Plan Review Details - Permit 09060175
Plan Review Stops For Permit 09060175
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-29 Cont ID  
Sent By jwitmer Date 2010-03-29 Time 14:21 Rev Time 0.50
Received By jwitmer Date 2010-03-29 Time 14:21 Sent To  
Notes
2010-03-29 14:22:25GC-501
 GC-502
 GC-503

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-07 Cont ID  
Sent By jwitmer Date 2009-08-07 Time 11:36 Rev Time 0.50
Received By jwitmer Date 2009-08-07 Time 11:06 Sent To  
Notes
2009-08-07 11:33:07BUILDING PLAN REVIEW
 PERMIT: 09060175
 ADD: 1302 PARKER AVE
 CONT: PLAN REVIEW/ TBA
 TEL: (561)706-0429 / ALBERT MARINCLLO
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 07/2009
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) PLANS ARE CURRENTLY IN AS A PLAN REVIEW, BUT WHEN
 THEY ARE SUBMITTED FOR PERMIT, THEY WILL NEED TO BE
 SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) COMPLIED.
  
 4) 2ND REQUEST, SHEET GC-503 GENERAL NOTE# 2 INDICATES
 A SOILS REPORT BY DUNKLEBURGER ENGINEERING AND TESTING
 WAS COMPLETED JULY 16, 2008, PLEASE SUPPLY (2) RAISED
 SEAL ORIGINALS.
  
 5) 2ND REQUEST, THERE ARE STRUCTURES FOUND ON THIS
 SHEET STRUCTUREE WITH WEIR AS WELL AS HANDRAILS,
 ALTHOUGH THE WEIR WILBE LOW GRADE THE HANDRAIL WILL BE
 ABOVE GRADE AND SUBJECT TO WIND. SHEET GC-502 DOES NOT
 INDICATE WIND DESIGN CRITERIA:1603.1.4 WIND DESIGN
 DATA. SHEET E-501 ALSO HAS LIGHT POLES THAT WILL NEED
 TO HAVE WHAT WIND DESIGN CRITERIA WOULD HAVE BEEN USED
 IN CALCULATING IF THEY WILL WITHSTAND 140 MPH WIND, IF
 DERATING FACTORS WERE USED.
  
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 08:02 Rev Time 0.55
Received By jwitmer Date 2009-07-08 Time 07:51 Sent To  
Notes
2009-07-08 08:13:16BUILDING PLAN REVIEW
 PERMIT: 09060175
 ADD: 1302 PARKER AVE
 CONT: PLAN REVIEW/ TBA
 TEL: (561)706-0429 / ALBERT MARINCLLO
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) PLANS ARE CURRENTLY IN AS A PLAN REVIEW, BUT WHEN
 THEY ARE SUBMITTED FOR PERMIT, THEY WILL NEED TO BE
 SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) OEST IS MISSING THEIR CERTIFICATE OF AUTHORIZATION
 IN THE TITLEBLOCK.
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 4) SHEET GC-003 GENERAL NOTE# 2 INDICATES A SOILS
 REPORT BY DUNKLEBURGER ENGINEERING AND TESTING WAS
 COMPLETED JULY 16, 2008, PLEASE SUPPLY (2) RAISED SEAL
 ORIGINALS.
  
 5) SHEET GC-002 DOES NOT INDICATE WIND DESIGN
 CRITERIA:1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-03-30 Cont ID  
Sent By btrobaug Date 2010-03-30 Time 12:31 Rev Time 0.00
Received By btrobaug Date 2010-03-30 Time 11:22 Sent To  
Notes
2010-03-30 12:31:32PROVISO
  
 SEPARATE PERMIT AND WIND LOAD CALCULATIONS REQUIRED FOR
 LIGHT POLES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-17 Cont ID  
Sent By dpalmer Date 2009-08-17 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2009-08-17 Time 14:42 Sent To  
Notes
2009-08-17 14:43:281) PLANS NOT SUBMITTED FOR PERMIT.
  
