Plan Review Details - Permit 09060303
Plan Review Stops For Permit 09060303
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-03 Cont ID  
Sent By jwitmer Date 2009-09-03 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2009-09-03 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 14:10 Rev Time 1.00
Received By jwitmer Date 2009-07-08 Time 13:00 Sent To  
Notes
2009-07-08 13:29:55BUILDING PLAN REVIEW
 PERMIT: 09060303
 ADD: 3100 N MILIARY TRL
 CONT:ANDERSON- MOORE CONSTRUCTION
 TEL: (561)662-1818
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THIS PROJECT IS TO
 BECOME A PHASED BUILDING WITH PROTIONS OF THE INTERIOR
 ARE TO BE DESIGNED AND BUILT UNDER THIS PERMIT
 APPLICATION. THE ORIGINAL PERMIT 07060707 IS FOR THE
 WHOLE BUILDING INCLUDING THE SCOPE OF WORK INTENDED FOR
 THIS PHASED PERMIT.
  
 THERE ARE TWO ISSUES THAT WILL NEED TO BE CLEARED
 BEFORE THIS CAN BE DECLARED A PHASED PERMIT:
 1A) THE ORIGINAL BUILDING PERMIT WILL NEED TO COME IN
 WITH A LETTER AND REVISION DECLARING THE ORIGINAL
 PERMIT WILL BECOME PHASED, A REVISION TO THE ORIGINAL
 PERMIT INDICATING WHAT WORK IS BEING DELETED FROM THEIR
 SCOPE OF WORK.
  
 1B) IF THE PHASE II PERMIT IS SUBMITTED FOR PERMIT
 BEFORE A CERTIFICATE OF OCCUPANCY HAS OCCURRED, THE
 ORIGINAL DESIGN TEAM WILL NEED TO REVIEW THE PHASE II
 DOCUMENTS AND APPLY THEIR SHOP DRAWING STAMP,
 INDICATING REVIEWED. NOTE THE NEW ENERGY CALCULATIONS
 MAY EFFECT THE WHOLE BUILDING ENERGY CALCULATIONS FROM
 THE ORIGINAL DESIGN.
  
 2) IF AT ANY TIME THERE IS A CHANGE IN THE BUILDING
 CONTRACTOR THE SAME WILL OCCUR, WE WILL NEED A LETTER
 FROM THE ORIGINAL BUILDING CONTRACTOR INDICATING THAT
 THE NEW BUILDING CONTRACTOR MAY WORK WITHIN THE
 INTERIOR OF THE BUILDING BEFORE THE CO IS ISSUED.
  
 3) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 11:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-22 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 09:24 Sent To  
Notes
2009-07-05 10:15:19REVIEW FOR ELECTRICAL COMPLETED AND PLANS ROUTED BACK
 TO ENG AS THEY WERE SIGNED OUT.
2009-07-05 10:14:04 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE
 STATED ON PLANS AS THEY ARE RELEVANT FOR THE MINIMUM
 DESIGNS. THERE IS CONFLICTS ON THE COVER SHEET FOR
 EXAMPLE WHICH INDICATES BOTH THE 2002 AND 2005 NEC.
 ALSO INDICATES 2003 NFPA-101
 AFTER DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED
 THE 2005 NEC.
 AFTER DECEMBER 31ST, 2008 THE STATE OF FLORIDA UNDER
 FAC 69A-60.004, AND 69A-3.012 ADOPTED THE 2006 NFPA-101
 THE PLANS INDICATE THE 2004 FLORIDA FIRE PREVENTION
 CODE HOWEVER UNDER THE SAME SECTIONS NOTED ABOVE THE
 EDITION SHOULD READ 2007.
 CURRENT NFPA-1 IS 2006.
  
