Plan Review Details - Permit 09060505
Plan Review Stops For Permit 09060505
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-17 Cont ID  
Sent By shill Date 2009-07-17 Time 14:54 Rev Time 0.00
Received By shill Date 2009-07-17 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By shill Date 2009-06-22 Time 16:22 Rev Time 0.00
Received By shill Date 2009-06-22 Time 16:22 Sent To  
Notes
2009-06-22 16:28:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE SPECIFICATION FOR SOUNDPROOFING, FBC1207.
 SPECIFICATIONS TO SHOW COMPLIANCE WITH ASTM E90, ASTM
 E492.
  
 2. PROVIDE INFORMATION REGARDING THE WEIGHT OF THE
 FLOORING MATERIAL, FBC1606.2.
  
 3. PROVIDE AN ENGINEERING ANALYSIS TO PROVIDE EVIDENCE
 THAT THE EXISTING FLOOR CAN RESIST THE ADDITIONAL
 SUPERIMPOSED DEAD LOAD OF THE NEW FLOORING.
  
 4. THE ESTIMATE SUBMITTED IS FOR LABOR ONLY. THE VALUE
 IS TO INCLUDE ALL LABOR AND MATERIALS.
  
 5. TWO SETS OF ALL PERMIT DOCUMENTS REQUIRED, FBC106.
  
 6. PROVIDE SQUARE FOOT AREA OF EACH FLOORING MATERIAL
 TO BE INSTALLED, LINEAR FOOT AREA OF BASE. THIS MAY BE
 PROVIDED EITHER ON THE PERMIT APPLICATION OR IN A FLOOR
 PLAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-22 Cont ID  
Sent By shill Date 2009-06-22 Time 16:29 Rev Time 0.00
Received By shill Date 2009-07-17 Time 14:54 Sent To  
Notes
***NONE***