Plan Review Details - Permit 09060605
Plan Review Stops For Permit 09060605 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-10-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-10-13 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-10-13 |
Time |
12:04 |
Sent To |
|
|
Notes |
2009-10-13 15:12:23 | *****APPROVED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED. THE FIRE ALARM PLAN (FA-1 THRU FA-17) | | FIRE-STAMPED ACCORDINGLY; READY FOR PERMIT ISSUANCE. | | | | | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2009-09-02 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-09-02 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-09-02 |
Time |
07:42 |
Sent To |
|
|
Notes |
2009-09-01 21:19:39 | *****DENIED***** | | | | OLD COMMENTS FROM PREVIOUS REVIEW WHICH STILL NEED TO | | BE ADDRESSED: | | | | | | 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS | | MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS | | SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) . | | SEQUENCE OF OPERATIONS MATRIX STILL INDICATES A | | SUPERVISORY SIGNAL FOR DUCT SMOKE DETECTOR | | | | 5. CORRELATE DRAWING MATCHLINES ACCORDINGLY. FOR | | EXAMPLE, SHEET 2 (OF 17)' S MATCHLINE IS NOTED AS | | "CONTINUED ON SHEET FA-2.5" , HOWEVER THERE IS NO | | FA-2.5 SHEET IN THE DRAWING LIST AND/OR THE PLAN SET. | | | | NEW COMMENT | | | | A. EXPLAIN WHY CERTAIN DEVICES SHOWN ON SHEET 9 (I.E. | | SMOKE DETECTORS - ABOVE THE FACP, IN THE SPRINKLER PUMP | | ROOM) ARE NOT SHOWN ON SHEET 2 . | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-07-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-07-24 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-07-15 |
Time |
12:53 |
Sent To |
|
|
Notes |
2009-07-24 13:32:15 | *****DENIED***** | | | | 1. ON SHEET 1 (OF 17), THE FIRE ALARM DRAWING LIST'S | | DRAWING NUMBERS DO NOT CORRELATE WITH THOSE LISTED IN | | THE TITLE BLOCKS OF THE SUBMITTED PLAN SHEETS. AMEND | | DRAWING NUMBER IN THE DRAWING LEGEND TO CORRELATE WITH | | THAT LISTED IN THE TITLE BLOCK. | | | | 2. ON SHEET 1 (OF 17) IN THE SEQUENCE OF OPERATIONS | | MATRIX, AMEND TO REFLECT THAT SMOKE DUCT DETECTORS | | SHALL INITIATE A GENERAL FIRE (AS PER LOCAL CODE) . | | | | 3. PROVIDE INFORMATION/SPECIFICATIONS FOR THE VESDA | | FIRE ALARM SYSTEM. | | | | 4. FIRE ALARM DEVICES ARE SHOWN FOR THE FUTURE PHASES | | OF THE FIRST LEVEL FIRE ALARM PLAN, HOWEVER NO SUCH | | DEVICES ARE SHOWN FOR THE FUTURE SPACES ON THE SECOND | | THRU FIFTH LEVEL. PLEASE EXPLAIN | | | | 5. IN REFERENCE TO COMMENT #1, CORRELATE DRAWING | | MATCHLINES ACCORDINGLY. | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-09-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-09-30 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-09-30 |
Time |
10:57 |
Sent To |
FIRE |
|
Notes |
2009-09-30 10:57:47 | SENT TO FIRE BOX. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-08-25 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-08-25 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-08-25 |
Time |
15:38 |
Sent To |
|
|
Notes |
2009-08-25 15:39:05 | IN FIRE BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-07-15 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-07-15 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-06-23 |
Time |
16:36 |
Sent To |
|
|
Notes |
2009-07-14 16:41:49 | PLANS PUT ON MIKE WILLIAMS DESK FOR REVIEW. PLANS FOUND | | IN OUT GOING BOX UP FRONT LM | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |