Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-07-13 Cont ID  
Sent By kstevens Date 2009-07-13 Time 08:52 Rev Time 0.00
Received By kstevens Date 2009-07-13 Time 08:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 08:58 Rev Time 0.00
Received By kstevens Date 2009-06-25 Time 10:02 Sent To  
Notes
2009-07-07 09:01:49DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- THE DISTANCE FOR THE
 MOST REMOTE FIXTURE IN THE HOUSE AFTER THE REGULATOR IS
 NOT INDICATED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  