 2) PLANS NOT SIGNED, DATED OR SEALED.
 3) ELECTRICAL CODE NOT YET DETERMINED UNTIL PERMIT
 APPLICATION IS MADE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By dpalmer Date 2009-07-08 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2009-07-08 Time 08:41 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-03-16 Cont ID  
Sent By mgonzale Date 2010-03-16 Time 08:01 Rev Time 1.00
Received By mgonzale Date 2010-03-16 Time 08:01 Sent To  
Notes
2010-03-16 08:08:14COMMENTS HAVE BEEN ADDRESSED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By mgonzale Date 2009-06-18 Time   Rev Time 1.00
Received By mgonzale Date 2009-06-15 Time   Sent To  
Notes
2009-06-18 09:36:04********** FAILED **********
  
 IRRIGATION COMMENTS:
  
 PROVIDE SOURCE OF WATER FOR IRRIGATION? WELL? CITY
 SERVICE?
  
 PROVIDE ADDRESS OF THE WELL OR WATER SERVICE? DOES THE
 WELL HAVE A PERMIT THRU SFWMD?
  
 PROVIDE PEAK GPM NEEDED IF REQUESTING CITY METER?
 PROVIDE 7 1/2" PUMP INFO? 100-120GPM? AND HOW MUCH HEAD
 IT CAN PROVIDE ON THE 3" TRUNK LINE.
 PROVIDE CALCULATIONS SHEET ON PUMP.
  
 IF PUMP IS DRAWING FROM THE LAKE, WILL NEW INTAKE BE
 PROVIDED? SHOW ON PLANS.
  
 IT IS RECOMMENDED THAT PUMP AREA BE GATED AND SECURED
 FOR PEDESTRIAN SAFETY AND VANDALISM.
  
 THERE IS A 2" CITY IRRGIATION METER SERVING THE STATUE
 CORNER AREA (SE CORNER OF OKEECHOBEE AND PARKER AVE),
 WILL THIS METER BE ABANDONED?
 PLEASE PROVIDE ADDRESS OR METER NO SO THAT WE CAN
 UPDATE THE WATER ACCOUNT. SHOW LOCATION ON PLAN. VERIFY
 THAT A BACKFLOW IS IN PLACE.
  
 TENNIS COURT BUILDING HAS LANDSCAPING, DOES THIS
 BUILDING HAS SEPERATE IRRIGATION OR WILL IT BE COMBINED
 WITH THIS PROJECT.
 PLEASE PROVIDE ADDRESS TO THIS BUILDING SO THAT WE CAN
 UPDATE ACCOUNT IN THE EVENT WE NEED TO UPDATE THE
 ACCOUNT.
 WATER SERVICE TO THIS BUILDING SHOULD BE PROTECTED
 DURING INSTALLATIONM OF IRRIGATION AND SITE
 LANDSCAPING. IT IS RECOMMENDED TO BE SHOWN ON THE
 PLANS.
  
 VERIFY EXISTING UTILITIES WM AND FM ALONG OKEECHOBEE
 BLVD AND TURNING SOUTH ALONG PARKER AVE. I THINK THEY
 MAY BE LABELED INCORRECTLY AND OR SHOWN IN WRONG
 LOCATION.
 THIS WILL HELP IRRIGATION LAYOUT AS IT MAY AVOID
 CONFLICTS. 24" FM RUNNNING PARALLEL TO OKEECHOBEE NOT
 SHOW.
  
 ELECTRICAL:
  
 CONVENTION CENTER INFO SIGN SITS ON PARK PROPERTY. WILL
 SIGN BE PROVIDED LIGHTING? CONCRETE PATH (ENTRY FROM
 OKEECHOBEE BLVD) MAY INTERFERE WITH THIS SIGN.
 THEY ARE APPROXIMATELY IN THE SAME LOCATION.
  
