.AB.5 AND SEE 13-415.AB.2.2 FOR EXTERIOR.
  
 6) NOTE: PLEASE VOLTAGE DROP FOR NEW SUB FEED FROM
 MAIN. SEE FBC 13-413.AB.1
  
 7) NOTE: GROUNDING ELECTRODE CONDUCTOR AND BUILDING
 FOOTER STEEL REQUIRED AT THE DETACHED STRUCTURE.
 250.32,250.50 ETC
  
 8) NOTE: PLEASE KNOW THAT WIND LOAD CALCULATIONS WILL
 BE REQUIRED TO BE SUBMITTED AND REVIEWED FOR MINIMUM
 CODE COMPLIANCE. THIS WILL BE A BUILDING REVIEW COMMENT
 HOWEVER IT IS NOTED FOR INFORMATION ONLY. THIS IS AN
 ITEM WHICH MAY BE A PROVISO ITEM.
 PLEASE ALSO KNOW THAT PER NEW BUILDING OFFICIAL THE
 SITE LIGHTING MAY BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT. PLEASE CONTACT THE NEW CONSTRUCTION SERVICES
 DIRECTOR TO CONFIRM.
  
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-12-09 Cont ID  
Sent By efabian Date 2009-07-17 Time 11:02 Rev Time 0.00
Received By efabian Date 2009-12-09 Time 13:47 Sent To FIRE
Notes
2009-07-17 11:08:01FAILED -
  
 1. PLEASE PROVIDE WATER SERVICE FLOW CALCULATIONS TO
 ENSURE ADEQUATE OPERATING PRESSURES FOR PROPOSED
 FACILITY
  
 2. PLEASE PROVIDE A DETAIL OF PROPOSED 1 INCH WATER
 SERVICE INTO EXISTING 1 INCH WATER SERVICE TO REST ROOM
 FACILITY

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status P Date 2009-11-16 Cont ID  
Sent By efabian Date 2009-11-16 Time 09:28 Rev Time 0.00
Received By efabian Date 2009-11-16 Time 09:28 Sent To  
Notes
2009-12-02 09:15:08PASSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-13 Cont ID  
Sent By efabian Date 2009-12-09 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2009-11-13 Time 12:38 Sent To  
Notes
2009-11-13 12:40:10PLANS PREVIOUSLY APPROVED BY THIS OFFICE. PLANS WERE
 STAMPED WITH APPROPRIATE STAMPS BY FIRE RESCUE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2009-07-27 Time   Rev Time 0.00
Received By mcarsill Date 2009-07-27 Time 07:57 Sent To  
Notes
2009-07-27 08:01:13PALN REVIEW ONLY
 2400 NORTH FLAGLER DRIVE - CURRIE PARK
  
 1. SUITABLE ROADS AND ACCESS LANES SHALL BE PROVIDED
 FOR FIRE AND PARAMEDICAL PURPOSES DURING CONSTRUCTION
 ACTIVITES.
  
 2. TENNIS SHADE STRUCTURE SHALL BE OF FLAME RETARDANT
 MATERIAL.
  
 3. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-09 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 16:49 Rev Time 0.00
Received By jgomez Date 2009-11-09 Time 09:04 Sent To  
Notes
2009-11-09 09:04:49SENT TO BOX #C27.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-28 Time   Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 10:52 Sent To  
Notes
2009-07-01 10:56:25C-19

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-12-09 Cont ID  
Sent By rkussner Date 2009-12-09 Time 15:42 Rev Time 0.00
Received By rkussner Date 2009-12-09 Time 15:42 Sent To  
Notes
2009-12-09 15:45:38***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 A SEPARATE LANDSCAPE PERMIT IS REQUIRED. IT MUST BE
 SUBMITTED, APPROVED AND THE WORK INSPECTED PRIOR TO THE
 ISSUANCE OF A C/O.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-11-16 Cont ID  
Sent By rkussner Date 2009-11-16 Time 16:32 Rev Time 0.00
Received By rkussner Date 2009-11-16 Time 16:32 Sent To  
Notes
2009-11-16 17:19:35***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. LANDSCAPE COMMENTS MADE ON 7/9/09 HAVE NOT BEEN
 ADDRESSED.
  
 2. PURSUANT TO SECTION 94-443 (C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY A LANDSCAPE
 ISLAND AND THE LANDSCAPE ISLAND SHALL CONTAIN AT LEAST
 ONE SHADE OR FLOWERING TREE. THE ISLAND AT THE
 NORTHWEST PORTION OF THE SITE IS MISSING THE REQUIRED
 TREE.
  
