Plan Review Details - Permit 09060210
Plan Review Stops For Permit 09060210
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-26 Cont ID  
Sent By jwitmer Date 2009-08-26 Time 14:48 Rev Time 0.55
Received By jwitmer Date 2009-08-26 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-14 Cont ID  
Sent By jwitmer Date 2009-07-14 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2009-07-14 Time 15:38 Sent To  
Notes
2009-07-14 16:03:52BUILDING PLAN REVIEW
 PERMIT:09060210
 ADD: 421 24TH ST
 CONT: ALONSO & ASSOCIATES
 TEL: (561)
 253-5350
 2007 BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET A-1 INDICATES A 2'-6" DOOR LEADING INTO A
 OFFICE PLEASE REVIEW SECTION FBC 1008.1.1 SIZE OF DOOR
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES .
  
 3) PRODUCT APPROVALS MISSING PREMANUFACTURED A/C STAND,
 PLEASE SEE RULE 9B-72. WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-09 Cont ID  
Sent By dpalmer Date 2009-09-09 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2009-09-09 Time 17:03 Sent To PC
Notes
2009-09-09 17:03:43** PROVISO **
  
 ** ALL OF THE FOLLOWING COMMENTS NEED TO BE ADDRESSED
 BEFORE ANY ROUGH ELECTRICAL INSPECTIONS. A MEETING WAS
 HELD WITH CONTRACTOR/OWNER TO GO OVER ALL NOTES. MR.
 ALONSO IS AWARE OF HOLD WHICH WILL BE PLACED ON
 INSPECTIONS.
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH THE * MINIMUM* FOR THE
 FBC 13-415.AB.5. A NEW FORM B WAS SUBMITTED HOWEVER
 WHEN USING A FORM B FOR MINIMUM PRESCRIPTIVE YOU WOULD
 USE ONE FOR EACH *SPACE TYPE*. NOT ONE FORM WHEN YOU
 HAVE MULTIPLE SPACES PER TABLE 13-415.B.1. AT THE
 REQUEST OF CONTRACTOR, FORM B WAS REMOVED FROM PLANS.
 PRESCRIPTIVE TO BE SUBMITTED FOR INTERIOR LIGHTING.
  
 SEE 13-415.AB.2.2 FOR EXTERIOR, NOTHING SHOWN. BASE DON
 THE PLANS SUBMITTED THE FIXTURES SHOWN WILL NOT EXCEED
 ALLOWANCES HOWEVER PLANS ( SIGN CIRCUIT IS NOT
 INCLUDED, EXEMPT).
 THE SPACE TYPE AS LISTED ON THE FORM B SUBMITTED STATES
 * FLUORESCENT*. HOW CAN THE SPACE TYPE BE FLUORESCENT?
 THIS WOULD BE LISTED UNDER FIXTURE TYPE FOR EACH SPACE.
 PART OF THE LIGHTING SPACE BY SPACE IS BEING SHOWN ON
 PLANS HOWEVER DUE TO THE INCONSISTENCIES ON THE FIXTURE
 LEGEND. CODE COMPLIANCE IS NOT SHOWN. IN FACT BASED ON
 SOME OF THE FIXTURE INFORMATION THE MAXIMUM LIGHTING
 ALLOWANCE LEVELS ARE EXCEEDED.
 SOME EXAMPLES WILL BE GIVEN.
  
 FOR EXAMPLE: FIXTURE TYPE *A* IS SHOWN AS 3-32W WITH AN
 OVER ALL AT 107WATTS DUE TO THE BALLAST POWER FACTOR.
 HOWEVER PLEASE SEE *LAMP TYPE LISTING ON THE FIXTURE
 TABLE. THIS CLEARLY STATES THERE WILL BE (4)-F32 W
 BULBS. PER CONTRACTOR THE FIXTURE WHICH IS GOING TO BE
 USED WILL NOT CONTAIN (4) F32.
  
 FOR EXAMPLE: THE SAME IS NOTED FOR FIXTURE B AS NOTED
 FOR FIXTURE *A*. THE LAMP LEGEND INDICATES (4) F32W
 BULBS. PER CONTRACTOR THE FIXTURE WHICH IS GOING TO BE
 USED WILL NOT CONTAIN (4) F32.
  
