Plan Review Details - Permit 09060152
Plan Review Stops For Permit 09060152
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 18:52 Rev Time 0.00
Received By shill Date 2009-07-22 Time 18:52 Sent To  
Notes
2009-07-22 18:52:12PASSED W/REDLINE, 45 MIN DOORS IN TENANT SEPARATION
 WALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 20:52 Rev Time 0.00
Received By shill Date 2009-06-15 Time 20:52 Sent To  
Notes
2009-06-15 20:53:05PASSED W/REDLINE, 45 MIN DOORS AT TENANT SEPARATION
 WALL

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-10-28 Cont ID  
Sent By dpalmer Date 2009-10-28 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2009-10-28 Time 09:10 Sent To  
Notes
2009-10-28 09:12:00** DENIED **
  
 SPEC SPACE #3 ON FLOOR 6.
  
 1) NOTE: SHEET E-1 DOES INDICATE REVISION A REVISION #3
 IN THE TITLE BLOCK HOWEVER NOTHING ON PLANS.
 E-2 DOES INDICATE REV #3 ON TITLE BLOCKS AND PLANS
 HWOEVER NO CHANGES FROM RECORD SETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 19:24 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By dpalmer Date 2009-06-18 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2009-06-18 Time 13:20 Sent To  
Notes
2009-06-18 13:20:12** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 ** PLEASE BE AWARE FRONT COVER SHEET IS SHOWING 2007
 AND 2004 FBC. REDLINED OFF THE 2004
  
 2) NOTE:
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE CLARIFY WHY PANEL 6-OHP IS SHOWN.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION.
 NEC 408,240,
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 16:01 Rev Time 0.00
Received By mawillia Date 2009-07-22 Time 15:52 Sent To B
Notes
2009-07-22 16:01:28*****APPROVED*****
  
 THE PROVISO COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED; PLAN SHEETS A1.1, A2.1, A3.1, AND
 E1 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By mawillia Date 2009-06-22 Time 14:54 Rev Time 0.00
Received By mawillia Date 2009-06-22 Time 14:47 Sent To  
Notes
2009-06-22 14:49:35*****PROVISO*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. ON SHEET A3.1, AS PER BUILDING EXAMINER'S
 RED-LINING, THE NEW FIRE RATED DOOR (DOOR A) SHALL BE
 45 MINUTES.
  
 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER
 HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A
 LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON
 SHEET A2.1, REFLECTED CEILING PLAN).
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE AS WELL AS OTHER PLAN EXAMINER(S)' COMMENTS
 HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 13:19 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 13:19 Sent To  
Notes
2009-10-20 13:20:09B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 15:08 Rev Time 0.00
Received By shill Date 2009-07-15 Time 15:08 Sent To  
Notes
2009-07-15 15:08:34B18
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 14:29 Sent To PC
Notes
2009-06-08 14:32:05B15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 09:28 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 09:24 Sent To  
Notes
2009-11-06 09:28:30REVISED M1 DELTA 4, M2 DELTA 1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-06 Cont ID  
Sent By rregueir Date 2009-07-06 Time 16:24 Rev Time 0.00
Received By rregueir Date 2009-07-06 Time 16:23 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 16:37 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-23 Cont ID  
Sent By aaponte Date 2009-06-23 Time 10:57 Rev Time 0.00
Received By aaponte Date 2009-06-23 Time 10:56 Sent To  
Notes
***NONE***