 3. PURSUANT TO SECTION 94-448 (F)(11), TREES WHICH ARE
 INCLUDED AS PROHIBITED TREES PURSUANT TO SUBSECTION
 94-445(4)(I) SHALL BE REMOVED AND DISPOSED OF FROM THE
 ENTIRE SITE BEFORE A CERTIFICATE OF OCCUPANCY CAN BE
 OBTAINED.
  
 4. PURSUANT TO SECTION 94-443 (E)(1), AT LEAST 30
 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR OF ALL
 COMMERCIAL STRUCTURES SHALL BE PLANTED WITH TREES,
 SHRUBS OR HEDGES. MUCH OF THE PLANTING SHOWN AROUND THE
 STRUCTURES IS SHOWN AS OPTIONAL. AT LEASE 30 PERCENT
 WILL BE REQUIRED.
  
 5. PURSUANT TO SECTION 94-443 (C)(3)(B), ONE INTERIOR
 LANDSCAPE ISLAND SHALL BE PROVIDED FOR EVERY TEN
 PARKING SPACES OR FRACTION THEREOF. ONE SHADE OR
 FLOWERING TREE IS REQUIRED IN EVERY INTEROR ISLAND.
 TREES ARE MISSING FROM THE IINTERIOR SLANDS THAT ARE
 CENTERED WITHIN THE TWO ROWS OF PARKING LOCATED EAST OF
 THE TENNIS COURTS. IN ADDTION, THE LANDSCAPE STRIP THAT
 SEPARATES THE DRIVE AISLE FROM THE ROW OF PARKING EAST
 OF THE TENNIS COURTS SHALL HAVE AT LEAST ONE TREE FOR
 EACH 30 LINEAR FEET. ADDITIONAL TREES WILL NEED TO BE
 PLANTED TO FULLY ESTABLISH THE TREE LINE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-09 Cont ID  
Sent By rkussner Date 2009-07-09 Time 11:19 Rev Time 0.00
Received By rkussner Date 2009-07-09 Time 11:19 Sent To  
Notes
2009-07-09 11:26:00***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-448(D)(1), HISTORIC TREES,
 SPECIMEN TREES AND ANY OTHER TREES OR VEGETATION
 LOCATED ON PROPERTY SUBJECT TO THE PROVISIONS OF THIS
 SECTION SHALL NOT BE REMOVED, RELOCATED OR REPLACED
 UNLESS A TREE ALTERATION PERMIT IS OBTAINED.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF THE LANDSCAPE PLAN
 WITH ALL TABULATION NECESSARY FOR THE EVALUATION OF
 COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 13:58 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 13:57 Sent To  
Notes
2009-07-28 13:58:17PROPOSED RESTROOM BUILDING HAS ADEQUATE NATURAL
 VENTILATION. NO MECHANICAL PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status N Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-11-19 Time 10:51 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 10:51 Sent To  
Notes
2009-11-19 10:52:53PLUMBING PLANS DELETED FROM SETS OF PLANS. A SEPARATE
 PLUMBING PERMIT SHALL BE SUBMITTED WITH PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 15:01 Rev Time 0.00
Received By kstevens Date 2009-07-06 Time 15:01 Sent To  
Notes
2009-07-06 15:11:29DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS DT-1, DT-2, LS-1 THRU LS-4, LD-1, LD-2, LP-1
 THRU LP-5 & IR-1 REQUIRES A FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), AND PHONE NUMBER IN THE
 TITLE BLOCK OF EACH SHEET. ALSO THE DATE THE SIGNATURE
 AND SEAL ARE AFFIXED SHALL BE INDICATED ON THE SEAL.
 FAC 61G10-11.010(1)(2) & FS 481.219, 481.306.
  
 2. SHT EP1.0 WASTE RISER DIAGRAM. THE FITTING
 DOWNSTREAM OF THE WATER CLOSETS DOES NOT GUIDE THE
 SEWAGE & WASTE IN THE DIRECT OF FLOW AS REQUIRED IN
 SECTION 706.3. PLEASE CORRECT RISER DIAGRAM.
  
 3. SHT EP1.0 NOTE #1 OF THE WATER RISER. AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201.
  
 4. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE WATER
 PIPING. SHOW ALL PIPE SIZES, VALVES ETC. SECTION
 106.3.5.1.3(3)(10)(13). SECTION 601.1.
  