 FOR EXAMPLE: PLEASE SEE FIXTURE TYPE *D* WHICH STATES
 IT IS AN INCANDESCENT FIXTURE YET ALSO STATES IT IS A
 RECESSED FLUORESCENT DOWN LIGHT.
  
 THE COMMENT REMAINS TO CALL IF THERE ARE QUESTIONS.
  
  
 2) NOTE: PLEASE SEE COMMENT FROM PREVIOUS REVIEW WHICH
 REQUIRED LIGHTING CONTROLS IN SPECIFIC ROOMS STATED IN
 13-415.AB.1.2 TO MEET THE FBC. AUTOMATED LIGHTING
 CONTROLS WERE ADDED TO ALL OTHER ROOMS EXCEPT THE TWO
 ROOMS AS NOTED IN THE PREVIOUS REVIEW. THE ONLY TWO
 ROOMS IN THIS BUILDING WHICH IS LESS THAN 5K SQ FT THAT
 REQUIRES AUTOMATED LIGHTING CONTROLS IS THE
 KITCHEN/BREAK ROOM AND THE CONFERENCE ROOM.
 THIS WAS GONE OVER WITH CONTRACTOR. PLANS WILL BE
 REVISED.
  
 ** AS A SIDE NOTE: EVEN THOUGH AUTOMATED LIGHTING
 CONTROLS ARE NOT REQUIRED IN THE OTHER ROOMS, THEY MAY
 CERTAINLY BE INSTALLED AS SHOWN ON PLANS.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 EXTERIOR LIGHTING CONTROLS. IT WAS NOTED THAT THERE
 WERE EXTERIOR LIGHTS ON SINGLE POLE SWITCHES WHICH WAS
 NOT PERMITTED AS SHOWN. THE PLANS NOW HAVE A NOTE WHICH
 STATES ALL EXTERIOR LIGHTS TO BE ON A TIME CLOCK.
 HOWEVER THE SINGLE POLE SWITCH IS ALSO STILL SHOWN??
 PLEASE KNOW THAT A STANDARD TIME CLOCK DOES NOT MEET
 ONE OF THE TWO ACCEPTABLE METHODS PER 13-415.AB.1.4. IF
 THIS IS GOING TO BE A TIME CLOCK THEN IT MUST BE
 *ASTRONOMICAL TYPE* WITH A MINIMUM OF 10HRS BATTERY
 BACK UP FOR PROGRAMMING.
 ** THIS WAS GONE OVER WITH CONTRACTOR.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO WATER
 HEATER LOADS ON STORAGE TYPE OF WATER HEATERS WHICH ARE
 REQUIRED TO BE SHOWN AND FIGURED AT 125%. SEE 422.13.
 THIS TYPE OF LOAD UNDER THE CHANGE IN THE 2005 NEC IS
 NOW CONSIDERED A CONTINUOUS LOAD. ALL CONTINUOUS LOADS
 ARE REQUIRED TO BE SHOWN AT 125%.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE 2005 NEC HANDBOOK. *** IF THERE ARE QUESTIONS,
 PLEASE CALL.
 ** PLEASE SEE LAST SENTENCE IN NOTES**
  
 **THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.**
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 MINIMUM LOAD CALCULATIONS REQUIRED TO BE SHOWN FOR A
 COMMERCIAL.
 THE PREVIOUS CALCULATIONS THAT WERE SUBMITTED WERE
 BASED ON RESIDENTIAL USE. THE CALCULATIONS SUBMITTED DO
 NOT MEET NEC. SEE
 220.12,220.14,220.42,220.44,220.56,220.60, 215.3 AND
 230.42. THERE ARE OTHER SECTIONS IN 220.
  
 FOR EXAMPLE:
 THE NEW CALCULATIONS INDICATE RECEPTACLES AT A TOTAL OF
 (4) AND A TOTAL OF 7500VA. THERE ARE MORE THAN 4
 RECEPTACLES.
  
 FOR EXAMPLE; THE TOTAL LIGHTING LOAD IS SHOWN AT
 1014VA. HOW IS THIS POSSIBLE WHEN THE LIGHTING LOAD
 SHOWN FOR THE INTERIOR LIGHTING ALONE ON SPACE BY SPACE
 IS 1917VA. ( WHICH MAY OR MAY NOT BE ACCURATE BASED ON
 FIXTURE LEGEND).
  
 ** PLEASE SEE NOTE ABOVE WITH RESPECT TO LOAD
 CALCULATIONS. WHEN KNOWN LIGHTING LOAD EXCEED THE NEC
 MINIMUM WATTS PER SQUARE FOOT, THEN THE HIGHER MUST BE
 USED.
 ** SEE NOTES ABOVE WITH RESPECT TO WATER HEATER LOAD.
  
 6) NOTE: NEW COMMENT: THE FRONT LOCATION STATES THE *
 EXIT SIGN TO BE ON TIME CLOCK*. THIS WAS GONE OVER WITH
 CONTRACTOR. THIS IS A MISPRINT AND WILL BE CORRECTED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-09-09 Cont ID  
Sent By dpalmer Date 2009-09-09 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2009-09-09 Time 11:02 Sent To PC
Notes
2009-09-09 11:03:04 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SEVERAL COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH THE * MINIMUM* FOR THE
 FBC 13-415.AB.5. A NEW FORM B WAS SUBMITTED HOWEVER
 WHEN USING A FORM B FOR MINIMUM PRESCRIPTIVE YOU WOULD
 USE ONE FOR EACH *SPACE TYPE*. NOT ONE FORM WHEN YOU
 HAVE MULTIPLE SPACES PER TABLE 13-415.B.1.
 SEE 13-415.AB.2.2 FOR EXTERIOR, NOTHING SHOWN. ( SIGN
 CIRCUIT IS NOT INCLUDED, EXEMPT).
 THE SPACE TYPE AS LISTED ON THE FORM B SUBMITTED STATES
 * FLUORESCENT*. HOW CAN THE SPACE TYPE BE FLUORESCENT?
 THIS WOULD BE LISTED UNDER FIXTURE TYPE FOR EACH SPACE.
 PART OF THE LIGHTING SPACE BY SPACE IS BEING SHOWN ON
 PLANS HOWEVER DUE TO THE INCONSISTENCIES ON THE FIXTURE
 LEGEND. CODE COMPLIANCE IS NOT SHOWN. IN FACT BASED ON
 SOME OF THE FIXTURE INFORMATION THE MAXIMUM LIGHTING
 ALLOWANCE LEVELS ARE EXCEEDED.
 SOME EXAMPLES WILL BE GIVEN.
  
 FOR EXAMPLE: FIXTURE TYPE *A* IS SHOWN AS 3-32W WITH AN
 OVER ALL AT 107WATTS DUE TO THE BALLAST POWER FACTOR.
 HOWEVER PLEASE SEE *LAMP TYPE LISTING ON THE FIXTURE
 TABLE. THIS CLEARLY STATES THERE WILL BE (4)-F32 W
 BULBS.
  
 FOR EXAMPLE: THE SAME IS NOTED FOR FIXTURE B AS NOTED
 FOR FIXTURE *A*. THE LAMP LEGEND INDICATES (4) F32W
 BULBS.
  
 FOR EXAMPLE: PLEASE SEE FIXTURE TYPE *D* WHICH STATES
 IT IS AN INCANDESCENT FIXTURE YET ALSO STATES IT IS A
 RECESSED FLUORESCENT DOWN LIGHT.
  
 ** ON THE PREVIOUS REVIEW ON THIS NOTE THIS REVIEWER
 STATED TO CALL TO GO OVER THIS COMMENT IF THERE WERE
 ANY QUESTIONS. TO DATE THIS DID NOT OCCUR. THE COMMENT
 REMAINS TO CALL IF THERE ARE QUESTIONS.
  
  
 2) NOTE: PLEASE SEE COMMENT #1 ABOVE. THERE ARE TWO
 COPIES OF *FORM B* SUBMITTED. BOTH ARE SIGNED AND DATED
 BY THE ARCHITECT WITH APPROPRIATE LICENSE NUMBER
 HOWEVER THERE IS NO RAISED SEAL. FS 481.221
 ** THIS IS BEING NOTED IN CASE DESIGNER DOES SUBMIT NEW
 FORM B FOR LIGHTING COMPLIANCE FOR EACH SPACE TYPE.
 AS STATED, CALL TO GO OVER HOW COMPLIANCE CAN BE SHOWN
 FOR PRESCRIPTIVE WITHOUT HAVING TO FILL OUT A FORM FOR
 EACH SPACE.
  
 3) NOTE: PLEASE SEE COMMENT FROM PREVIOUS REVIEW WHICH
 REQUIRED LIGHTING CONTROLS IN SPECIFIC ROOMS STATED IN
 13-415.AB.1.2 TO MEET THE FBC. AUTOMATED LIGHTING
 CONTROLS WERE ADDED TO ALL OTHER ROOMS EXCEPT THE TWO
 ROOMS AS NOTED IN THE PREVIOUS REVIEW. THE ONLY TWO
 ROOMS IN THIS BUILDING WHICH IS LESS THAN 5K SQ FT THAT
 REQUIRES AUTOMATED LIGHTING CONTROLS IS THE
 KITCHEN/BREAK ROOM AND THE CONFERENCE ROOM.
  
 ** AS A SIDE NOTE: EVEN THOUGH AUTOMATED LIGHTING
 CONTROLS ARE NOT REQUIRED IN THE OTHER ROOMS, THEY MAY
 CERTAINLY BE INSTALLED AS SHOWN ON PLANS.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 EXTERIOR LIGHTING CONTROLS. IT WAS NOTED THAT THERE
 WERE EXTERIOR LIGHTS ON SINGLE POLE SWITCHES WHICH WAS
 NOT PERMITTED AS SHOWN. THE PLANS NOW HAVE A NOTE WHICH
 STATES ALL EXTERIOR LIGHTS TO BE ON A TIME CLOCK.
 HOWEVER THE SINGLE POLE SWITCH IS ALSO STILL SHOWN??
 PLEASE KNOW THAT A STANDARD TIME CLOCK DOES NOT MEET
 ONE OF THE TWO ACCEPTABLE METHODS PER 13-415.AB.1.4. IF
 THIS IS GOING TO BE A TIME CLOCK THEN IT MUST BE
 *ASTRONOMICAL TYPE* WITH A MINIMUM OF 10HRS BATTERY
 BACK UP FOR PROGRAMMING.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO WATER
 HEATER LOADS ON STORAGE TYPE OF WATER HEATERS WHICH ARE
 REQUIRED TO BE SHOWN AND FIGURED AT 125%. SEE 422.13.
 THIS TYPE OF LOAD UNDER THE CHANGE IN THE 2005 NEC IS
 NOW CONSIDERED A CONTINUOUS LOAD. ALL CONTINUOUS LOADS
 ARE REQUIRED TO BE SHOWN AT 125%.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE 2005 NEC HANDBOOK. *** IF THERE ARE QUESTIONS,
 PLEASE CALL.
 ** PLEASE SEE LAST SENTENCE IN NOTES**
  
 **THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.**
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 MINIMUM LOAD CALCULATIONS REQUIRED TO BE SHOWN FOR A
 COMMERCIAL.
 THE PREVIOUS CALCULATIONS THAT WERE SUBMITTED WERE
 BASED ON RESIDENTIAL USE. THE CALCULATIONS SUBMITTED DO
 NOT MEET NEC. SEE
 220.12,220.14,220.42,220.44,220.56,220.60, 215.3 AND
 230.42. THERE ARE OTHER SECTIONS IN 220.
  
 FOR EXAMPLE:
 THE NEW CALCULATIONS INDICATE RECEPTACLES AT A TOTAL OF
 (4) AND A TOTAL OF 7500VA. THERE ARE MORE THAN 4
 RECEPTACLES.
  
 FOR EXAMPLE; THE TOTAL LIGHTING LOAD IS SHOWN AT
 1014VA. HOW IS THIS POSSIBLE WHEN THE LIGHTING LOAD
 SHOWN FOR THE INTERIOR LIGHTING ALONE ON SPACE BY SPACE
 IS 1917VA. ( WHICH MAY OR MAY NOT BE ACCURATE BASED ON
 FIXTURE LEGEND).
  
 ** PLEASE SEE NOTE ABOVE WITH RESPECT TO LOAD
 CALCULATIONS. WHEN KNOWN LIGHTING LOAD EXCEED THE NEC
 MINIMUM WATTS PER SQUARE FOOT, THEN THE HIGHER MUST BE
 USED.
 ** SEE NOTES ABOVE WITH RESPECT TO WATER HEATER LOAD.
  
 7) NOTE: NEW COMMENT: THE FRONT LOCATION STATES THE *
 EXIT SIGN TO BE ON TIME CLOCK*. PLEASE SEE NFPA-70
 700.12F AND NFPA-101 7.8,7.9, THE EXIT SIGN MAY NOT BE
 ON A TIME CLOCK.
 ** THIS MAY BE SOME SORT OF MISPRINT???
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 08:36 Sent To  
Notes
2009-07-04 08:36:45 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012 AS THE
 APPLICABLE NFPA-101 IS THE 2006. PLANS SHOW 2003.
  
 2) NOTE: THE SUBMITTED FORM FOR ENERGY CODE COMPLIANCE
 IS FROM THE 2004 FBC. PLEASE KNOW THAT UNDER THE 2007
 FBC WITH 2009 REVISIONS THERE IS NO LONGER A METHOD
 *C*. ALL PERMIT APPLICATIONS AFTER MARCH 1ST, 2009 NEED
 TO BE UNDER THE REVISED FBC CHAPTER 13.
 PLEASE SEE 13-415.AB.5 FOR LIGHTING PERFORMANCE
 CALCULATIONS AND LEVELS PERMITTED.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
 PLEASE KEEP IN MIND A FIXTURE LEGEND WITH SPECIFIC
 FIXTURES IS NEEDED TO VERIFY MINIMUM CODE COMPLIANCE.
  
 3) NOTE: PLEASE SEE 13-415.AB.1.2 FOR ROOMS WHICH ARE
 REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS WHETHER
 OR NOT THEY ARE IN A BUILDING GREATER THAN 5K SQ FT. T
 THIS WOULD BE THE KITCHEN/BREAK ROOM, CONFERENCE ROOM.
  
 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER
 HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%.
  
 5) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT.
 THIS DOES NOT REQUIRE A SIGN TO BE INSTALLED ONLY
 PROVISIONS FOR CIRCUIT AT FRONT DOOR AREA LOCATION.
 ( VA TO BE FIGURED IS 1200VA)
  
 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS IS BASED
 ON A RESIDENTIAL HOUSE. PLEASE SEE NEC
 220.12,220.14,220.42,220.44, 220.43,220.56,220.60, ETC
 AND 215.3, 230.42 FOR ALL OTHER CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125%.
  
 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EXIT AND
 EMERGENCY LIGHTS. NO CIRCUITING SHOWN, MUST BE TO LOCAL
 LIGHTING BRANCH CIRCUIT.
  
 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING
 CONTROLS. MAY NOT BE ONLY A SINGLE POLE SWITCH.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-27 Cont ID  
Sent By mawillia Date 2009-08-27 Time 14:47 Rev Time 0.00
Received By mawillia Date 2009-08-27 Time 14:29 Sent To  
Notes
2009-08-27 14:47:51*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A-1 AND A-2 WERE STAMPED,
 INITIALED, AND DATED;
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 10:28 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 09:44 Sent To  
Notes
2009-06-29 10:06:04*****DENIED*****
  
  
 1. EFFECTIVE 12/31/08, THE 2006 EDITION OF NFPA 101,
 LIFE SAFETY CODE, SHALL BE REFERENCED. ON SHEET A-1,
 GENERAL NOTE #1, UPDATE TO CURRENT NFPA 101 EDITION.
  
 2. THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED SHEET. THE CORRECT ZIP CODE FOR
 THIS PROJECT SITE IS 33407, NOT 33405 AS LISTED.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 4. INDICATE THE OCCUPANCY CLASSIFICATION AND OCCUPANT
 LOAD FOR THIS PROJECT SITE.
  
 5. INDICATE IF THE BUILDING IS EQUIPPED WITH FIRE
 SPRINKLER AND/OR FIRE ALARM SYSTEMS.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINUISHER(S) WHICH SATIFIES THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2010-01-13 Time 11:35 Sent To  
Notes
2010-01-13 11:37:40ENERGY CALCS FOR RESTAMP ROUTED TO J. WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-26 Cont ID  
Sent By lmartine Date 2009-08-26 Time 09:32 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 09:32 Sent To  
Notes
2009-08-26 09:33:19B-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-14 Cont ID  
Sent By jwitmer Date 2009-07-14 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2009-06-11 Time 13:02 Sent To  
Notes
2009-06-11 13:04:23TO B-22

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-03 Cont ID  
Sent By rregueir Date 2009-09-03 Time 10:57 Rev Time 0.00
Received By rregueir Date 2009-09-03 Time 10:13 Sent To  
Notes
2009-09-03 10:57:14**PROVISO**
 OUTSIDE AIR CALCULATIONS SHOW VENTILATION RATE IN
 EXCESS OF THAT REQUIRED BY FBC-M TABLE 403.3. REVISE
 CALCULATIONS TO SHOW A VENTILATION RATE BASED ON THE
 OCCUPANT LOADS SHOWN ON TABLE 403.3. IF VENTILATION
 RATE EXCEEDS 300 CFM, A MOTORIZED DAMPER IS REQUIRED ON
 THE OUTSIDE AIR INTAKE IN ACCORDANCE WITH FBC-B
 13-409.AB.3.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 15:01 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 14:31 Sent To  
Notes
2009-07-13 14:59:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THERE DO NOT APPEAR TO BE ANY PROVISIONS FOR
 VENTILATION ON PLANS. THE MINIMUM VENTILATION RATE OF
 OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE WITH
 FBC-M SECTION 403.3. PROVIDE VENTILATION CALCULATIONS
 TO DETERMINE THE REQUIRED RATE OF VENTILATION FOR EACH
 SPACE IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEQANS
 AND LOCATION OF VENTILATION AIR INTAKE IN ACCORDANCE
 WITH FBC-M 401.4.
  
 2. PAGE A2 SHOWS AN EXHAUST FAN ON THE PLANS BUT NO
 INFORMATION IS PROVIDED REGARDING THE FAN. PROVIDE FAN
 DATA SHOWING THE EXHAUST RATE IN ACCORDANCE WITH FBC-M
 TABLE 403.3. ALSO, SHOW THE MEANS AND LOCATION OF
 EXHAUST DUCT DISSCHHARGE IINCORDANCE WITH FBC-M 401.4
 AND FBC-M 501.2.
  
 3. A RETURN AIR TRANSFER DUCT IS SHOWN FOR THE
 CONFERENCE ROOM. THE TRANSFER DUCT IS NOT SIZED IN
 ACCORDANCE WITH THE EXCEPTIONS UNDER FBC-M 601.4. SIZE
 THIS RETURN TRANSFER DUCT IN ACCORDANCE WITH THE
 EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT TIME OF
 FINAL INSPECTION TO DETERMINE THE ACTUAL PRESSURE
 DIFFERENTIAL ACROSS THE CLOSED DOOR.
  
 4. EQUIPMENT SCHEDULE CALLS FOR AHU TO PROVED 2000 CFM
 OF SUPPLY WHILE FLOOR PLAN ONLY CALLS FOR 1540 CFM.
 WHICH IS CORRECT? PLEASE COORDINATE FLOOR PLAN AND
 EQUIPMENT SCHEDULE ENSURING EQUIPMENT IS PROPERLY SIZED
 FOR THE COOLING LOADS IN ACCORDANCE WITH FBC-M 312.1.
 NOTE: THE MODEL NUMBERS LISTED ON THE SCHEDULE INDICATE
 A 4 TON SYSTEM. IF A 5 TON SYSTEM IS INSTALLED, PROVIDE
 DUCT SMOKE DETECTOR ON SUPPLY SIDE IN ACCORDANCE WITH
 FBC-M 606.2.1.
  
 5. CONDENSING UNIT STAND INFORMATION ON PLANS IS
 OUT-DATED AND PARTIALLY ILLEGIBLE. PLEASE SUBMIT AN
 ACTUAL CURRENT PRODUCT APPROVAL OR THE PROPOSED STAND,
 APPROVED IN WRITING BY THE DESIGNER OF RECORD IN
 ACCORDANCE WITH FBC-B 106.3.3.
  
 6. ENERGY CODE COMPLIANCE FORM SUBMITTED IS OUT OF
 DATE. THE CORRECT FORM IS 400B-08 AS OF MARCH 1, 2009.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-26 Cont ID  
Sent By kstevens Date 2009-08-26 Time 13:01 Rev Time 0.00
Received By kstevens Date 2009-08-26 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 13:43 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 16:54 Sent To  
Notes
2009-07-01 14:04:54DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
 1. SHT A-2 SANITARY RISER DIAGRAM. THE SINK SHALL NOT
 DISCHARGE INTO THE HORIZONTAL WET VENT OF THE TOILET
 ROOM FIXTURES. SECTION 909.1.
  
