Plan Review Details - Permit 09060151
Plan Review Stops For Permit 09060151
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 18:42 Rev Time 0.00
Received By shill Date 2009-07-22 Time 18:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-01 Cont ID  
Sent By jwitmer Date 2009-07-01 Time 12:15 Rev Time 0.77
Received By jwitmer Date 2009-07-01 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-28 Cont ID  
Sent By dpalmer Date 2009-10-28 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2009-10-28 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 20:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By dpalmer Date 2009-06-18 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2009-06-18 Time 11:56 Sent To  
Notes
2009-06-18 11:56:47 
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC
 ARE ALSO NOT IN THE CODE.
 PLANS SHOW THE ADDITIONAL FUTURE PENDANT FIXTURES
 HOWEVER NO ALLOWANCES ARE SHOWN.
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SHOW LIGHTING FOR BATHROOMS PER
 NFPA-101 7.8, 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES
 SHOWN FOR MINIMUM EGRESS LIGHTING.
 ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE
 OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER
 EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR
 LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS
 COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS.
 PLEASE BE SURE TO GO OVER THIS WITH BUILDING
 OWNER/MANAGEMENT.
 OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED
 UNDER EMERGENCY POWER.
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-11-10 Cont ID  
Sent By mawillia Date 2009-11-10 Time 09:56 Rev Time 0.00
Received By mawillia Date 2009-11-10 Time 09:48 Sent To M
Notes
2009-11-10 09:54:29*****REVISION, DATED 10/01/09 APPROVED*****
  
 OF THE 5 SUBMITTED REVISED PLAN SHEETS, SHEET E2
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 15:00 Rev Time 0.00
Received By mawillia Date 2009-07-22 Time 14:51 Sent To B
Notes
2009-07-22 15:00:19*****APPROVED*****
  
 THE PROVISO COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED; PLAN SHEETS A1.1, A2.1, A3.1, AND
 E2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By mawillia Date 2009-06-19 Time 15:09 Rev Time 0.00
Received By mawillia Date 2009-06-19 Time 14:54 Sent To  
Notes
2009-06-19 15:06:46*****PROVISO*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER
 HEADS TO BE REMODELED IN ANY MANNER?
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE AS WELL AS OTHER PLAN EXAMINER(S)' COMMENTS
 HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 13:22 Sent To  
Notes
2009-10-20 13:22:48B10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 15:01 Rev Time 0.00
Received By shill Date 2009-07-15 Time 15:01 Sent To  
Notes
2009-07-15 15:01:58B17
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 14:55 Sent To PC
Notes
2009-06-08 14:55:28B17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 09:50 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 09:32 Sent To  
Notes
2009-11-06 09:50:33REVISED M1 DELTA 5, M2 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By rregueir Date 2009-07-22 Time 11:42 Rev Time 0.00
Received By rregueir Date 2009-07-22 Time 11:22 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-06 Cont ID  
Sent By rregueir Date 2009-07-06 Time 16:46 Rev Time 0.00
Received By rregueir Date 2009-07-06 Time 16:41 Sent To PC
Notes
2009-07-06 16:46:21REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 SHOWS TWO NEW SUPPLY DUCTS AND TWO NEW
 EXHAUST DUCTS ENTERING RESTROOMS FROM THE COMMON AREA
 CORRIDOR/ELEVATOR LOBBY AREA. ARCHITECTURAL PLANS
 INDICATE RATED WALLS AT THESE LOCATIONS. SHOW HOW DUCT
 PENETRATIONS OF THESE RATED ASSEMBLIES ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBC-M 607.5.
  
 2. PAGE M1 SHOWS 8" ROUND DUCT AT HEAT PUMP TIES INTO
 EXISTING SMOKE EVAC/FRESH AIR DUCT. FLOOR PLAN
 INDICATES THE 8" ROUND TIES IN AT THE SAME LOCATION OF
 AN EXISTING FIRE DAMPER, HALF WAY THROUGH A RATED WALL.
 PLEASE CLARIFY AND SHOW HOW REQUIRED FIRE RATINGS ARE
 TO BE MAINTAINED AT THIS LOCATION PER FBC-M 607.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-18 Cont ID  
Sent By kstevens Date 2009-06-18 Time 08:32 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 16:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-23 Cont ID  
Sent By aaponte Date 2009-06-23 Time 10:58 Rev Time 0.00
Received By aaponte Date 2009-06-23 Time 10:58 Sent To  
Notes
***NONE***