Plan Review Details - Permit 09060399
Plan Review Stops For Permit 09060399
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-01 Cont ID  
Sent By jwitmer Date 2009-07-01 Time 13:03 Rev Time 0.55
Received By jwitmer Date 2009-07-01 Time 13:03 Sent To  
Notes
2009-07-01 13:20:37BUILDING PROVISO: 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-31 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 09:11 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 09:11 Sent To  
Notes
2009-07-04 09:11:12 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
 ELECTRICAL PLANS THE * LATEST EDITION* WHICH IS NOT
 PERMITTED. ALL PLANS SHALL CONTAIN THE MINIMUM CODES IN
 WHICH THE DESIGN IS UNDER.
 PLEASE SEE THAT THE FOLLOWING FOR THIS PROJECT SHALL BE
 AS FOLLOWS.
 COVER SHEET HAS CONFLICTING SUPPLEMENTS FOR THE 2007
 FBC. ONE AREA SHOWS 2009 AND THE OTHER 2007.
  
 ELECTRICAL SHALL CONTAIN:
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-72
  
  
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012.
 FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS
  
 2) NOTE:
  
 3) NOTE: PLEASE SEE RISER. RISER SHOWS NEW BRANCH
 CIRCUIT #42, HOWEVER PER THE PANEL SCHEDULE SUBMITTED
 CIRCUIT #42 IS SHOWN BLANK.
 PLEASE COORDINATE PLANS FOR ALL.
 408.4.
  
 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER
 HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%.
  
 5) NOTE:
  
 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS ARE BASED
 ON A RESIDENTIAL USE. CODE SECTIONS ON LOAD
 CALCULATIONS ARE NOT FROM THE 2005 NEC. PLEASE SEE
 PLANS FOR EXAMPLE: 220.4,220.30. THE 2005 NEC HAS BEEN
 THE STATE ADOPTED CODE SINCE DECEMBER 8TH, 2006. PLANS
 STATE THE DESIGN IS UNDER THE *LATEST EDITION* OF THE
 NEC. PLEASE KNOW EVEN IF THIS WAS THE CASE AND THE 2008
 NEC WAS ADOPTED BY THE STATE, THERE IS NO 220.30, 220.4
 IN THE 2008 CODE.
  
 *** KEEP IN MIND LOADS FOR OFFICE EQUIPMENT AS OFFICE
 FOR EXAMPLE IS SHOWING ALL ON EXISTING CIRCUIT #17. ANY
 NEW COPIERS OR EQUIPMENT WHICH MAY EXCEED THE RATING OF
 THIS RESIDENTIAL BRANCH CIRCUIT?
  
 PLEASE SEE NEC 220 UNDER THE 2005 NEC.
 SINCE USE IS STILL SHOWN AS COMPLETELY RESIDENTIAL.
  
 7) NOTE: ALL CIRCUITS SHALL BE SPECIFIC ON PLANS.
 STATING GENERAL LIGHTS, OR GENERAL RECEPTACLES IS NOT
 PERMITTED. PLEASE SEE COMMENTARY UNDER THE 2005 NEC IN
 408.4
 PLEASE SEE ITEMS SUCH AS CIRCUIT #17.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-03 Cont ID  
Sent By mawillia Date 2009-08-03 Time 10:48 Rev Time 0.00
Received By mawillia Date 2009-08-03 Time 10:37 Sent To B
Notes
2009-08-03 10:45:18*****APPROVAL*****
  
 PLAN SHEET E1.01 WAS STAMPED, INITIALED, AND DATED;
 SHEET FP1.01WAS FIRE-STAMPED ON 7/07/2009.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By mawillia Date 2009-07-07 Time 15:43 Rev Time 0.00
Received By mawillia Date 2009-07-07 Time 15:15 Sent To  
Notes
2009-07-07 15:38:51*****PARTIAL APPROVAL*****
  
 PLAN SHEET FP1.01 WAS STAMPED, INITIALED, AND DATED;
 HOWEVER SHEET E1.01 TO BE FIRE-STAMPED WHEN THE
 ELETRICAL EXAMINER COMMENTS AS WELL AS THE FOLLOWING
 HAVE BEEN ADDRESSED:
  
 1. ON SHEET E1.01, SMOKE DETECTORS (SD)ARE SHOWN.
 PLEASE BE ADVISED THAT SMOKE ALARMS ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM. IF THESE DEVICES SOUND
 ONLY WITHIN THE INDIVIDUAL DWELLING UNIT AND DOES NOT
 ACTUATE THE BUILDING FIRE ALARM SYSTEM, SMOKE ALARMS
 (SA) INSTEAD OF SMOKE DETECTORS (SD) SHOULD BE
 LEGENDED/SYMBOLED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 09:28 Rev Time 0.00
Received By shill Date 2009-07-15 Time 09:28 Sent To  
Notes
2009-07-15 09:29:45B4
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-13 Cont ID  
Sent By lmartine Date 2009-07-07 Time 14:09 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 16:23 Sent To  
Notes
2009-06-16 16:23:06B-23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-01 Cont ID  
Sent By jwitmer Date 2009-07-01 Time 13:20 Rev Time 0.22
Received By jwitmer Date 2009-07-01 Time 13:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-08 Cont ID  
Sent By aaponte Date 2009-07-08 Time 11:16 Rev Time 0.00
Received By aaponte Date 2009-07-08 Time 11:16 Sent To  
Notes
***NONE***