Plan Review Details - Permit 09060097
Plan Review Stops For Permit 09060097
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-06-09 Cont ID  
Sent By jnguyen Date 2009-06-09 Time 09:23 Rev Time 0.00
Received By jnguyen Date 2009-06-08 Time 13:25 Sent To  
Notes
2009-06-09 09:05:56THIS PARCEL (PCN# 74424320010050010) WAS PREVIOUSLY AN
 UNADDRESSED ONE THAT TOOK ACCESS OFF OKEECHOBEE BLVD. I
 EXAMINED THE SITE PLANS & NOTICED THAT THERE WOULD BE
 ADDITIONAL NEW COMMERCIAL STRUCTURES ON THESE TWO
 PARCELS (PCN#S 74424320010050010 & 74424320000005040)
 TO THE WEST OF WPB FIRE STATION #7. IN THE MEANTIME,
 THIS PERMIT WAS ONLY REFERRING TO THE PROPOSED PALM
 BEACH COMMUNITY BANK (LABELED BUILDING D ON THE SITE
 PLAN IN B). I CONTACTED THE ARCHITECTURAL COMPANY,
 URBAN DESIGN KILDAY STUDIOS & REQUESTED THAT THEY SEND
 ME A PART OF THE SITE PLAN BACK IN DIGITAL FORMAT
 (FSP-1 OF 2), WHICH THEY DID. I ALSO SENT THEM A COPY
 OF OUR ADDRESSING & STREET NAMING POLICY, SPECIFICALLY
 POINTED OUT SECTION 1.3: IT WILL BE THE DEVELOPER
 RESPONSIBILITY TO ASSIGN UNIT (DESIGNATORS) ADDRESSES
 TO ALL UNITS INSIDE THE STRUCTURE .THE LIST OF
 ADDRESSES MUST BE APPROVED BY THE SUPPORT SERVICES
 DEPARTMENT IN CHARGE OF ADDRESSING PRIOR TO RELEASE THE
 CERTIFICATE OF OCCUPANCY.
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO 199, (100
 MAIN ST. # 101, INDICATES THE UNIT ON THE FIRST FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299, (100 MAIN
 ST. # 201, INDICATES THE FIRST UNIT ON THE SECOND
 FLOOR)
  
 AFTER ANALYZING THE STREET RANGE, I DECIDED TO ASSIGN
 THE PALM BEACH COMMUNITY BANK THE PRIMARY ADDRESS OF
 8101 OKEECHOBEE BLVD FOR PCN# 74424320010050010. I
 ADJUSTED THE LOCATION RECORD IN COMMUNITYPLUS TO 8101
 OKEECHOBEE BLVD UNDER PCN# 74424320010050010, THEN
 NOTIFIED ALL OF THE RELEVANT PARTIES (FPL, USPS, PAPA,
 ETC.) VIA E-MAIL OF THE NEWLY ISSUED ADDRESS (CC: URBAN
 DESIGN KILDAY STUDIOS & SISCA CONSTRUCTION SERVICES,
 LLC). I ALSO CORRECTED IT ON THE ORIGINAL PERMIT
 APPLICATION & RETURNED ALL OF THE ASSOCIATED DOCUMENTS
 BACK INTO THE C-30 BOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-06-14 Cont ID  
Sent By shill Date 2010-06-14 Time 13:36 Rev Time 0.00
Received By shill Date 2010-06-14 Time 13:36 Sent To  
Notes
2010-06-14 13:37:05NOA FOR BILCO ROOF HATCH SUBMITTED
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-02-01 Cont ID  
Sent By shill Date 2010-02-01 Time 11:19 Rev Time 0.00
Received By shill Date 2010-02-01 Time 11:19 Sent To  
Notes
2010-02-01 11:25:22****PROVISOS****
 ***PERMIT IS ISSUED AT CONTRACTOR'S RISK***
 ***REVISION REQUIRED***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 ****PROVISO ITEMS****
  
 1. WINDOW SPRINKLER REQUIRED APPROVAL BY BUILDING
 OFFICIAL THROUGH ALTERNATE MATERIAL & METHODS, ADDRESS
 BEFORE INSTALLATION. SEE FBC715.3, TABLE 715.5.
  
