2009-06-26 16:55:14 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- CLEARLY MARK ON ROOF TILE NOA 07-0220.04 SUBMITTED |
| WHICH FASTENING OPTION IS GOING TO BE USED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| 2007 FLORIDA RESIDENTIAL CODE. SEE TABLES 4 AND 5 AND |
| MARK SPECIFIC FASTENING OPTION. PROVIDE PRODUCT |
| APPROVAL IF USING ANY TYPE OF ADHESIVE. |
| |
| 2- FLAT ROOF PRODUCT APPROVAL NOA 09-0224.01 SUBMITTED. |
| CLEARLY MARK WHICH APPROVED ASSEMBLY AND BASE SHEET |
| FASTENING OPTION IS GOING TO BE USED. IF SELECTED |
| ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7 THEN |
| PROVIDE RAS 117 CALCULATIONS SIGNED AND SEALED AS |
| REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| SUBMITTED. IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #9, THEN IT CAN'T BE USED FOR THIS BUILDING |
| BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES AND NAIL |
| ENHANCING IS NOT ALLOWED. |
| ***NOTE: DESIGN PROFESSIONAL DOING RAS 117 CALCULATIONS |
| TO HAVE INTO CONSIDERATION THAT ACCORDING TO THE 2009 |
| REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE THIS |
| BUILDING IS LOCATED ON EXPOSURE "C". |
| |
| 3- HOUSE VALUE IS MORE THAN $300,000. NEED TO COMPLY |
| WITH THE ROOF TO WALL CONNECTIONS OF SEC. R611.8.1 OF |
| 2009 REVISIONS TO THE 2007 FLORIDA EXISTING BUILDING |
| CODE. PROVIDE COMPLETE SPECIFICATIONS PACKAGE SHOWING |
| COMPLIANCE WITH THIS SECTION. |
| |