 2007 FBC W/ 2009 SUPPLEMENTS
 2005 NFPA-70
 2006 NFPA-101
 2007 FLORIDA FIRE PREVENTION CODE
 2006 NFPA-1
  
  
 2) NOTE: THE APPLIED SCOPE OF WORK IS IN DIRECT
 CONFLICT WITH WORK AND AREAS UNDER THE PHASE 1 PROJECT
 WHICH IS UNDER A SEPARATE DESIGN TEAM. ALL PLAN SHALL
 BE *SHOP DRAWING REVIEW STAMPED* BY THE BASE BUILDING
 DESIGNERS OF RECORD. THERE IS WORK SHOWN ON THE BASE
 BUILDING DESIGN TEAMS PLANS WHICH IS ALSO IN THESE SAME
 AREAS.
 UNTIL THE BASE BUILDING AND THOSE AREAS ARE CLOSED FOR
 FINAL SCOPE OF WORK AND CONTAIN A CERTIFICATE OF
 OCCUPANCY THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE
 FOR THE SCOPE OF WORK.
  
 *** DO NOT SUBMIT REVISIONS TO BASE BUILDING UNDER THE
 SUBMITTED PERMITTED FOR NEW SCOPE OF WORK.
  
 THE BASE BUILDING PLANS HAVE NOT BEEN REVISED TO REMOVE
 SCOPE OF WORK FROM THEIR PLANS. MANY OF THESE LOCATIONS
 ARE REQUIRED TO CONTAIN MINIMUM LIFE SAFETY BEFORE C OF
 O CAN BE GRANTED.
  
 ** THERE IS STILL A FEE DUE HOLD ALSO ON BASE BUILDING
 BEFORE C OF O. THE AMOUNT OF $57,200 REMAINS
 OUTSTANDING.
  
  
 3) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR REQUIRED
 CALCULATIONS AND COORDINATION OF ALL DOCUMENTS AND
 REPORTS WITH THE SUBMITTED PLANS. THERE ARE
 INCONSISTENCIES IN THE SUBMITTED PLANS AND
 CALCULATIONS.
  
 A) PLEASE EXPLAIN THE INPUT DATA REPORT WHICH DOES NOT
 COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES
 AS FOR EXAMPLE, THE WAREHOUSE/STORAGE/KENNEL AREAS
 INDICATE FLOORS AS *CARPET AND RUBBER PADDING*. THIS IS
 NOT POSSIBLE.
  
 B) SCOPE OF WORK ACTUAL SQUARE FOOTAGE NEEDS TO
 COORDINATE FROM PLANS TO THE SUBMITTED CALCULATIONS.
  
 C) SEE THE IDR AS THE LIGHTING CONTROLS ARE SHOWN AS
 MANUAL ON/OFF. NOT ALL AREAS ARE MANUAL ON/OFF WHERE
 WORK IS ACTUALLY BEING DONE.
  
 D) SEE THE LPD ON PLANS WHICH IS LESS THAN THAT
 SUBMITTED AND SHOWN ON THE INPUT DATA REPORT AND
 SUMMARY SHEETS OF THE SUBMITTED FLA COM REPORT. PLEASE
 EXPLAIN CONFLICT.
  
 E) PLEASE SEE THE IDR AS *ALL* FIXTURES ARE SHOWN AS
 64WATT FIXTURES, YET THE PLANS CLEARLY INDICATE
 FIXTURES WITH A MUCH GREATER WATTAGE.
 PLEASE SEE 13-415.AB.5.1 AS THE VA RATING SHALL BE
 BASED ON THE INPUT OF THE BALLAST. DO NOT USE THE BULBS
 AS WATTAGE. SOMETIMES THIS CAN HELP ON CALCULATIONS
 DEPENDING ON THE EFFICIENCY RATING OF FIXTURES.
 SOMETIMES THE FIXTURE VA IS HIGHER THAN THE WATTAGE OF
 BULBS.
  