 2. SEPARATE PERMITS REQUIRED FOR SITEWORK ON ADJACENT
 PARCELS (WORK SHOWN ON SITE PLAN).
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE ROOF HATCH, FAC9B72. THE SPEC SHEET PROVIDED IS FOR
 SEVERAL DIFFERENT ROOF HATCH PRODUCTS; ONLY THE S20
 (AND ATTACHMENT TO STEEL) HAS A LOCAL PRODUCT APPROVAL.
 PLEASE CONFIRM THAT THIS IS THE SPECIFIC PRODUCT YOU
 WISH TO USE AND A COPY OF THE LOCAL PRODUCT APPROVAL
 WILL BE PROVIDED, OR SUBMIT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL FOR THE ROOF HATCH. ADDRESS PRIOR TO
 INSTALLATION.
  
 4. ROOFING INFORMATION TO BE SUBMITTED WITH ROOF
 PERMIT; NOA07-1023.09, 07-0228.07 (CONCRETE TILE AND
 MODIFIED). WHEN SUBMITTING FOR ROOF PERMIT, INDICATE
 WHICH APPROVED ASSEMBLY IS TO BE INSTALLED, INCLUDE
 SPECIFIC FASTENING INFORMATION AND ENHANCED FASTENING
 FOR ZONES 2 & 3 IF APPLICABLE. ROOF DPS, SHEET S501:
 -48.3, -81.1, -113.9
  
 5. ORIGINAL SOILS REPORT REQUIRED FS471.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-01-28 Cont ID  
Sent By shill Date 2009-12-23 Time 13:17 Rev Time 0.00
Received By rbrown Date 2009-12-23 Time 13:17 Sent To  
Notes
2010-01-28 17:08:02IMPACT FEES HAVE BEEN PAID. PASSED WITH PROVISOS AS
 STATED BELOW.
  
2009-12-23 13:27:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS WHICH HAVE BEEN ADDRESSED HAVE BEEN REMOVED.
 NUMBERING FOR OTHER COMMENTS REMAIN THE SAME AS
 PREVIOUS LIST.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 ****PROVISO ITEMS****
 THESE ITEMS WILL NOT PREVENT "P" STATUS FOR BUILDING -
 ANY ITEMS NOT ADDRESSED AFTER THE ABOVE TWO ITEMS HAVE
 BEEN ADDRESSED WILL BE PROVISO ITEMS, TO BE ADDRESSED
 AS NOTED:
  
 4. WINDOW SPRINKLER REQUIRED APPROVAL BY BUILDING
 OFFICIAL THROUGH ALTERNATE MATERIAL & METHODS, ADDRESS
 BEFORE INSTALLATION (SEE ALSO ITEM 9).
  
 5. PLEASE SEE ZONING COMMENTS ; 2ND REVIEW, PLEASE
 EITHER SUBMIT TWO ADDITIONAL PERMIT APPLICATIONS FOR
 THE TWO OTHER PARCELS WHICH SCOPE OF WORK INCLUDES, OR
 APPLY FOR A SEPARATE SITEWORK PERMIT. PLEASE CONTACT ME
 IF YOU NEED ASSISTANCE. ADDRESS BEFORE COMMENCEMENT OF
 SITEWORK.
  
 9. PRIOR COMMENT WAS ADDRESSED BUT SEE FBC715.3,
 PROVIDE DOCUMENTATION (WINDOW TO COMPLY WITH FBC TABLE
 715.5). ADDRESS BEFORE INSTALLATION.
  
 18. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH, FAC9B72. THE SPEC SHEET PROVIDED IS
 FOR SEVERAL DIFFERENT ROOF HATCH PRODUCTS; ONLY THE S20
 (AND ATTACHMENT TO STEEL) HAS A LOCAL PRODUCT APPROVAL.
 PLEASE CONFIRM THAT THIS IS THE SPECIFIC PRODUCT YOU
 WISH TO USE AND A COPY OF THE LOCAL PRODUCT APPROVAL
 WILL BE PROVIDED. ADDRESS PRIOR TO INSTALLATION.
  
 21. ROOFING INFORMATION TO BE SUBMITTED WITH ROOF
 PERMIT; NOA07-1023.09, 07-0228.07 (CONCRETE TILE AND
 MODIFIED).
  
 23. ORIGINAL SOILS REPORT REQUIRED FS471. (I WAS UNABLE
 TO LOCATE THIS IN THE NEW SUBMITTAL.)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-01 Cont ID  
Sent By shill Date 2009-10-01 Time 19:44 Rev Time 0.00
Received By shill Date 2009-09-28 Time 14:35 Sent To  
Notes
2009-10-01 20:02:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS WHICH HAVE BEEN ADDRESSED HAVE BEEN REMOVED.
 NUMBERING FOR OTHER COMMENTS REMAIN THE SAME AS
 PREVIOUS LIST.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 4. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2). SOME SHEETS REFER TO ATTACHED FIRE
 SPRINKLER/FIRE ALARM PLANS, BUT THEY WERE NOT INCLUDED.
 2ND REVIEW, PLEASE SUBMIT AS DISCUSSED.
  
