Plan Review Details - Permit 09060157
Plan Review Stops For Permit 09060157
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-06-10 Cont ID  
Sent By mcarsill Date 2009-06-10 Time 14:11 Rev Time 0.00
Received By mcarsill Date 2009-06-10 Time 13:58 Sent To  
Notes
2009-06-10 14:11:13EXISTING FIRE SPRINKLER SYSTEM BEING CHANGED FOR THE
 PALM BEACH PHOTOGRAPHIC CENTER AT CITY CENTER.
  
 1. ENSURE THAT ALL SERVICE ROOMS TO INCLUDE ELECTRICAL,
 MECHANICAL, SERVICE AND CLOSETS ARE EQUIPPED WITH FIRE
 SPRINKLER HEADS.
  
 2. THE FIRE SPRINKLER HEADS PLANNED FOR THE INTERIOR OF
 THE PHOTOGRAPHIC CENTER AT THE WATER CURTAIN LOCATION
 SHALL BE INSTALLED AT 1' OFF THE GLASS AND BE NO MORE
 THAN 6' APART.
  
 3. THE CONCEALED PLATES SHALL ONLY CONTAIN PAINT THAT
 IS APPLIED AT THE FACTORY.
  
 4. THE FIRE SPRINKLER SYSTEM INSTALLATION TO COMPLY
 WITH NFPA 13, THE STANDARD FOR AUTOMATIC FIRE
 SPRINKLERS.
  
 5. THE QUALITY AND DESIGN OF THE REMODEL SHALL BE EQUAL
 TO THAT OF THE REMAINDER OF THE COMPLEX.
  
 6. INSTALLATION IS SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
 7, SHOULD THE FIRE SPRINKLER NEED TO BE SHUT OFF FOR
 MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR PERIOD, A
 FIRE WATCH SHALL OCCUR. ALL FIRE WATCH ACTIVITIES SHALL
 BE APPROVED BY THE BATTALION CHIEF OF FIRE PREVENTION
 OR HIS DESIGNEE. MORE INFORMATION CAN BE OBTAINED
 REGARDING FIRE WATCH AT 804-4774,
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX