Plan Review Details - Permit 09060742
Plan Review Stops For Permit 09060742
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-01 Cont ID  
Sent By rmcdouga Date 2009-12-01 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2009-12-01 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-22 Cont ID  
Sent By rmcdouga Date 2009-07-22 Time 09:59 Rev Time 0.00
Received By rmcdouga Date 2009-07-22 Time 09:59 Sent To  
Notes
2009-07-21 14:11:522007 FBC W/2009 REVISIONS
 RESIDENTIAL ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SIGNED AND SEALED SITE PLAN
 OR A SURVEY SHOWING THE LOCATION OF THE PROPOSED
 ADDITION AND DISTANCES TO THE PROPERTY LINES.
  
 2) SHEET 1 OF THE PLANS SPECIFIES THE SCOPE OF WORK AS
 A LEVEL 2 ALTERATION. THIS IS INCORRECT. THE PROJECT IS
 A LEVEL 3 ALTERATION AND AN ADDITION.
  
 3) THE VALUE SPECIFIED FOR THE PROJECT ON THE
 APPLICATION IS LOW AND HAS BEEN ADJUSTED BASED ON ICC
 VALUATION TABLES. ADDITIONAL PERMIT FEES ARE OWED.
  
 4) THE WINDOW BUCK DETAIL ON SHEET 5 DOES NOT SPECIFY
 THE FASTENERS OR SPACING FOR ATTACHING THE BUCKS TO THE
 MASONRY OPENINGS. PLEASE SPECIFY ATTACHMENT.
  
 5) THE DOOR BUCK DETAIL ON SHEET 5 DOES NOT INDICATE
 THE ATTACHMENT OF THE BUCK TO THE MASONRY OPENING.
 PLEASE SPECIFY THE ATTACHMENTS. ALSO THE DOOR JAMB TO
 BUCK ATTACHMENT IS SPECIFIED WITH 8D NAILS AND THE
 PRODUCT APPROVAL SPECIFIES SCREWS. PLEASE CORRECT.
  
 6) SPECIFY THE REQUIRED LOADS FOR THE FLOOR TRUSSES ON
 THE PLANS. FBC R 301.4 AND R301.5.
  
 7) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING-SHANK NAILS. PLEASE REVISE THE
 NOTES ON THE WALL SECTION ON SHEET 5 OF THE PLANS.
  
 8) SPECIFY THE INSULATION ON THE WALL SECTION AT THE
 MASONRY WALL AND AT THE EXTERIOR WALL AT THE FLOOR
 TRUSSES. FBC 13-600
  
 9) THE ROOF LOADS SPECIFIED ON SHEET 1 DO NOT MATCH THE
 ONES ON THE TRUSS DRAWINGS. PLEASE CORRECT.
  
 10) WHERE STUCCO IS TO BE APPLIED TO LATH OVER FRAME
 CONSTRUCTION A BOND BREAK IS REQUIRED BETWEEN THE
 WATER-RESISTIVE BARRIER AND THE STUCCO PER FBC
 R703.6.3. SPECIFY TWO LAYERS OF APPROVED
 WATER-RESISTANT BARRIER (ASPHALT FELT) OR OTHER
 APPROVED METHOD OR MATERIALS.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 GAF SHINGLES FL183 IS FOR THE 2001 FBC AND IS NOT
 ACCEPTABLE FOR THE CURRENT CODE WHICH IS THE 2007 FBC.
 ALSO THE NOA # 06-0331.12 FOR THE SHINGLES IS CLOSED.
 SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES. DCA RULE 9B-72
  
 12) THE FL PRODUCT APPROVAL COVERSHEET FOR THE SINGLE
 HUNG WINDOWS IS FOR THE 2004 FBC AND IS NOT ACCEPTABLE
 FOR THE CURRENT CODE WHICH IS THE 2007 FBC. HOWEVER,
 THE MIAMI DADE NOA THAT WAS SUBMITTED IS CURRENT AND
 ACCEPTABLE WITHOUT THE FL COVERSHEET.
  