 ****PROVISO ITEMS****
 THESE ITEMS WILL NOT PREVENT "P" STATUS FOR BUILDING -
 ANY ITEMS NOT ADDRESSED AFTER THE ABOVE TWO ITEMS HAVE
 BEEN ADDRESSED WILL BE PROVISO ITEMS, TO BE ADDRESSED
 AS NOTED:
  
 5. PLEASE SEE ZONING COMMENTS ; 2ND REVIEW, PLEASE
 EITHER SUBMIT TWO ADDITIONAL PERMIT APPLICATIONS FOR
 THE TWO OTHER PARCELS WHICH SCOPE OF WORK INCLUDES, OR
 APPLY FOR A SEPARATE SITEWORK PERMIT. PLEASE CONTACT ME
 IF YOU NEED ASSISTANCE. ADDRESS BEFORE COMMENCEMENT OF
 SITEWORK.
  
 9. PRIOR COMMENT WAS ADDRESSED BUT SEE FBC715.3,
 PROVIDE DOCUMENTATION (WINDOW TO COMPLY WITH FBC TABLE
 715.5). ADDRESS BEFORE INSTALLATION.
  
 18. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH, FAC9B72. THE SPEC SHEET PROVIDED IS
 FOR SEVERAL DIFFERENT ROOF HATCH PRODUCTS; ONLY THE S20
 (AND ATTACHMENT TO STEEL) HAS A LOCAL PRODUCT APPROVAL.
 PLEASE CONFIRM THAT THIS IS THE SPECIFIC PRODUCT YOU
 WISH TO USE AND A COPY OF THE LOCAL PRODUCT APPROVAL
 WILL BE PROVIDED. ADDRESS PRIOR TO INSTALLATION.
  
 21. ROOFING INFORMATION TO BE SUBMITTED WITH ROOF
 PERMIT; NOA07-1023.09, 07-0228.07 (CONCRETE TILE AND
 MODIFIED).
  
 23. ORIGINAL SOILS REPORT REQUIRED FS471. (I WAS UNABLE
 TO LOCATE THIS IN THE NEW SUBMITTAL.)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-26 Cont ID  
Sent By shill Date 2009-06-26 Time 17:57 Rev Time 0.00
Received By shill Date 2009-06-22 Time 17:16 Sent To  
Notes
2009-06-26 17:57:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT APPEARS THAT THIS PARCEL MAY BE LOCATED IN A HIGH
 HAZARD FLOOD ZONE. THE STRUCTURE IS TO COMPLY WITH WPB
 ADMIN CODE 94-546(B). PLEASE NOTE FINISHED FLOOR
 ELEVATION, MINIMUM 6" ABOVE BASE FLOOD, ON THE PLAN AND
 PROVIDE THE FLOOD ELEVATION CERTIFICATE. A FORM BOARD
 ELEVATION CERTIFICATE AS WELL AS A FINAL ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3. RADON FEES DUE, FS*553.721. SEE ATTACHED.
  
 4. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2). SOME SHEETS REFER TO ATTACHED FIRE
 SPRINKLER/FIRE ALARM PLANS, BUT THEY WERE NOT INCLUDED.
  
 5. PLEASE SEE ZONING COMMENTS AND CLARIFY LOCATION OF
 PARCEL LINES. PLEASE CLARIFY LOCATION OF IMPROVEMENTS
 IN RELATION TO THE LEGAL RECORDED LOT LINES/PLAT. THE
 TRACTS SHOWN ON THE PLAN ARE NOT CONSISTENT WITH COUNTY
 RECORDS. WWW.PBCGOV.COM/PAPA, WWW.PBCOUNTYCLERK.COM
  
 6. AREA INCREASE CALCULATIONS ARE TO BE INCLUDED ON THE
 PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503, SHEET A1.
  
 7. STORAGE AREAS AND A CONFERENCE ROOM (ASSEMBLY) ARE
 SHOWN. PLEASE INCLUDE THESE AREAS IN THE AREA
 CALCULATIONS, SHEET A1, FBC508.1. ANY ACCESSORY OR
 INCIDENTAL USE AREAS ARE TO BE NOTED AS SUCH WITH
 APPROPRIATE FIRE RESISTIVE SEPARATIONS NOTED ON THE
 PLAN (BOTH HORIZONTAL AND VERTICAL), FBC TABLE 508.2,
 FBC 508.3.1.
  