 5. ALL SHEETS DESIGNED BY A DESIGN PROFESSIONAL SHALL
 BE SIGNED, SEALED AND DATED BY THE DESIGN PROFESSIONAL.
 SECTION 106.1. SOME SHEETS ARE NOT SIGNED, SEALED OR
 DATED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-12-09 Cont ID  
Sent By jroach Date 2009-12-09 Time 16:54 Rev Time 0.00
Received By jroach Date 2009-12-09 Time 16:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-11-17 Cont ID  
Sent By jroach Date 2009-11-17 Time 16:13 Rev Time 0.00
Received By jroach Date 2009-11-17 Time 16:13 Sent To  
Notes
2009-11-17 16:27:45ZONING PLAN REVIEW
  
 PERMIT NO.: 09060761
 ADDRESS: 2400 N FLAGLER DR
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: CURRIE PARK IMPROVEMENTS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) REPEAT COMMENT - PHOTOMETRIC LEVELS SHALL BE
 EXTENDED TO THE NORTH PROPERTY LINE ADJACENT TO THE
 RESIDENTIAL DEVELOPMENT AND SHALL NOT EXCEED 0.5
 FOOTCANDLES.
  
 2) REPEAT COMMENT - STRIPING DETAIL SHALL BE PROVIDED
 FOR THE PARKING STALLS AND SHALL COMPLY WITH THE
 CITY???S MINIMUM STANDARDS (SEE ATTACHED DETAIL).
  
 3) REPEAT COMMENT - IS THERE ANY WAY TO ENCLOSE THE
 DUMPSTER LOCATED NEAR THE LOADING DOCKS? PURSUANT TO
 SECTION 94-444(B) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS, DUMPSTERS ARE TO BE COMPLETELY
 SCREENED. SCREENING SHALL CONSIST OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. LANDSCAPING SHALL ALSO BE
 PROVIDED ALONG THE EXTERIOR OF THE WALL/FENCE AND SHALL
 CONSIST OF SHRUB OR HEDGES PLANTED AT TWO (2) FOOT
 INTERVALS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-16 Cont ID  
Sent By jroach Date 2009-07-16 Time 11:05 Rev Time 0.00
Received By jroach Date 2009-07-16 Time 11:05 Sent To  
Notes
2009-07-16 11:39:18ZONING PLAN REVIEW
  
 PERMIT NO.: 09060761
 ADDRESS: 2400 N FLAGLER DR
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: CURRIE PARK IMPROVEMENTS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF CURRENT / ACCURATE SURVEY SHALL BE
 SUBMITTED WITH THE PERMIT APPLICATION.
  
 2) THE OVERALL BUILDING HEIGHT SHALL BE PROVIDED FOR
 ALL STRUCTURES (I.E. PAVILIONS, BATHROOM BUILDING,
 ETC.). OVERALL HEIGHT SHALL BE MEASURED FROM FINISHED
 GRADE TO THE MEAN POINT OF THE PITCHED ROOF.
  
 3) PHOTOMETRIC LEVELS SHALL BE EXTENDED TO THE NORTH
 PROPERTY LINE ADJACENT TO THE RESIDENTIAL DEVELOPMENT
 AND SHALL NOT EXCEED 0.5 FOOTCANDLES.
  
 4) STRIPING DETAIL SHALL BE PROVIDED FOR THE PARKING
 STALLS AND SHALL COMPLY WITH THE CITY???S MINIMUM
 STANDARDS (SEE ATTACHED DETAIL).
  
 5) SETBACKS SHALL BE PROVIDED FOR ALL STRUCTURES (I.E.
 PAVILIONS, BATHROOM BUILDING, ETC.). SETBACKS SHALL BE
 MEASURED FROM THE EXTERIOR OF THE STRUCTURE TO ADJACENT
 PROPERTY LINES.
  
 6) IS THERE ANY WAY TO ENCLOSE THE DUMPSTER LOCATED
 NEAR THE LOADING DOCKS? PURSUANT TO SECTION 94-444(B)
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS,
 DUMPSTERS ARE TO BE COMPLETELY SCREENED. SCREENING
 SHALL CONSIST OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL. LANDSCAPING SHALL ALSO BE PROVIDED ALONG THE
 EXTERIOR OF THE WALL/FENCE AND SHALL CONSIST OF SHRUB
 OR HEDGES PLANTED AT TWO (2) FOOT INTERVALS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved