Plan Review Details - Permit 09060273
Plan Review Stops For Permit 09060273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-26 Cont ID  
Sent By shill Date 2009-06-26 Time 11:00 Rev Time 0.00
Received By shill Date 2009-06-26 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-12 Cont ID  
Sent By shill Date 2009-06-12 Time 09:58 Rev Time 0.00
Received By shill Date 2009-06-12 Time 09:58 Sent To  
Notes
2009-06-12 10:04:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE DOOR SIZE AND DISTANCE FROM DOOR TO OUTSIDE
 CORNER OF BUILDING ON THE FLOOR PLAN. DESIGN PRESSURES
 CANNOT BE DETERMINED WITHOUT THIS INFORMATION. FBC
 R301, ASCE7-05.
  
 2. PLEASE CLARIFY; APPLICATION STATES THAT THIS IS AN
 IMPACT FRAME WITH IMPACT INSERTS, PRODUCT APPROVAL
 STATES THIS IS NON IMPACT. PLEASE CLARIFY SCOPE OF WORK
 FBC*106, FBC R301.2.1.2. BASED ON HOUSE CONSTRUCTION
 DATE, THIS RESIDENCE SHOULD HAVE EXISTING IMPACT
 PROTECTION. HOWEVER, IF THE CONTRACTOR STATES THAT HE
 IS INSTALLING IMPACT DOORS, IMPACT DOORS ARE TO BE
 INSTALLED. PLEASE EITHER REVISE THE APPLICATION OR
 PROVIDE IMPACT DOOR PRODUCT APPROVALS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-12 Cont ID  
Sent By shill Date 2009-06-12 Time 10:31 Rev Time 0.00
Received By shill Date 2009-06-11 Time 14:19 Sent To  
Notes
2009-06-11 14:19:55TO MISC 1