 8. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1. FIRE
 RATING FOR FIRE BARRIER NOT SHOWN, A1, WALL SYMBOLS.
 SPECIFY FIRE RESISTIVE RATING AND PROVIDE A DETAIL,
 FBC703.2.
  
 9. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1.4,
 PLEASE NOTE REQUIRED FIRE RESISTANCE ON WALLS WITHIN
 10FT AS WELL AS OPENINGS WITHIN THE 10FT. PROVIDE
 PRODUCT APPROVAL FOR THE FIRE RATED WINDOW AND IMPACT
 PROTECTION, FAC9B72.
  
 10. A1, PLEASE REVISE OCCUPANT LOAD, TAKING INTO
 ACCOUNT CONFERENCE ROOM AREA, SEE FBC TABLE 1004.1.1.
  
 11. THE FILE STORAGE/IT AREA IS NOTED AS A FIRE PROOF
 AREA, BUT FIRE RESISTANCE IS NOT SPECIFIED ON THE PLAN,
 SEE A1, WALL SYMBOLS. SEE OTHER COMMENTS REGARDING
 OCCUPANCY CLASSIFICATION AND REQUIRED SEPARATIONS. SHOW
 ALL REQUIRED FIRE RATINGS ON THE PLAN, BOTH HORIZONTAL
 AND VERTICAL, FBC 7.
  
 12. SHOW MANEUVERING CLEARANCE, PULL SIDE, ON THE
 FOLLOWING DOORS PER FBC FIGURE 11-25:
  
 EXEC. OFFICE 10, SOUTHEAST CORNER
 CEO OFFICE 5, NORTH DOOR
  
 13. TR 5, CEO OFFICE 5, IS TO BE ADAPTABLE,
 FBC11-4.1.3(11). SHOW BLOCKING FOR FUTURE GRAB BARS,
 TURNING RADIUS.
  
 14. JANITOR'S CLOSET SHALL BE CONSTRUCTED SO THAT
 EMPLOYEES WITH DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE AREA FBC11-4.1(3).
  
 15. STAIRS, SHOW PROTECTION FROM OVERHEAD HAZARDS, FBC
 FIGURE 11-8 (C1).
  
 16. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE,
 INCLUDING ACCESS AISLE. PLEASE INCLUDE SLOPE AND CROSS
 SLOPE. FBC FIGURE 11-10.
  
 17. TR2, 2ND FLOOR, CLEAR FLOOR SPACE FOR THE LAV
 CANNOT ENCROACH INTO THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET. FBC FIGURE 11-30E.
  
 18. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH, FAC9B72. SEE ALSO DCA DECLARATORY
 STATEMENT CONFIRMING THIS REQUIREMENT. THIS MAY BE A
 PROVISO ITEM UPON REQUEST BUT MUST BE PROVIDED PRIOR TO
 INSTALLATION.
  
 19. A3 SHOWS A BACKUP GENERATOR ON THE ROOF, S103 DOES
 NOT APPEAR TO INCLUDE THE GENERATOR. PLEASE ADDRES,
 FBC16.
  
 20. FBC13-103.1.1.1, DESIGN PROFESSIONALS RESPONSIBLE
 UNDER FLORIDA LAW FOR THE DESIGN OF THE BUILDING SHELL,
 SHALL CERTIFY COMPLIANCE OF THOSE BUILDING SYSTEMS WITH
 THE CODE BY SIGNING AND PROVIDING THEIR PROFESSIONAL
 REGISTRATION NUMBER ON THE ENERGY CODE FORM PROVIDED AS
 PART OF THE PLANS AND SPECIFICATIONS TO THE BUILDING
 DEPARTMENT.
  
 21. FOR THE MODIFIED ROOF SYSTEM, PLEASE INDICATE WHICH
 APPROVED ASSEMBLY WILL BE INSTALLED, FASTENER SELECTED,
 AND ENHANCED FASTENING SPECIFICATION IN ACCORDANCE WITH
 RAS117 (PREPARED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT); SEE GENERAL LIMITATION #7
 ON THE NOA. THIS CAN BE A PROVISO ITEM, TO BE PROVIDED
 AT TIME OF ROOF PERMIT SUBMITTAL.
  
