Plan Review Details - Permit 09060324
Plan Review Stops For Permit 09060324
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-20 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 15:18 Rev Time 0.35
Received By jwitmer Date 2009-07-20 Time 14:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-10 Cont ID  
Sent By dpalmer Date 2009-09-10 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2009-09-10 Time 09:59 Sent To PC
Notes
2009-09-10 10:00:17** PROVISO **
  
 ** ALL OF THE FOLLOWING COMMENTS NEED TO BE ADDRESSED
 BEFORE ANY FINAL ELECTRICAL INSPECTION.
 ** OTHER ITEMS REVISED ON PLANS WHICH ARE NOT PART OF
 PROVISO, SHALL BE REVISED AND SUBMITTED BEFORE ROUGH
 ELECTRICAL INSPECTION.
 ****
 *PROVISO IS GIVEN AT THE REQUEST OF THE DESIGNER AND
 WILL BE COMPLETELY AT THE RISK OF CONTRACTOR,
 ELECTRICAL CONTRACTOR AND DESIGNER OF RECORD.
  
 1) NOTE: PLANS NEED TO SHOW ALL CIRCUITING FOR LIGHTING
 AND RECEPTACLES. THIS WILL NEED TO BE SUBMITTED AND
 COORDINATE WITH PANEL SCHEDULES WHICH HAVE NOT YET BEEN
 SUBMITTED AND SHOWN ON RECORD SET OF PLANS.
 408.4,310.16,240.4 ETC
  
 2) NOTE: ALL FINAL LOAD CALCULATIONS FOR ALL LIGHTING,
 RECEPTACLES AND OTHER LOADS SHALL BE COMPLETED ON
 RECORD SET OF PLANS.
 PLEASE SEE ALL OF NEC 220 FOR CODES SUCH AS
 220.12,220.14,220.42,220.44 ETC
 PLEASE SEE 215.3,230.42 ETC FOR CONTINUOUS LOADS.
  
 3) NOTE: PANEL AND TAPPED CONDUCTORS ON THE SECONDARY
 SIDE OF COMPUTER TRANSFORMER SHALL MEET 240.21,408.36,
 240.4,310.16 ETC
 THE PLANS ARE NOT COMPLETE WITH CONDUCTORS ETC SHOWN
 FOR EXISTING. THERE MAY BE CODE COMPLIANCE COMMENTS
 WHICH CAN NOT BE REVIEWED OR MADE AT THIS TIME. THIS
 MAY CREATE CHANGES NEEDED IN FIELD.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 14:06 Sent To  
Notes
2009-07-05 14:07:09 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES NEED TO BE
 UPDATED. THE COVER SHEET DOES LIST MOST OF THE CURRENT
 ADOPTED CODES HOWEVER NOT ALL.
 PLEASE SEE THE FOLLOWING.
  
 2006 NFPA-101. THIS EDITION WAS ADOPTED DECEMBER 31ST
 2008. FAC 69A-60.004
 2007 FLORIDA FIRE PREVENTION CODE.
  
 ALL PLANS SHALL CONTAIN MINIMUM DESIGN CODES.
  
 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS SHOWING
 MINIMUM CODE COMPLIANCE. PLEASE COORDINATE WITH PANEL
 SCHEDULES TO BE SUBMITTED.
 THERE ARE NUMEROUS ITEMS FOR MINIMUM CODE COMPLIANCE
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
 408.4,310.16,240,220 ETC PLEASE BE SURE TO CIRCUIT
 EMERGENCY AND EXIT LIGHTS PER 700.12F
  
 EVERYTHING IS SHOWN AS NEW. PLEASE PLACE ITEMS ABOVE ON
 PLANS. THE PLANS STATES MANY ITEMS ARE NO CLEAR ON
 PANELS YET LOADS FOR NEW CIRCUITS, RECEPTACLES ETC
 SHOULD BE KNOWN AT THIS TIME.
 THE PLANS ALSO STATE THE *ENTIRE* 8TH FLOOR IS FED FROM
 ONE 125AMP PANEL. IF THIS IS THE CASE THERE IS CONCERN
 ON LOADS ON EQUIPMENT. PLANS SHOW THREE SEPARATE PANELS
 ???
 ** ALL TENANTS ARE FED FROM ONE METER?
  
  
 4) NOTE: PLEASE SEE 13-415.AB.5 FOR MINIMUM CODE
 COMPLIANCE REQUIRED FOR LIGHTING PERFORMANCE
 CALCULATIONS.
 ** PLEASE BE SURE TO COMPLETE A FIXTURE LEGEND WHICH
 STATES THE SPECIFIC FIXTURES.
  
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-25 Cont ID  
Sent By mawillia Date 2009-08-25 Time 11:41 Rev Time 0.00
Received By mawillia Date 2009-08-25 Time 11:26 Sent To  
Notes
2009-08-25 11:41:42*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS.1 AND E1 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By mawillia Date 2009-07-20 Time 12:42 Rev Time 0.00
Received By mawillia Date 2009-07-20 Time 12:15 Sent To  
Notes
2009-07-20 12:42:43*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, NFPA 1, UNIFORM FIRE CODE,
 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, 2006
 EDITION SHALL BE REFERENCED. AMEND SHEET LS.1 TO
 REFLECT THE CURRENT CODE EDITIONS.
  
 3. PLEASE SHOW AND/OR EXPLAIN HOW THE PROJECT SCOPE OF
 WORK WILL AFFECT FIRE SPRINKLERS AND/OR FIRE ALARM
 DEVICES.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-11 Cont ID  
Sent By lmartine Date 2009-08-11 Time 11:58 Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 11:58 Sent To  
Notes
2009-08-11 11:58:39B-19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-20 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2009-06-12 Time 14:00 Sent To  
Notes
2009-06-16 14:00:58C-18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-27 Cont ID  
Sent By rregueir Date 2009-08-27 Time 16:08 Rev Time 0.00
Received By rregueir Date 2009-08-26 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 10:46 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 10:29 Sent To  
Notes
2009-07-20 10:46:49REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS FOR ALL
 RECONFIGURED SPACES PER FBC-EB 709.1.
  
 2. PROVIDE CFM ON PLAN TO SHOW PROPER AIR DISTRIBUTION
 IN ALL HABITABLE SPACES PER FBC-EB 711.1, FBC-B
 13-410.AB.4, FBC-M 403.3.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-14 Cont ID  
Sent By kstevens Date 2009-08-14 Time 14:13 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 14:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 09:17 Rev Time 0.00
Received By kstevens Date 2009-07-06 Time 09:17 Sent To  
Notes
2009-07-06 09:24:37DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHTS A1.1 & A6.1 SHOW THE CLEAR FLOOR SPACE REQUIRED
 PER SECTION 11-4.24.5.
  
 2. SHT A3.1 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.7 FAUCTES
  
 3. SHT MEP-1 THE AAV IS NOT APPROVED IN THE CEILING
 UTILIZED AS A PLENUM. SECTION 917.8.
  
 4. SUBMIT A WATER ISOMETRIC RISER DIAGRAM. SECTION
 106.3.5.1.3(3)(10)(13). SHOW ALL PIPE SIZES, VALVES
 AND, (WHERE REQUIRED), WATER HAMMER ARRESTORS. SECTIONS
 604.3, 604.9 & 606.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-18 Cont ID  
Sent By eschneid Date 2009-06-18 Time 08:48 Rev Time 0.25
Received By eschneid Date 2009-06-18 Time 08:48 Sent To  
Notes
2009-06-18 08:49:47NOT REQUIRED - INTERIOR WORK - VALUE OF THIS AND
 PERMITS WITHIN LAST YEAR ARE LESS THAN 50% OF THE VALUE
 OF THE BUILDING.