 13) THE TRUSS LAYOUT AND DRAWINGS ARE NOT REQUIRED TO
 BE SUBMITTED FOR PLAN REVIEW FOR SINGLE FAMILY
 RESIDENCES. HOWEVER, THEY ARE REQUIRED TO BE GIVEN TO
 THE BUILDING INSPECTOR AT THE ROOF FRAMING INSPECTION.
 BECAUSE THE TRUSS INFORMATION WAS SUBMITTED IT WAS
 REVIEWED AND A NUMBER OF DEFICIENCIES WERE FOUND AS
 FOLLOWS. THE TRUSS LAYOUT AND DRAWINGS ARE REQUIRED TO
 HAVE THE ORIGINAL SIGNATURE OF THE TRUSS ENGINEER PER
 FS471. SIGNATURE STAMPS AND COPIES ARE NOT ACCEPTABLE.
 THE ROOF LOADS DO NOT CORRESPOND TO THE PLANS. THE
 BOTTOM CORD LIVE LOAD FOR THE ROOF TRUSSES IS REQUIRED
 TO BE A MINIMUM OF 10 PSF PER FBC R301.5. THE LOADS ARE
 NOT SPECIFIED ON THE TRUSS LAYOUT. THE TRUSS DRAWINGS
 ARE MISSING REQUIRED INFORMATION SUCH AS UPLIFT,
 WINDSPEED, DESIGN CRITERIA, ETC. PAGE 8 OF THE TRUSS
 DRAWINGS SPECIFIES THE WRONG EDITION OF ASCE 7, WHICH
 SHOULD BE ASCE 7-05 FOR THE 2007 FBC. PAGE 1 LISTS THE
 TRUSS DESIGN PER IBC NOT FBC. PLEASE CORRECT THE
 DEFICIENCIES BEFORE TRUSS DRAWINGS ARE GIVEN TO THE
 BUILDING INSPECTOR AT THE ROOF FRAMING INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-26 Cont ID  
Sent By btrobaug Date 2009-10-26 Time 11:13 Rev Time 0.00
Received By btrobaug Date 2009-10-26 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-07-10 Cont ID  
Sent By btrobaug Date 2009-07-10 Time 16:45 Rev Time 0.00
Received By btrobaug Date 2009-07-10 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-19 Cont ID  
Sent By dpalmer Date 2009-10-19 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2009-10-19 Time 15:39 Sent To  
Notes
2009-10-19 15:39:50R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-22 Cont ID  
Sent By rmcdouga Date 2009-07-22 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2009-07-22 Time 10:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-01-05 Cont ID  
Sent By rmcdouga Date 2010-01-05 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2010-01-05 Time 09:18 Sent To  
Notes
2010-01-05 09:19:32SUBMITTED PAID RECEIPT AND PLAN STAMPED FOR IMPACT
 FEES.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-07-21 Cont ID  
Sent By rmcdouga Date 2009-07-21 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2009-07-21 Time 10:37 Sent To  
Notes
2009-07-21 10:38:38NEED TO PAY COUNTY IMPACT FEES.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-10-20 Cont ID  
Sent By rkussner Date 2009-10-20 Time 12:20 Rev Time 0.00
Received By rkussner Date 2009-10-20 Time 12:20 Sent To  
Notes
2009-10-20 12:29:37***LANDSCAPE PLAN APPROVED WITH PROVISO***
  
 1, LIVE OAKS MUST BE SET BACK 30 FEET FROM FRONT
 PROPERTY LINE.
  
 2. SUBMIT TREE ALTERATION PERMIT APPLICATION IF ANY
 TREES ARE TO BE REMOVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By rkussner Date 2009-07-02 Time 14:44 Rev Time 0.00
Received By rkussner Date 2009-07-02 Time 14:44 Sent To  
Notes
2009-07-02 14:48:22***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE PROVIDE THE REQUIRED XERISCAPE DESIGN
 OPTIONS.
  
 2. PROVIDE 120% IRRIGATION COVERAGE TO ALL LANDSCAPED
 AREAS, INCLUDING RIGHT-OF-WAY. AN IRRIGATION PERMIT IS
 REQUIRED.
  
 3. SUBMIT A COST ESTIMATE THE INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR.
  
 4. PLANTING ALONG THE FOUNDATION OF THE BUILDING SHOULD
 BE PROVIDED ON THE STREET SIDE OF THE STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 12:01 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-17 Cont ID  
Sent By rregueir Date 2009-07-17 Time 16:09 Rev Time 0.00
Received By rregueir Date 2009-07-17 Time 15:59 Sent To  
Notes
2009-07-17 16:09:24REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A6 SHOWS CONDENSER AT REAR OF HOUSE WHILE M1
 SHOWS CONDENSERS ON SIDE OF HOUSE. PLEASE CORRELATE
 PLANS AND SHOW THE CORRECT LOCATION ON SITE PLAN FOR
 ZONING REVIEW.
  
 2. THE ENERGY CODE COMPLIANCE FORM SUBMITTED IS NO
 LONGER VALID. THE CORRECT FORM FOR THIS PROJECT IS FORM
 1100A-08 AS OF MARCH 1, 2009. PLEASE SUBMIT THE CORRECT
 COMPLETED FORM TO DEMONSTRATE COMPLIANCE WITH FBC-R
 CHAPTER 11
  
 3. PROVIDE COOLING AND HEATING LOAD CALCULATIONS
 ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBC-R SECTION N1107.AB.1
  
 4. PROVIDE EQUIPMENT SCHEDULE ON PLANS PER FBC-R
 SECTION M1401.1
  
 5. DUCT SIZE MISSING ON PLANS FROM AHU TO FIRST
 DISTRIBUTION BOX. PROVIDE MISSING INFORMATION PER FBC-R
 SECTION N1110.A.1
  
