Plan Review Details - Permit 09060229
Plan Review Stops For Permit 09060229
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-02 Cont ID  
Sent By jgomez Date 2009-07-02 Time 11:54 Rev Time 0.00
Received By jgomez Date 2009-07-02 Time 11:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-15 Cont ID  
Sent By jgomez Date 2009-06-15 Time 10:28 Rev Time 0.00
Received By jgomez Date 2009-06-15 Time 10:27 Sent To PC
Notes
2009-06-15 10:28:22RESIDENTIAL (R2) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON SHEET 14 OF NOA
 07-1018.10 SUBMITTED.
 ***NOTE: ACCORDING TO 2009 REVISIONS TO FBC 2007 THIS
 BUILDING IS LOCATED ON EXPOSURE "C". DESIGN
 PROFESSIONAL TO HAVE THIS EXPOSURE IN CONSIDERATION
 WHEN DOING THE RAS 117 CALCULATIONS.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES. NOA SUBMITTED SHOWS TWO DIFFERENT
 ASSEMBLIES. ONE ON PAGE 7 AND ONE ON PAGE 9. SELECT
 ONLY ONE ASSEMBLY AND PROVIDE RESPECTIVE RAS 117
 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-15 Cont ID  
Sent By jgomez Date 2009-06-15 Time 10:28 Rev Time 0.00
Received By jgomez Date 2009-06-15 Time 10:28 Sent To  
Notes
***NONE***