 4) NOTE: PLEASE SEE FBC 11-4.27.4. AREAS IN WHICH MAY
 BE ACCESSIBLE TO ADA SHALL NOT CONTAIN SWITCHING
 DEVICES WHICH DO NOT MEET SECTION GIVEN.
 NOT ALL LOCATIONS WOULD BE CONSIDERED ADA HOWEVER SOME
 ON PLANS ARE.
  
 5) NOTE: PLEASE PROVIDE ACCURATE PANEL SCHEDULES FROM
 BASE BUILDING DESIGN TEAM AND INCORPORATE INTO THE
 SUBMITTED PANEL SCHEDULES. THE RECORD SET OF PLANS WILL
 NEED TO BE ACCURATE FOR SCOPE.
 EXISTING CIRCUITS MAY JUST BE LABELED WITH AN *E* NEXT
 TO EACH ITEM ON THE OUTSIDE OF SCHEDULE.
 408.4.
 ALL LOADS SHALL BE REVISED WITH THE LATEST PLANS OF
 JOBSITE ONCE CO IS ISSUED.
  
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-07-08 Cont ID  
Sent By mgonzale Date 2009-07-08 Time   Rev Time 1.00
Received By mgonzale Date 2009-07-08 Time   Sent To  
Notes
2009-07-08 11:39:48PLAN DOES NOT CONSTITUTE AN ENGINEERING REVIEW FOR THIS
 SUBMITTAL
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-10-07 Cont ID  
Sent By mawillia Date 2009-10-07 Time 13:12 Rev Time 0.00
Received By mawillia Date 2009-10-07 Time 12:56 Sent To  
Notes
2009-10-07 13:12:18*****REVISION #2, DATED 09/28/2009, APPROVED*****
  
 OF THE TEN SUBMITTED PLAN SHEETS, REVISED PLAN SHEETS
 E-101 AND E-102 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-17 Cont ID  
Sent By mcarsill Date 2009-09-17 Time 14:20 Rev Time 0.00
Received By mcarsill Date 2009-09-17 Time 14:18 Sent To  
Notes
2009-09-17 14:19:591. ALL EXIT ACCESS AND EXIT DOORS ARE TO BE PROPERLY
 IDENTIFIED WITH ILLUMINATED EXIT SIGNS.
  
 2. ALL WORK IS SUBJECT TO FIELD INSPECTION AND APPROVA.
  
 3. COORDINATION IS REQUIRED DURING PHASE ONE AND PHASE
 TWO CONSTRUCTION PERIODS.
  
  
 MIKE CARSILLO
 BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-21 Cont ID  
Sent By mcarsill Date 2009-07-21 Time 08:38 Rev Time 0.00
Received By mcarsill Date 2009-07-21 Time 08:22 Sent To  
Notes
2009-07-21 08:38:13GRACE PAVILLION
 3100 NORTH MILITARY TRAIL
 PHASE II, INCLUDING HVAC UNITS, PLUMBING, AND FLAT WORK
  
 1. WRONG CODE REFERENCES NOTED ON PAGE CS-1.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3. ALL REQUIRED FIRE DAMPERS ARE TO BE DROP TESTED
 AFTER INSTALLATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL OR ADDITIONS.
  
 5. PLANS DO NOT ILLUSTRATE ILLUMINATED EXIT SIGNS OR
 PORTABLE FIRE EXTINGUISHER LOCATIONS.
  
 6. TWO HOUR RATED WALLS ARE DISPLAYED BUT COULD NOT
 LOCATE RATED DOOR INFORMATION.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-11-18 Cont ID  
Sent By lmartine Date 2009-11-18 Time 16:59 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 16:59 Sent To  
Notes
2009-11-18 17:03:43GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-20 Cont ID  
Sent By lmartine Date 2009-10-20 Time 15:18 Rev Time 0.00
Received By lmartine Date 2009-10-20 Time 15:18 Sent To  
Notes
2009-10-20 15:20:00GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-01 Cont ID  
Sent By lmartine Date 2009-10-01 Time 15:59 Rev Time 0.00
Received By lmartine Date 2009-10-01 Time 15:59 Sent To  
Notes
2009-10-01 16:16:46C--15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 11:30 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 11:30 Sent To  
Notes
2009-09-01 11:42:48SENT TO C-16.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 14:06 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 11:36 Sent To  
Notes
2009-06-12 11:39:24SENT TO COMMERCIAL C33

