Plan Review Details - Permit 09060533
Plan Review Stops For Permit 09060533
Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-10-28 Cont ID  
Sent By mawillia Date 2009-10-28 Time 13:39 Rev Time 0.00
Received By mawillia Date 2009-10-28 Time 13:11 Sent To  
Notes
2009-10-28 13:28:52*****REVISIONS, 1 & 2, APPROVED*****
  
 THE REVISED PLAN (FA-1 & FA-2) WERE STAMPED, INTIALED,
 AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2009-10-27 Cont ID  
Sent By mawillia Date 2009-10-27 Time 15:08 Rev Time 0.00
Received By mawillia Date 2009-10-27 Time 14:35 Sent To  
Notes
2009-10-27 15:08:37*****REVISION, DATED 8/19/09, DENIED*****
  
  
 1. THE ENTIRE ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2. THE SUBMITTED PLAN SHEETS HAS THE STAMP OF
 PROFESSIONAL ENGINEER TIMOTHY C. TREWYN WITHOUT HIS
 SEAL AND SIGNATURE.
  
 3. SHOW THE NECESSARY CHANGE(S) ON SHEET FA-2 TO
 REFLECT THE PROJECT'S REVISION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-08-03 Cont ID  
Sent By mawillia Date 2009-08-03 Time 14:33 Rev Time 0.00
Received By mawillia Date 2009-08-03 Time 12:52 Sent To  
Notes
2009-08-03 14:37:16*****APPROVED*****
  
  
 THE FIRE ALARM PLAN SET (FA-1 & FA-2) WERE FIRE-STAMPED
 ACCORDINGLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-07-16 Cont ID  
Sent By mawillia Date 2009-07-16 Time 14:24 Rev Time 0.00
Received By mawillia Date 2009-07-16 Time 13:15 Sent To  
Notes
2009-07-16 14:20:49*****DENIED*****
  
 THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEEDS TO BE ADDRESSED:
  
 1. PLEASE PROVIDE A FLOOR PLAN SHOWING THE LAYOUT OF
 ALL EQUIPMENT PROPOSED WITHIN THIS SCOPE OF WORK OR
 PROVIDE A LETTER OR ADDENDUM TO THE APPROPIATE PLAN
 SHEET THAT THE AS-BUILTS DRAWINGS SHALL BE SUBMITTED
 AND APPROVED BY CONSTRUCTION SERVICES DEPARTMENT/FIRE
 PLAN REVIEW PRIOR TO THE FINAL FIRE ALARM INSPECTION.
  
 THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED:
  
 2. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH WITH THE IOSSUING
 AUTHORITHY EITHER A CERTIFIED COPY OF THE RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE OF COMMENCEMENT HAS BEEN FILED FOR
 RECORDING, ALONG WITH A COPY THEREOF.
  
 3. SINCE THE SCOPE OF WORK IS GREATER THAN $5000.00,
 ALL PLAN SHEETS ARE TO BE SEALED, SIGNED, AND DATED BY
 THE ENGINEER OF RECORD (AS PER FAC 61G15-23.002 AND/OR
 FS 472.025) WHOSE INFORMATION IS IN THE TITLE BLOCK.
 SEE SHEET FA-02
  
 4. THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 LOCATED IN THE TITLS BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 5. DRAWINGS FA-1 AND FA-2 ARE BOTH LISTED AS 1 OF 1
 SHEET NUMBERS. PLEASE AMEND TO 1 OF 2 AND 2 OF 2
 DRAWING/SHEET NUMBERS.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2009-07-09 Cont ID  
Sent By jgomez Date 2009-07-09 Time 13:58 Rev Time 0.00
Received By jgomez Date 2009-07-08 Time 13:58 Sent To FIRE
Notes
2009-07-16 13:12:32SHOULD HAVE BEEN AN I STOP.
2009-07-09 13:58:49SENT TO FIRE BOX.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-24 Cont ID  
Sent By mwennerg Date 2009-06-24 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2009-06-24 Time 11:17 Sent To  
Notes
2009-06-24 11:22:08***DENIED***
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LAYOUT OF
 ALL EQUIPMENT PROPOSED WITHIN THIS SCOPE OF WORK.
  
 2) WORK TO COMPLY WITH 2002, NFPA 72.
  
 3) LIFE SAFETY TO COMPLY WITH 2006, NFPA 101.
  
 4) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGRE, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 14:30 Sent To FIRE
Notes
2009-10-20 14:31:12T FIRE IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-22 Cont ID  
Sent By rmcdouga Date 2009-06-22 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2009-06-22 Time 10:09 Sent To  
Notes
2009-06-22 10:09:50SENT TO FIRE