Plan Review Details - Permit 09060159
Plan Review Stops For Permit 09060159
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-18 Cont ID  
Sent By jwitmer Date 2009-11-18 Time 08:22 Rev Time 0.22
Received By jwitmer Date 2009-11-18 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-08 Cont ID  
Sent By jwitmer Date 2009-10-08 Time 13:55 Rev Time 0.77
Received By jwitmer Date 2009-10-08 Time 13:54 Sent To  
Notes
2009-10-08 14:00:39BUILDING PLAN REVIEW
 PERMIT: 09060159
 ADD: 1501 S FLAGLER DR.
 CONT: CARPENTER ELECTRIC
 TEL: (561)848-7881
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT.8/09
 2ND REVIEW
 ACTION: DENIED
  
 1) SEMI COMPLIED, THE TANK ONLY SHEET FROM AMPS WITH
 COUNTY STAMP DOES INDICATE 2007/2009 CODES, THE AMPS
 SHEET S-1.0 TANK AND GENERATOR DOES NOT INDICATE TO
 WHICH CODE THESE PLANS WERE DESIGNED UNDER.
  
 2) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.8.4.1* EPSSS, INCLUDING ALL
 APPURTENANT COMPONENTS, SHALL BE INSPECTED WEEKLY AND
 EXERCISED UNDER LOAD AT LEAST MONTHLY.
  
 NOTE: TTHE GENERATOR SITS ON TOP OF A 3'-0" BELLY TANK,
 TO GAIN ACCESS TO THE GENERATOR FBC 1009.3EXCEPTION 6
 WOULD REQUIRE THE STAIRS AND LANDING.
  
 2A ) STAIRS 1009.3 EXCEPTION# 6. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 2B ) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 2C ) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A SPHERE WITH A DIAMETER OF 21
 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A DIAMETER OF 21 INCHES
 (533 MM) TO PASS THROUGH ANY OPENING.
  
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 ***
 10-28-09 ADDITIONAL INFORMATION RECEIVED THAT
 DISCONNECT CAN BE REACHED FROM GRADE AND PLATFORM,
 GAURD AND STEPS WILL NOT BE REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-23 Cont ID  
Sent By jwitmer Date 2009-06-23 Time 13:59 Rev Time 0.50
Received By jwitmer Date 2009-06-23 Time 13:00 Sent To  
Notes
2009-06-23 15:58:58BUILDING PLAN REVIEW
 PERMIT: 09060159
 ADD: 1501 S FLAGLER DR.
 CONT: CARPENTER ELECTRIC
 TEL: (561)848-7881
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED INDICATE THE 2004 FBC , FOR PERMIT
 (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE
 REVIEWED TO THE 2007 FBC BUILDING WITH 2009
 SUPPLEMENTS. PLEASE UPDATE PLANS.
  
 2) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 2A ) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 2B ) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 2C ) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A SPHERE WITH A DIAMETER OF 21
 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 13:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By dpalmer Date 2009-10-01 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2009-10-01 Time 09:45 Sent To  
Notes
2009-10-01 09:45:31 
 **PROVISO **
  
  
  
 1) NOTE: THIS IS NOTE #4 FROM PREVIOUS REVIEW IS STILL
 APPLICABLE. PLEASE SEE NEC 230.70, 71. THE CITY OF WEST
 PALM BEACH IS AWARE OF THE OLD PREVIOUS TECHNICAL
 AMENDMENTS BEFORE THE 2001 FBC. HOWEVER THE NEC STATES
 THE DISTANCE OF UNPROTECTED CONDUCTORS IS UP TO THE
 AHJ. THIS AHJ HAS REMAINED WITH NO MORE THAN 8FT BASED
 KEEPING WITH THE PREVIOUS TECHNICAL AMENDED CODES. SOME
 JURISDICTIONS HAVE A 0 FT REQUIREMENT THAT DOES NOT
 PERMIT UNPROTECTED CONDUCTORS INSIDE THE BUILDING AT
 ALL.
 THE INSTALLATION FOR THE NEW SERVICE ENTRANCE
 CONDUCTORS IS NEW. THERE HAVE BEEN SEVERAL OTHERS WHICH
 HAVE EITHER POURED INTO A CONCRETE TROUGH OR PLACED
 UNDER SLAB TO MINIMIZE THE LENGTH INSIDE BUILDING.
 PLEASE SEE 230.6 FOR CONDUCTORS INSIDE BUILDING. THIS
 WAS GONE OVER THE CHIEF ELECTRICAL INSPECTOR ALSO.
 THE CONDUCTORS FOR EM ATS/MAIN MUST MEET 700.9C, D1
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-09 Cont ID  
Sent By dpalmer Date 2009-07-09 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 14:54 Sent To  
Notes
2009-07-09 17:02:33 
 ** DENIED **
  
