Plan Review Stops For Permit 09060714 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-07-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-07-03 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-07-03 |
Time |
10:45 |
Sent To |
PC |
|
Notes |
2009-07-03 10:46:01 | | | ** DENIED | | | | | | 1) NOTE: NEED LAYOUT OF EQUIPMENT LOCATIONS IN ROOMS | | AND AREAS. SEE NOTE #3. | | | | 2) NOTE: PLEASE INDICATE CONDUCTOR SIZES FOR EQUIPMENT. | | IS PUMP 120V? EXISTING? NEW? THE PERMIT WHICH WAS | | PULLED IN OCTOBER DID NOT PROVIDE ELECTRICAL | | INFORMATION OR VALUE FOR COMPLETE SCOPE. | | 310.16, FBC 106.1.1, 106.1.2 | | | | 3) NOTE: PLANS NEED TO SHOW LOCATIONS AND ALL WIRING | | METHODS UNDER NEC 500, 500.4,.6,501.5, 505. | | PLEASE SEE NFPA-50A, AND B. | | | | 4) NOTE: PERSON RESPONSIBLE FOR PLANS NEEDS TO PRINT | | NAME AND SIGN WHEN MEETING EXCEPTIONS TO FS | | 471.003,481.229. | | | | 5) NOTE: VALUE FOR COMPLETE SCOPE OF WORK INCLUDING ALL | | EQUIPMENT EVEN IF OWNER SUPPLIED NEEDS TO BE INCLUDED. | | FBC 108.3. AS THE COMPLETED VALUE AND SCOPE WAS NOT | | PART OF MAIN PERMIT, IT LEAVES ALL PUMP AND WIRING ETC | | VALUE UNDER ELECTRICAL. THE PERMIT MAY ALSO NEED ONE | | FOR ANY LINE VOLTAGE EQUIPMENT AS LOW VOLTAGE PERMIT | | WAS APPLIED. FBC 105.1 IT IS NOT KNOWN AT THIS TIME. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
|