Plan Review Details - Permit 09060684
Plan Review Stops For Permit 09060684
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-06 Cont ID  
Sent By jgomez Date 2009-08-06 Time 09:41 Rev Time 0.00
Received By jgomez Date 2009-08-06 Time 09:41 Sent To Z
Notes
2009-08-06 09:42:12SENT TO ZONING BOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-30 Cont ID  
Sent By jgomez Date 2009-07-30 Time 13:58 Rev Time 0.00
Received By jgomez Date 2009-07-30 Time 13:57 Sent To PC
Notes
2009-07-30 13:58:17NEW SIGN, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- COORDINATE SIZE OF LETTERS WITH ZONING COMMENTS.
  
 3- SEE ELECTRICAL COMMENTS REGARDING ENGINEER SEAL AND
 TOTAL PERMIT VALUATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2009-08-05 Time 12:11 Sent To Z
Notes
2009-08-05 12:17:47REDLINED PLANS FOR DISCONNECT, 600.5

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By dpalmer Date 2009-07-27 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2009-07-27 Time 09:49 Sent To B
Notes
2009-07-27 09:49:25 
 ** DENIED REVIEW. **
  
 1) NOTE: THE SEAL USED BY THE ENGINEER ON PLANS IS NO
 LONGER VALID IN THE STATE OF FLORIDA. IN FACT THE SEAL
 HAS NOT BEEN VALID FOR MANY YEARS. THE RULING UNDER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001 REQUIRED
 ENGINEERS TO UPDATE THEIR SEALS TO NEW REQUIREMENTS.
 THIS RULE WAS PASSED IN FEBRUARY OF 2004. THE STATE DID
 GRANT AN EXTENSION HOWEVER THE FINAL DATE OF EXTENSION
 WAS DECEMBER 31ST 2005. AT THAT TIME THE SEALS WITH THE
 WORDING OF *CERTIFICATE* WERE NO LONGER ACCEPTABLE OR
 TO BE USED.
 THE LICENSE NUMBER ON SAID PLANS IS STILL VALID WITH
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE OBTAIN NEW SEAL. PLEASE SIGN, DATE AND SEAL NEW
 PLANS UNDER FLORIDA STATUTES 471.025.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE: PLEASE SEE THAT THE ELECTRICAL DETAIL/PLAN
 SUBMITTED CONTAINS NO DESIGN PROFESSIONAL PER 471, 481
 OR 489. WHEN MEETING EXCEPTIONS TO 471.003 THEN PLANS
 MUST STILL BE UNDER THE DESIGN OF A LICENSED CONTRACTOR
 PER 489.
  
 3) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST, INSTALLATION ETC EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. THE APPLIED VALUE FOR THE
 COMPLETE SCOPE OF WORK AT $7,000 IS LOW.
 FBC 108.3.
 PLEASE PROVIDE COPY OF SIGNED CONTRACTS FOR ALL OF THE
 ABOVE.
  
 ** PER BUILDING OFFICIAL. PLANS AND PERMIT APPLICATIONS
 ARE NO LONGER RELEASED AND SHALL REMAIN ON FILE.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 12:11 Rev Time 0.00
Received By dpalmer Date   Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-30 Cont ID  
Sent By jgomez Date 2009-07-30 Time 13:58 Rev Time 0.00
Received By jgomez Date 2009-07-01 Time 09:15 Sent To  
Notes
2009-07-01 09:15:31TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2009-08-11 Cont ID  
Sent By lfranco Date 2009-08-11 Time 18:16 Rev Time 0.00
Received By lfranco Date 2009-08-11 Time 18:16 Sent To B
Notes
2009-08-11 18:17:27PLANNING AND ZONING: **** PASSED WITH PROVISO, AN
 APPLICATION FOR A MINOR AMENDMENT TO THE METROCENTRE
 CPD SHOWING THE PROPOSED SIGNAGE WILL BE REQUIRED TO BE
 FILED TO THE PLANNING AND ZONING DEPARTMENT AND
 APPROVED PRIOR TO THE CO BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 THE FOLLOWING, BUT NOT LIMITED TO ITEMS SHALL BE SHOWN
 ON THE PLANS SUBMITTED:
  
 THE TOTAL SQUARE FOOTAGE OF ALL SIGNAGE SHALL BE SHOWN
 ON A SITE DATA IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR"). REFER TO THE ZLDR FOR
 SIGNAGE REGULATIONS, UNDER THE GENERAL COMMERCIAL (GC)
 ZONING DISTRICT. ADDITIONALLY, AN APPROVAL LETTER FROM
 THE METROCENTRE ARCHITECTURAL REVIEW BOARD SHALL BE
 SUBMITTED ALONG WITH THE MINOR PD AMENDMENT
 APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-24 Cont ID  
Sent By lfranco Date 2009-07-24 Time 17:56 Rev Time 0.00
Received By lfranco Date 2009-07-24 Time 17:56 Sent To E
Notes
2009-07-24 18:08:51PLANNING AND ZONING: PLANNING AND ZONING
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. ELEVATIONS- WEST: THE DIMENSIONS ON SIGNAGE THAT IS
 USED TO CALCULATE TOTAL SQUARE FOOTAGE PER SIGN,
 EXCEEDS THE SQUARE FOOTAGE SHOWN UNDER THE FORMAL SITE
 PLAN REVIEW PLANS (PB878F) FOR THE HOTEL. PROVIDE TOTAL
 SQUARE FOOTAGE OF THE THE SIGN, BASED ON A "BOX"
 SURROUNDING THE PERIMETER OF THE ENTIRE SIGN.
 ADDITIONALLY, IF THIS WILL BE THE NEW SIZE FOR THE
 SIGNAGE, THEN AN APPLICATION FOR A MINOR AMENDMENT TO
 THE CPD SHOWING THE PROPOSED SIGNAGE WILL BE REQUIRED
 TO BE FILED TO THE PLANNING AND ZONING DEPARTMENT AND
 APPROVED PRIOR TO THE BUILDING PERMIT BEING APPROVED.
 SEE HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 THE FOLLOWING, BUT NOT LIMITED TO ITEMS SHALL BE SHOWN
 ON THE PLANS SUBMITTED:
  
 THE TOTAL SQUARE FOOTAGE OF ALL SIGNAGE SHALL BE SHOWN
 ON A SITE DATA IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR"). REFER TO THE ZLDR FOR
 SIGNAGE REGULATIONS, UNDER THE GENERAL COMMERCIAL (GC)
 ZONING DISTRICT. ADDITIONALLY, AN APPROVAL LETTER FROM
 THE METROCENTRE ARCHITECTURAL REVIEW BOARD SHALL BE
 SUBMITTED ALONG WITH THE MINOR PD AMENDMENT
 APPLICATION.
  
 3. CLARIFY WHY THE SAME SIGNAGE WAS SUBMITTED UNDER THE
 FOLLOWING PERMITS (09060222, 09060223, 09060225),
 FAILED ON CIRCA JUNE 2009? ADDRESS THESE COMMENTS WITH
 THE OTHER PERMITS TO AVOID DELAYS IN THE PERMITTING
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  