 2. SHT A-2 WATER RISER DIAGRAM. AIR CHAMBERS ARE NOT
 APPROVED. PDI-2H 201. PLEASE DELETE FROM RISER DIAGRAM.
 IF WATER HAMMER ARRESTORS ARE INSTALLED, (SECTION
 604.9), THEN THEY SHALL BE INSTALLED NEAR THE FIXTURES,
 IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
  
 3. THE WATER HEATER SHALL BE PROVIDED WITH THERMAL
 EXPANSION CONTROL. SECTION 607.13.2. PLEASE INDICATE
 METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-02 Cont ID  
Sent By eschneid Date 2009-09-02 Time 10:36 Rev Time 0.50
Received By eschneid Date 2009-09-02 Time 10:36 Sent To  
Notes
2009-09-02 10:41:24PASSED W/PROVISOS PER ANGELLA VANN
  
 1) THE NEW ACCU ON THE ROOF SHALL BE SCREENED AS SHOWN
 IN THE PHOTO RENDERINGS ATTACHED TO THE PLANS. FAILURE
 TO DO SO WILL REQUIRE ADDITIONAL SCREENING OR THE
 RELOCATION OF THE ACCU.
  
 2) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE PROPERTY, THE GLAZING REQUIREMENTS OF THE NMUD
 REGULATIONS SHALL BE AMENDED (INITIATED BY THE CRA OR
 THE APPLICANT) OR GLAZING SHALL BE INSTALLED ON THE
 FRONT OF THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-25 Cont ID  
Sent By eschneid Date 2009-06-25 Time 10:38 Rev Time 1.00
Received By eschneid Date 2009-06-25 Time 10:38 Sent To  
Notes
2009-06-25 14:18:04FAILED
  
 1) SECTION 94-213(D)(5)C OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRES THAT RENOVATIONS TO
 EXISTING BUILDINGS THAT HAVE CLEAR GLAZED AREAS LESS
 THAN 50 PERCENT OF ITS FACADE, BETWEEN TWO AND EIGHT
 FEET FROM THE GROUND, MUST PROVIDE AT LEAST 50 PERCENT
 CLEAR GLAZED OF ITS FACADE, BETWEEN TWO AND EIGHT FEET
 FROM THE GROUND. PLEASE PROVIDE AN ELEVATION OF THE
 FRONT FACADE THAT SHOWS COMPLIANCE WITH THE MINIMUM
 GLAZING REQUIREMENT. PLEASE NOTE THAT THE PRIOR
 VARIANCE ALLOWING 49 PERCENT GLAZING (149 SQ. FT.)
 EXPIRED ON MAY 1, 2009.
  
 2) SECTION 94-213(G)(1) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRES THAT OFF-STREET
 PARKING LOTS CONFORM TO THE CITY'S LANDSCAPE CODE.
 PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 THE CODE FOR THE PARKING LOT BEHIND THE BUILDING.
  
 3) SECTION 94-213(A)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRES THAT STORIES AT THE
 SIDEWALK LEVEL SHALL BE NO LESS THAN 12 FEET IN HEIGHT
 FROM FINISHED FLOOR TO FINISHED CEILING. IF THE
 EXISTING FLOOR TO CEILING HEIGHT IS CURRENTLY LESS THAN
 12 FEET, THEN IT MAY NOT BE REDUCED BELOW THE EXISTING
 HEIGHT. PLEASE PROVIDE PRE- AND POST- FLOOR TO CEILING
 HEIGHT MEASUREMENTS. THE PLANS SHOW THAT A NEW SLAB IS
 BEING POURED ON TOP OF THE EXISTING FLOOR AND THAT
 THERE IS WORK BEING DONE TO THE CEILING.
  
 4) SECTION 94-213(D)(15) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRES THAT MECHANICAL
 EQUIPMENT SHALL BE SCREENED FROM VIEW BY LANDSCAPING OR
 BUILT ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE
 BUILDING ARCHITECTURE. THE PLANS SHOW SPECIFICATIONS
 FOR AN ACCU STAND AND A LABEL FOR A 5 TON ACCU ON THE
 ROOF. PLEASE PROVIDE DETAILS OF THE FULL HEIGHT OF THE
 ACCU, INCLUDING STAND, AND HOW THIS WILL BE SCREENED
 FROM VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.