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-10-21 Cont ID  
Sent By rregueir Date 2009-10-21 Time 18:51 Rev Time 0.00
Received By rregueir Date 2009-10-21 Time 18:48 Sent To  
Notes
2009-10-21 18:50:59REVISED M-101, M-102 DELTA 4
  
  
 **REVISION REQUIRED**
  
 PAGE M-101: PLAN SHOWS EXHAUST OUTLETS SEPARATED BY
 LESS THAN 10' FROM FRESH AIR INTAKES. REVISE PLANS TO
 SHOW THESE OPENINGS TO BE MINIMUM 10 FEET APART IN
 ACCORDANCE WITH FBC-M 401.4. THIS IS THE SECOND TIME
 THIS CORRECTION HAS BEEN REQUESTED BY PROVISO.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-02 Cont ID  
Sent By rregueir Date 2009-10-02 Time 15:55 Rev Time 0.00
Received By rregueir Date 2009-10-02 Time 15:53 Sent To  
Notes
2009-10-02 15:55:46**PROVISO**
 REVISED M-101 AND M-102, DELTA 2
  
 EXHAUST AND INTAKE LOUVERS SHALL BE MINIMUM 10' APART
 PER FBC-M 401.5. PLAN SHOWS A MEASUREMENT OF 10'
 CENTER-TO-CENTER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-17 Cont ID  
Sent By rregueir Date 2009-07-17 Time 09:05 Rev Time 0.00
Received By rregueir Date 2009-07-17 Time 09:03 Sent To  
Notes
2009-07-17 09:05:38**PROVISO**
  
 1. REVISE PLANS REMOVING FIRE DAMPERS FROM NON-RATED
 WALLS AS SHOWN ON M101. THERE ARE NO RATED WALL
 ASSEMBLES SHOWN BEING PENETRATED ON THIS PLAN. FBC-M
 607.1.1
  
 2. VERIFY PROPER SERVICE CLEARANCE FOR AHU-2 PER FBC-M
 304.1 AND 306.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 18:30 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 18:30 Sent To  
Notes
2009-10-08 18:31:06REVISION OK -- SHTS P-201 & P-202 REV #1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-08 Cont ID  
Sent By kstevens Date 2009-09-08 Time 15:49 Rev Time 0.00
Received By kstevens Date 2009-09-08 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 13:49 Rev Time 0.00
Received By kstevens Date 2009-07-30 Time 17:05 Sent To  
Notes
2009-08-05 14:04:27DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
  
 1. SEE COMMENTS 1, 1A & 1B BY THE BUILDING PLANS
 REVIEWER AND COMMENT 2 BY THE ELECTRICAL PLANS
 REVIEWER. THESE COMMENTS SHALL BE ADDRESSED PRIOR TO
 PERMIT ISSUANCE.
  
 2. SHT P-102 NOTE STATES IN PART "CONNECT NEW 4"
 SANITARY LINE" BUT SHOWS A 6" SANITARY LINE. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 701.1.
  
 3. SHT P-103 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN WHERE THE FLOOR DRAIN CONNECTS TO THE
 BRANCH LINE WEST OF THE BOUTIQUE. THE FLOOR PLAN SHOWS
 THE FLOOR DRAIN IN THE DOG ADOPTION ROOM CONNECTING
 BETWEEN THE 2ND AND THIRD FLOOR DRAINS TO THE EAST OF
 THE BRANCH LINE, BUT BETWEEN THE 1ST & 2ND FLOOR DRAINS
 ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS
 106.1.1 & 701.1.
  