 1) NOTE: PLEASE PROVIDE SELECTIVE COORDINATION STUDY
 FOR 700 AND 701 SYSTEMS. PLEASE SEE 701.27, 701.18 AND
 240.12. NFPA-110 6.5.1
  
 2) NOTE: PLEASE PROVIDE ELEVATION FOR EPS EQUIPMENT
 MEETING THE 100 YR STORM ELEVATIONS OR LEVELS ON THE
 SLOSH CHARTS FOR AREA.
 PLEASE SEE NFPA-110 7.2.3
  
 3) NOTE: PLEASE SEE 7.2.2 AND 7.2.1. LOCATIONS OF
 EQUIPMENT CLEARANCES OF ATS EQUIPMENT TWICE THE
 MINIMUMS PER 110.26 OF NFPA-70.
  
 4) NOTE: PLEASE KNOW THAT NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE THE
 BUILDING. PLEASE SEE 230.70, 230.6 FOR WHAT IS
 CONSIDERED OUTSIDE THE BUILDING.
  
 5) NOTE: IT IS UNCLEAR OF THE INTENT OF SERVICE RISER.
 IT APPEARS THE EXISTING 2000AMP SERVICE WILL BE TAPPED
 AND FED FROM NEW 400AMP SERVICE. THE LOADS SHOWN PER
 220.87 ARE INDICATED HOWEVER THE MINIMUM SERVICE SIZE
 FOR BUILDING IS STILL REQUIRED TO BE SIZED PER MINIMUM
 LOAD CALCULATIONS.
 THIS IS BASED ON DETERMINING EXISTING LOADS.
 THE REMAINDER OF 220 WOULD APPLY FOR MINIMUM SERVICE
 SIZE.
  
 ** IF THIS IS NOT THE INTENT THEN PLEASE CALL TO GO
 OVER. BASED ON THE RISER IT APPEARS THE LINE SIDE OF
 GUTTER WHICH IS FED FROM THE EXISTING 2000AMP MAIN WILL
 BECOME NEW SERVICE FEEDERS.
  
 *** PLEASE BE AWARE OF OTHER COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT PLANS.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-11-24 Cont ID  
Sent By mawillia Date 2009-11-24 Time 12:14 Rev Time 0.00
Received By mawillia Date 2009-11-24 Time 12:02 Sent To E
Notes
2009-11-24 12:10:29*****APPROVED*****
  