 NO LIGHTING SHOWN FOR PARKING AREA.
  
 HC ACCESS ALONG PARKER AVE IS BROKEN WITH ENTRY TO
 PARKING THEREFORE LEAVING NO OPTION AS TO TRAVEL AROUND
 THE PARKING SIDEWALK AREA.
 SHOULD THIS SIDEWALK BE LIGHTED FOR SAFETY? OR SHOULD
 HC ACCESS BE ADDED SO THAT ADA PATH IS MADE AVAILABLE
 ALONG PARKER AVE.
  
 POLE ALONG PARKER AVE WILL REMAIN ALONG WITH THE
 ADDITIONAL THREE PLANNED ALONG CONCRETE WALK?
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time   Rev Time 0.00
Received By mawillia Date 2010-03-25 Time   Sent To  
Notes
2010-03-25 19:11:35*****APPROVED**** (HOWEVER, NO FIRE-STAMPING NEEDED)
  
 THE SCOPE OF WORK AND/OR NO PERSON SHALL PLACE OR KEEP
 ANY POST, FENCE, VEHICLE, GROWTH, VEGETATION, TRASH, OR
 STORAGE OF OTHER MATERIALS THAT WOULD OBSTRUCT A FIRE
 HYDRANT OR FIRE PROTECTION APPLIANCE AND HINDER OR
 PREVENT ITS IMMEDIATE USE BY FIRE DEPARTMENT PERSONNEL.
 SUCH FIRE HYDRANT OR FIRE PROTECTION APPLIANCE SHALL BE
 MAINTAINED READILY VISIBLE AT ALL TIMES.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-07-21 Cont ID  
Sent By mcarsill Date 2009-07-21 Time 08:21 Rev Time 0.00
Received By mcarsill Date 2009-07-21 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-04-09 Cont ID  
Sent By lmartine Date 2010-04-09 Time 13:29 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 11:06 Sent To  
Notes
2010-03-18 11:07:44INCOMING SENT TO C-36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-04 Cont ID  
Sent By rmcdouga Date 2009-08-04 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2009-08-03 Time 10:47 Sent To  
Notes
2009-08-04 10:48:29TO C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 16:45 Rev Time 0.00
Received By mawillia Date 2009-06-10 Time 08:30 Sent To  
Notes
2009-06-10 08:30:29C36

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-08-18 Cont ID  
Sent By rkussner Date 2009-08-18 Time 16:01 Rev Time 0.00
Received By rkussner Date 2009-08-18 Time 16:01 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2009-07-09 Time   Rev Time 0.00
Received By rkussner Date 2009-07-09 Time 09:56 Sent To  
Notes
2009-07-09 11:01:43***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-443 (C)(3), OFF-STREET
 PARKING LOTS CONTAINING AT LEAST 12 INTERIOR PARKING
 SPACES SHALL CONTAIN LANDSCAPE AREAS. THE TOTAL SIZE OF
 SUCH LANDSCAPED AREAS SHALL BE EQUAL TO TEN SQUARE FEET
 FOR EACH PARKING SPACE AND SHALL BE PROVIDED WITHIN THE
 INTERIOR OF AN OFF-STREET PARKING AREA. LANDSCAPED
 AREAS SHALL CONTAIN AT LEAST ONE SHADE TREE OF
 FLOWERING TREE FOR EACH 100 SQUARE FEET OF REQUIRED
 LANDCAPED AREA. A MINIMUM OF 75 PERCENT OF ALL TREES
 THAT ARE REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF
 AN OFF-STREET PAKRING AREA SHALL BE SHADE TREES.
  
 2. PURSUANT TO SECTION 94-443 (C)(3)(B), ONE INTERIOR
 LANDSCAPE ISLAND SHALL BE PROVIDED FOR EVERY TEN
 PARKING SPACES OR FRACTION THEREOF. INTERIOR LANDSCPAE
 ISLANDS SHALL BE AT LEAST FIVE FEET WIDE (EXCLUDING THE
 REQUIRED CURBING) AND SHALL CONTAIN AT LEAST ONE SHADE
 OR FLOWERING TREE.
  
 3. PURSUANT TO SECTION 94-443 (C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH AND NOT
 LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL. THE
 LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE. NO TERMINAL ISLANDS EXIST AT THE
 NORTHEAST END OF THE PARKING LOT.
  
 4. PURSUANT TO SECTION 94-443 (C)(2), VEHICULAR USE
 AREAS SHALL BE SCREENED FROM THOROUGHFARES BY A
 LANDSCAPE BUFFER OF AT LEAST FIVE FEET IN WIDTH. HEDGES
 SHALL BE PLANTED AT TWO-FOOT INTERVALS FOR EACH
 REQUIRED LANDSCAPE BUFFER AND TREES SHALL BE PLANTED AT
 30-FOOT INTERVALS. THIS APPLIES TO ALL SIDES OF THE
 PARKING LOT.
  
 5. PURSUANT TO SECTION 94-448(D)(1), A TREE ALTERATION
 PERMIT IS REQUIRED. THE APPLICANT FOR A TREE REMOVAL
 PERMIT SHAL BE REQUIRED TO RELOCATE OR REPLACE TREES TO
 BE REMOVED. REPLACEMENT TREES SHALL HAVE SHADE AND
 SCREENING POTENTIAL EQUAL TO OR SUPERIOR TO THAT OF THE
 TREES THAT THEY REPLACE AT THE TIME OF THE INITIAL
 INSTALLATION. THERE IS A NET LOSS OF TREE CANOPY THAT
 WILL NEED TO BE MITIGATED.
  
 7. THERE IS A LACK OF PROPOSED TREES FOR THIS PROJECT.
 BECAUSE THIS PARK AREA IS DIRECTLY ACROSS FROM THE
 KRAVIS CENTER RETENTION AREA PLANTING, THE DESIGN
 SHOULD INCORPORATE SIMILAR LANDSCAPE ELEMENTS. BALD
 CYPRESS TREES SHOULD BE PLANTED AROUND THE WATER
 RETENTION AREA. THIS WILL HELP TO TIE THE TWO PARK
 AREAS TOGETHER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-04-05 Cont ID  
Sent By kstevens Date 2010-04-05 Time 09:31 Rev Time 0.00
Received By lwagner Date 2010-04-05 Time 09:26 Sent To  
Notes
2010-04-05 09:31:56IRRIGATION PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 17:07 Rev Time 0.00
Received By kstevens Date 2009-08-10 Time 17:07 Sent To  
Notes
2009-08-10 17:07:22PLUMBING REVIEW:
  
 IRRIGATION PLANS ARE CODE COMPLIANT, BUT WILL REMAIN IN
 FAILED STATUS UNTIL APPLICATION FOR PERMIT AND PLANS
 ARE SIGNED & SEALED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 14:53 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 14:52 Sent To  
Notes
2009-07-01 15:05:12PLUMBING REVIEW:
  
 IRRIGATION PLANS ARE CODE COMPLIANT, BUT WILL REMAIN IN
 FAILED STATUS UNTIL APPLICATION FOR PERMIT AND PLANS
 ARE SIGNED & SEALED.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-08-18 Cont ID  
Sent By aaponte Date 2009-08-18 Time 15:40 Rev Time 0.00
Received By aaponte Date 2009-08-18 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-02 Cont ID  
Sent By aaponte Date 2009-07-02 Time 11:51 Rev Time 0.00
Received By aaponte Date 2009-07-02 Time 11:51 Sent To  
Notes
2009-07-02 11:52:58IRRIGATION AND ELECTRICAL ONLY. PERMIT SHALL BE
 REVIEWED BY ZONING WHEN ENTIRE PROJECT IS PRESENTED.