 4. SHT P-203 A SHUT OFF VALVE IS REQUIRED ON THE WATER
 SUPPLY LINE TO EACH HOSE BIBB. SECTION 606.2(2).
  
 5. SHT P-300 PLUMBING NOTES NUMBER 13. AIR CHAMBERS ARE
 NOT APPROVED. PDI-WH 201. PLEASE DELETE FROM NOTES.
  
 ***NOTE: THE COMMENTS 3 THRU 5 CAN BE PROVISO'D AND
 REVISIONS CAN BE SUBMITTED FOR THESE COMMENTS.***
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-09-23 Cont ID  
Sent By eschneid Date 2009-09-23 Time 18:47 Rev Time 0.50
Received By eschneid Date 2009-09-23 Time 18:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-09-16 Cont ID  
Sent By eschneid Date 2009-09-16 Time 17:24 Rev Time 0.75
Received By eschneid Date 2009-09-16 Time 17:24 Sent To  
Notes
2009-09-16 17:28:43FAILED
  
 1) REPEAT COMMENT: SITE AND LANDSCAPE PLANS SHALL BE
 PROVIDED WITH THIS PERMIT AS THERE IS EXTERIOR WORK
 INVOLVED.
  
 2) PHASE II CIVIL PLANS SHALL BE PROVIDED.
  
 3) AN UPDATED SQUARE FOOT USE BREAKDOWN IS REQUIRED FOR
 THE NEW INTERIOR LAYOUT. THIS USE BREAKDOWN SHALL BE
 USED TO UPDATE THE PARKING TABLES.
  
 4) SHEET CS-1 INCORRECTLY REFERENCES SHEET SP-1 AS
 HAVING THE PARKING BREAKDOWN. THERE IS NO SHEET SP-1
 AND PREVIOUS PARKING BREAKDOWNS ARE INCLUDED AS PART OF
 SHEET A-012.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By eschneid Date 2009-06-19 Time 14:38 Rev Time 1.00
Received By eschneid Date 2009-06-19 Time 14:38 Sent To  
Notes
2009-06-19 15:17:23FAILED
  
 1) A MINOR PLANNED DEVELOPMENT AMENDMENT APPROVAL IS
 REQUIRED FOR THE CHANGES TO THE SITE AND LANDSCAPE
 PLANS. THE FOLLOWING ISSUES HAVE BEEN IDENTIFIED:
  
 A. THE PROPOSED NEW AC UNITS NEED TO BE SCREENED AND
 SHOWN ON ZONING APPROVED PLANS.
  
 B. THE PROPOSED NEW CANOPY(S) NEED TO BE SHOWN ON
 ZONING APPROVED PLANS. NOTE: THERE ARE DISCREPANCIES
 AMONG THE PLANS AS TO THE LOCATION OF THE CANOPY AS
 WELL AS ISSUES WITH THE CANOPY IN RELATION TO CURBING,
 THE LOADING ZONE AND LANDSCAPE.
  
 C. THE PROPOSED NEW INTERIOR LAYOUT NEEDS TO SHOWN ON
 ZONING APPROVED PLANS - THE SQUARE FOOTAGE MIX OF THE
 USES HAS CHANGED FROM THE APPROVED PLANS. THIS
 POTENTIALLY AFFECTS PARKING. THE APPROVED AND PROPOSED
 PLANS HAVE PARKING DISCREPANCIES IN NUMBER
 REQUIRED/PROVIDED.
  
 2) THERE ARE DISCREPANCIES ON THE VARIOUS ARCHITECTURAL
 PLANS SUBMITTED WITH THIS PERMIT.
  
 3) SITE AND LANDSCAPE PLANS SHALL BE PROVIDED WITH THIS
 PERMIT AS THERE IS EXTERIOR WORK INVOLVED.
  
 4) NEW EXTERIOR PLUMING AND ELECTRICAL WORK SHALL NOT
 INTERFERE WITH APPROVED LANDSCAPE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.