 6. CONTRACTOR SHALL PROVIDE SIGNATURE AND LICENSE
 NUMBER ON PLANS AS DESIGNER OF RECORD.
  
 7. PROVIDE MANUAL D TO SHOW JUSTIFICATION FOR DUCT
 DESIGN PER FBC-R SECTION N1110.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-10-21 Cont ID  
Sent By kstevens Date 2009-10-21 Time 17:38 Rev Time 0.00
Received By kstevens Date 2009-10-21 Time 17:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-10 Cont ID  
Sent By kstevens Date 2009-07-10 Time 08:49 Rev Time 0.00
Received By kstevens Date 2009-07-10 Time 08:49 Sent To  
Notes
2009-07-10 09:00:10DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
 1. SHT 2 OF 6 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE RISER DIAGRAM SHOWS THE LAVS PAST THE
 TUBS, BUT THE FLOOR PLAN SHOWS THE LAVS AHEAD OF THE
 WATER CLOSETS. -- ALSO THE FIXTURES FROM THE SECOND
 FLOOR SHALL NOT DRAIN THROUGH THE VENT FOR THE FIRST
 FLOOR FIXTURES. SECTIONS 3107.1, 3107.2 & 3107.3. --
 THE SECOND FLOOR FIXTURES SHALL NOT DISCHARGE THROUGH
 THE HORIZONTAL WET VENT FOR THE FIRST FLOOR BATHROOM
 FIXTURES. SECTION 3108.1. -- A SECOND RISER CONNECTED
 PRIOR TO THE BATHROOM FIXTURES IS REQUIRED FOR THE
 SECOND FLOOR BATHROOM FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-21 Cont ID  
Sent By jroach Date 2009-10-21 Time 15:48 Rev Time 0.00
Received By jroach Date 2009-10-21 Time 15:48 Sent To  
Notes
2009-10-21 15:55:14ZONING PLAN REVIEW
  
 PERMIT NO.: 09060742
 ADDRESS: 1120 11TH STREET
 CONTRACTOR/CONTACT: SYLVESTER MCKINAN
 TELEPHONE NO.: 561.628.4195
 SCOPE OF REVIEW: RENOVATIONS/ADDITIONS TO EXISTING
 RESIDENCE.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) THE A/C EQUIPMENT LOCATED ON THE EAST SIDE OF THE
 BUILDING SHALL BE NO CLOSER THAN ONE (1) FOOT TO THE
 PROPERTY LINE.
  
 2) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY, THE
 EXISTING SHED SHALL BE DEMOLISHED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-22 Cont ID  
Sent By mcruz Date 2009-07-22 Time 14:29 Rev Time 0.00
Received By mcruz Date 2009-07-22 Time 14:10 Sent To  
Notes
2009-07-22 14:29:47PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. INDICATE PRINCIPAL STRUCTURE SETBACKS TO REAR AND
 SIDE PROPERTY LINES. NOTE: PURSUANT TO THE ZLDR,
 SECTION 94-74: SINGLE FAMILY HIGH DENSITY (SF14)
 RESIDENTIAL DISTRICT - MINIMUM SETBACKS FOR PRINCIPAL
 BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED OR
 RELOCATED A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT
 THE ZLDR, SECTION 94-305(B)(4): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 5. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B): OVERHANGS SHALL NOT PROJECT MORE THAN THREE
 (3) FEET INTO A REQUIRED SETBACK.
  
 6. IS THE EXISTING GOING TO BE DEMOLISHED? IF NOT,
 INDICATE THE SEPARATION DISTANCE OF THE PROPOSED
 ADDITION TO THE EXISTING SHED. NOTE: PURSUANT TO THE
 ZLDR, ACCESSORY STRUCTURES SHALL BE LOCATED NO CLOSER
 THAN SIX (6) FEET TO THE PRINCIPAL STRUCTURE.
  
 7. CLEARLY INDICATE ON THE FLOOR LAYOUT AND ELEVATION
 PLAN THE LOCATION OF THE PROPOSED WORK, BY LABELING THE
 AREA "PROPOSED" VS. "EXISTING.
  
 8. PURSUANT TO THE ZLDR, SECTION 94-482(A): REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
  
 ADDITIONALLY, A RIGHT-OF-WAY PERMIT WILL NEED TO BE
 ACQUIRED FROM THE CITYS ENGINEERING DEPARTMENT
 (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION.
  
 9. THE COUNTY'S PROPERTY APPRAISER'S OFFICE RECORDS
 SHOW THAT THE SUBJECT SITE IS OWNED BY THE DO IR RIGHT
 CHURCH OF JESUS CHRIST, GOD AND THE HOLY GHOST...WHAT
 IS THE INTENDED USE FOR THE SUBJECT SITE? PLEASE NOTE,
 PURSUANT TO THE ZLDR, SECTION 94-272, PERMITTED USE
 TABLE, CHURCHES, SYNAGOGUES, AND PLACES OF WORSHIP
 REQUIRE A CLASS B SPECIAL USE PERMIT APPROVED BY THE
 ZONING BOARD OF APPEALS. CONSULT WITH THE PLANNING AND
 ZONING DEPARTMENT AT 561.822.1435, FOR DEVELOPMENT
 APPLICATION REQUIREMENTS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  