Plan Review Details - Permit 09060269
Plan Review Stops For Permit 09060269
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-08-13 Cont ID  
Sent By shill Date 2009-08-13 Time 14:52 Rev Time 0.00
Received By shill Date 2009-08-13 Time 14:52 Sent To  
Notes
2009-08-13 14:52:52DOOR REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 22:42 Rev Time 0.00
Received By shill Date 2009-07-22 Time 22:42 Sent To  
Notes
2009-07-22 22:43:48***PROVISO***
  
 SUBMIT A REVISION WHICH INCLUDES DOOR ENGINEERING
 CONTRACTOR DID NOT ADDRESS COMMENT REQUESTING DOOR
 PRODUCT APPROVAL, BUT SUBMITTED A COPY OF THE FBC R
 613.4.3 WHICH STATES THAT A DOOR CAN BE TESTED OR
 DESIGNED ACCORDING TO STANDARD ENGINEERING PRACTICE.
 PROVIDE EITHER A TEST REPORT OR ENGINEERING (DOOR
 DESIGN INCLUDING ALL DETAILS, MATERIALS, ETC.). THE
 PLAN DOES NOT INCLUDE COMPLETE DOOR
 CONSTRUCTION/INSTALLATION INFORMATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-12 Cont ID  
Sent By shill Date 2009-06-12 Time 09:04 Rev Time 0.00
Received By shill Date 2009-06-12 Time 09:04 Sent To Z
Notes
2009-06-12 09:28:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE DOOR, FAC9B72. LOCAL PRODUCT APPROVAL APPLICATION
 IS AVAILABLE ON THE INTERNET AT
 WWW.FLORIDABUILDING.ORG.
  
 2. FBC1507.2.9.3, SEE FIRST OVERHANG OPTION. IT IS NOT
 CLEAR HOW THE DRIP EDGE WILL PROPERLY BE INSTALLED
 USING THIS OPTION. PLEASE PROVIDE A LEGIBLE DETAIL
 SHOWING ALL COMPONENTS.
  
 3. SHEATHING IS REQUIRED TO MEET MINIMUM REQUIREMENTS
 OF FBC R TABLE 803.1.
  
 4. 6D NAILS SPECIFIED ON SHEET 3, DOES NOT MEET MINIMUM
 SHEATHING REQUIREMENTS, FBC R803.2.3.1.
  
 5. THE ENGINEER'S SEAL REQUIRES A DATE,
 FAC61G15-23.002.
  
 6. CERTIFICATE OF AUTHORIZAITON REQUIRED TO PRACTICE
 ENGINEERING THROUGH A COMPANY, FS471. TRUSS ENGINEERING
 INCLUDES "RICHARD WEINGARDT CONSULTANTS."
  
 7. ALL INFORMATION REQUIRED BY FAC61G15-23.002 ON EACH
 SHEET (TRUSS ENGINEERING).
  
 8. TRUSS ENGINEERING DESIGN SPECIFIES IBC, PLEASE
 REVISE TO GOVERNING CODE.
  
 9. ROOF PERMIT REQUIRED.
  
 10. PLEASE INCLUDE DISTANCE FROM EXISTING HOUSE TO
 PROPOSED NEW STRUCTURE, FBC R302.1.
  
 11. IT IS NOT CLEAR HOW THE DOOR WILL COMPLY WITH FBC
 R311.4.4. IS THIS DOOR OPERABLE FROM THE INSIDE?
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-13 Cont ID  
Sent By jgomez Date 2009-08-13 Time 12:14 Rev Time 0.00
Received By jgomez Date 2009-08-13 Time 12:14 Sent To  
Notes
2009-08-13 12:15:10SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 15:37 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 15:36 Sent To  
Notes
2009-07-22 15:37:22GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-19 Cont ID  
Sent By mcruz Date 2009-06-19 Time 11:43 Rev Time 0.00
Received By mcruz Date 2009-06-11 Time 14:21 Sent To  
Notes
2009-06-11 14:21:13TO MISC 2

Review Stop Z ZONING
Rev No 1 Status P Date 2009-06-19 Cont ID  
Sent By mcruz Date 2009-06-19 Time 11:42 Rev Time 0.00
Received By mcruz Date 2009-06-19 Time 11:41 Sent To  
Notes
***NONE***