Plan Review Details - Permit 09060146
Plan Review Stops For Permit 09060146
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-23 Cont ID  
Sent By shill Date 2009-09-23 Time 15:54 Rev Time 0.00
Received By shill Date 2009-09-23 Time 15:54 Sent To  
Notes
2009-09-23 15:55:20REVISION #2 DATED 9/10/9, SHEET A1.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 18:31 Rev Time 0.00
Received By shill Date 2009-07-22 Time 18:31 Sent To  
Notes
2009-07-22 18:31:26PASSED W/REDLINE, 45 MIN DOORS IN TENANT SEPARATION
 WALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 20:23 Rev Time 0.00
Received By shill Date 2009-06-15 Time 20:23 Sent To  
Notes
2009-06-15 20:23:36PASSED W/REDLINE, 45 MIN DOOR AT TENANT SEPARATION

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-10-28 Cont ID  
Sent By dpalmer Date 2009-10-28 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2009-10-28 Time 08:20 Sent To  
Notes
2009-10-28 08:20:14** DENIED **
  
 SPEC SPACE #5 ON FLOOR 6.
  
 1) NOTE: SHEET E-1 DOES NOT ACTUALLY INDICATE ANY
 REVISION IN THE TITLE BLOCK OR ON THE PLANS.
 SHEET E-2 DOES CONTAIN A REVISION #3 IN THE TITLE BLOCK
 HOWEVER NO REVISION OR #3 CAN BE LOCATED ON THE PLANS.
 SHEET E-3 DOES CONTAIN A REVISION #3 ON THE TITLE
 BLOCKS AND A TRIANGLE #3 ON PLANS HOWEVER THE PLANS
 WERE NOT ACTUALLY REVISED. THE PLANS HAVE NO CHANGES
 THAT COULD BE FOUND.
 SHEETS E-1, 2, AND 3 WERE STAMPED INADVERTENTLY AND ARE
 SINCE VOIDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 19:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By dpalmer Date 2009-06-18 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2009-06-18 Time 08:35 Sent To  
Notes
2009-06-18 08:35:31 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC
 ARE ALSO NOT IN THE CODE.
 PLANS SHOW CALCULATIONS FOR MOST AREAS HOWEVER SOME ARE
 IN QUESTION.
 FOR EXAMPLE: ROOM 631 MISSING FROM CALCULATIONS.
 FOR EXAMPLE: SQ FT FOR AREA629 EXCEED SQ FT ON PLANS.
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE CLARIFY WHY PANEL 6-OHP IS SHOWN.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION.
 NEC 408,240,
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 15:31 Rev Time 0.00
Received By mawillia Date 2009-07-22 Time 15:17 Sent To B
Notes
2009-07-22 15:31:11*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A1.1, A2.1, A3.1, AND E2
 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By mawillia Date 2009-06-19 Time 14:51 Rev Time 0.00
Received By mawillia Date 2009-06-19 Time 13:59 Sent To  
Notes
2009-06-19 14:49:45*****DENIED*****
  
 1. ON SHEET T, A WHITE-OUTED AREA IN THE PROJECT DATA
 IS SHOWN. BE ADVISED THAT THE PLANS SHALL BE PRESENTED
 WITH NO INK, PENCIL, AND/OR ANY OTHER MARKINGS.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE
 PROJECT SITE. (THEY MAY BE SHOWN ON SHEET A2.1
 REFLECTED CEILING PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 12:46 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 12:46 Sent To  
Notes
2009-10-20 12:47:11B5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 16:36 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 16:36 Sent To  
Notes
2009-09-15 16:39:12SENT TO SHILL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 14:55 Rev Time 0.00
Received By shill Date 2009-07-15 Time 14:55 Sent To  
Notes
2009-07-15 14:55:46B15
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 14:19 Sent To PC
Notes
2009-06-08 14:20:08TO B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 10:06 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 10:00 Sent To  
Notes
2009-11-06 10:06:07REVISED M1 DELTA 5, M2 DELTA 1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-06 Cont ID  
Sent By rregueir Date 2009-07-06 Time 15:51 Rev Time 0.00
Received By rregueir Date 2009-07-06 Time 15:49 Sent To PC
Notes
2009-07-06 15:51:15**PROVISO**
 REVISE PAGE M1 TO SHOW MISSING "D1" MOTORIZED VOLUME
 DAMPERS TO CORRESPOND WITH DETAIL ON PAGE M2 FOR SMOKE
 CONTROL SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 16:00 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 15:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-23 Cont ID  
Sent By aaponte Date 2009-06-23 Time 10:54 Rev Time 0.00
Received By aaponte Date 2009-06-23 Time 10:53 Sent To  
Notes
***NONE***