 PLAN SHEET E-1 (OF 3) STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-10-16 Cont ID  
Sent By mawillia Date 2009-10-16 Time 14:01 Rev Time 0.00
Received By mawillia Date 2009-10-16 Time 13:51 Sent To  
Notes
2009-10-16 13:55:41*****FIRE STAMPING NEEDED*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 13:08 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 12:30 Sent To  
Notes
2009-06-29 13:07:17*****FIRE STAMPING NEEDED*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 10:46 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 13:56 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 13:52 Sent To R
Notes
2009-07-13 13:56:39REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SUBMITTAL DATA INDICATES AN 850 GALLON DIESEL FUEL
 TANK. ALL ABOVE GROUND FUEL TANKS IN EXCESS OF 550
 GALLONS SHALL BE SUBMITTED TO AND APPROVED BY PALM
 BEACH COUNTY DERM PRIOR TO PERMIT ISSUANCE. SUBMIT TWO
 SETS OF PBC DERM APPROVED PLANS UPON RESUBMISSION. FOR
 ADDITIONAL INFORMATION ON THE DERM APPROVAL PROCESS
 PLEASE VISIT WWW.PBCGOV.COM/ERM OR CALL 561-233-2400.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-16 Cont ID  
Sent By shill Date 2009-11-16 Time 11:05 Rev Time 0.00
Received By shill Date 2009-11-16 Time 11:05 Sent To  
Notes
2009-11-16 11:09:41B15
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-22 Time 15:41 Rev Time 0.00
Received By lmartine Date 2009-09-22 Time 15:41 Sent To  
Notes
2009-09-22 15:42:07B--9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-13 Time   Rev Time 0.00
Received By dpalmer Date 2009-06-10 Time 08:02 Sent To  
Notes
2009-06-10 08:17:56B-20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 10:47 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 13:51 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 13:45 Sent To FUEL
Notes
2009-07-13 13:51:03REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ALL APPLIANCES EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12. PAGE 31 OF THE SUBMITTAL PACKAGE INDICATES THE
 WEATHERPROOF ENCLOSURE WAS DESIGNED TO ASCE 7-98 FOR
 WIND RESISTANCE. THE CURRENT REFERENCE STANDARD IN THE
 2007 FBC FOR WIND RESISTANCE IS ASCE 7-05 IN ACCORDANCE
 WITH FBC-B CHAPTER 35. PLEASE UPDATE ALL WIND
 RESISTANCE ANALYTICAL DATA AND DESIGN CRITERIA TO
 REFLECT COMPLIANCE WITH THE CURRENTLY ADOPTED REFERENCE
 STANDARD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2009-11-19 Cont ID  
Sent By kdfreema Date 2009-11-19 Time 11:37 Rev Time 0.00
Received By kdfreema Date 2009-11-19 Time 11:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-10-05 Cont ID  
Sent By kdfreema Date 2009-10-05 Time 13:12 Rev Time 0.00
Received By kdfreema Date 2009-10-05 Time 13:12 Sent To  
Notes
2009-10-05 15:42:07***FAILED***
  
 1. PLEASE SHOW THE PROPOSED HEDGING ON THE PLANS,
 INCLUDING MATERIAL HEIGHT AND SPACING. NOTE THAT SINCE
 THE GENERATOR HEIGHT IS APPROXIMATELY 9.5 FEET THE
 HEDGE MATERIAL NEEDS TO BE AT LEAST 8 FEET IN HEIGHT AT
 THE TIME OF INSTALLATION. AS AN ALTERNATIVE, A 10 FOOT
 FENCE COULD BE INSTALLED AROUND THE GENERATOR WHICH
 WOULD ALLOW YOU TO INSTALL THE HEDGES AT 24 INCHES IN
 HEIGHT. IN ANY EVENT, BEAR IN MIND THE REQUIRED
 CLEARANCES FOR THE GENERATOR SO THAT FENCING AND/OR
 LANDSCAPE MATERIALS DO NOT INCROACH INTO IT.
  
 NOTE THAT WHATEVER COMBINATION OF PLANTS AND FENCING IS
 USED, IT MUST BE SHOWN ON THE PLAN WITH DIMENSIONS AND
 SPECIFICATIONS.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By kdfreema Date 2009-06-18 Time 11:30 Rev Time 0.00
Received By kdfreema Date 2009-06-18 Time 11:30 Sent To  
Notes
2009-06-18 14:26:59***FAILED***
  
 1.PURSUANT TO SECTION 94-444(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE GENERATOR IS REQUIRED TO
 BE FULLY SCREENED FROM VIEW BY MEANS OF A WALL OR FENCE
 SURROUNDED BY SHRUBS AND HEDGES PLANTED AT TWO FOOT
 INTERVALS. THERE IS FLEXIBILITY WITH RESPECT TO THE
 DESIGN AND MATERIALS. FOR INSTANCE, A DENSE PLANTING OF
 PODOCARPUS MACROPHYLLA INSTALLED AT 6-8 FEET IN HEIGHT
 AT THE TIME OF PLANTING MAY BE PROVIDED IN LIEU OF THE
 WALL. PLEASE CONTACT ME TO WORK OUT THE SPECIFICS ON
 THIS SITE.
  
 2. PLEASE PROVIDE THE SETBACK OF THE GENERATOR ITSELF.
 THE PLANS SHOW THE SETBACK TO THE SLAB AS TEN FEET
 SEVEN INCHES, HOWEVER, THE SETBACK TO THE GENERATOR
 ENCLOSURE IS NOT NOTED. PLEASE BEAR IN MIND THAT THE
 REQUIRED SETBACK IS NO LESS THAN 11 FEET.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.