 22. FOR THE ROOF TILE, PLEASE INDICATE METHOD OF
 ATTACHMENT. IF FOAM ADHESIVE IS PROPOSED, PLEASE
 PROVIDE PRODUCT APPROVAL FAC9B72. THIS CAN BE A PROVISO
 ITEM, TO BE PROVIDED AT TIME OF ROOF PERMIT SUBMITTAL.
  
 23. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. PLEASE SUBMIT TWO ORIGINAL SOILS REPORTS.
  
 24. ENERGY CALC SHOWS A BUILT UP ROOF, R19. PLEASE
 PROVIDE CLARIFICATION. A3 SHOWS 2" INSULATION BOARD;
 PROVIDE SPEC SHEETS FOR THE INSULATION TO SHOW THAT IT
 MEETS THE MINIMUM R19 REQUIREMENT.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-12-08 Cont ID  
Sent By dpalmer Date 2009-12-08 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2009-12-08 Time 09:21 Sent To  
Notes
2009-12-08 09:23:16GENERATOR, SITE LIGHTING AND LOW VOLTAGE UNDER SEPARATE
 PERMITS.
 LOW VOLTAGE PERMITS FOR WORK SHWON ON PLANS MAY BE TURN
 AROUND PERMITS BY REFERENCING THE MAIN PERMITTED PLANS.
 ANY ACCESS CONTROLS SHALL BE UNDER SEPRATE PERMIT AND
 PLANS MEETING NFPA-101 CHAPTER 7, 7.2.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-12-04 Cont ID  
Sent By dpalmer Date 2009-12-04 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2009-12-04 Time 09.25 Sent To  
Notes
2009-12-04 07:44:43** TEMPORARY FAILED**
  
 1) NOTE: SETS ARE MISSING PREVIOUS STAMPED SHEETS BY
 PLUMBING AND MECHANICAL REVIEWERS. CALLED AND SPOKE TO
 JESSICA FROM SISCA CONSTRUCTION. NEW SHEETS INSERTED
 WERE PLACED INTO THE ORIGINAL SETS OF DENIED PLANS AND
 NOT THE 1ST RESUBMITTED SETS OF PLANS. THERE ARE NEW
 REVISED ELECTRICAL AND MECHANICAL IN SETS DATED
 5/28/09.
 CONTRACTOR WILL BE COMING INTO OFFICE ON 12/7/09 TO
 MEET WITH THIS REVIEWER AND MAKE TWO COMPLETE SETS OF
 PLANS.
 STAMPING AND FINISHED REVIEW OF ELECTRICAL CAN NOT BE
 DONE AT THIS TIME AND WILL BE COMPLETED ON 12/7.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-09-26 Cont ID  
Sent By dpalmer Date 2009-09-26 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2009-09-26 Time 08:18 Sent To  
Notes
2009-09-26 11:13:07 
  
 ** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
 ** THERE ARE ALSO SOME NEW NOTES BASED ON PLANS
 SUBMITTED.
  
 1) NOTE: NO FIRE ALARM PLANS FOR BASE DESIGN INTENT AS
 REQUIRED PER FBC CHAPTER 9 AND FS 633 SUBMITTED.
 RESPONSE MENTIONS THAT THESE WILL BE SUBMITTED BEFORE
 PERMIT ISSUANCE. HOWEVER AS STATED ON PREVIOUS REVIEW,
 THE BASE BUILDING PLANS ARE REQUIRED TO SHOW BASE
 DESIGN INTENT REQUIRED BY THE ABOVE CODES AND OTHER
 APPLICABLE CODES SUCH AS NFPA-72.
 IF PLANS ARE NOT SUBMITTED TO COORDINATE REVIEW WITH
 THE SUBMITTED PLANS THERE COULD ALSO BE COMMENTS WHICH
 CAN NOT BE MADE AT THIS TIME.
 ** AS NOTED ON PREVIOUS REVIEW PLEASE BE SURE TO SEE
 FBC 11-4.28.1,.2 AND .3 FOR ALL MINIMUMS REQUIRED FOR
 ADA COMPLIANCE.
  
 2) NOTE: PREVIOUS NOTE #26. PLEASE SEE FS 655.962 FOR
 REQUIRED LIGHTING FOR ATM AREAS. BASED ON S-LTG SHEET
 AND OTHER PHOTO-METRICS PER FAE, THE MINIMUM LEVELS
 REQUIRED BY STATUE ARE NOT MET. SEE SECTION OF THE
 STATUE WHICH IS NOT ONLY THE LIGHTING LEVELS WITHIN
 10FT.
  
 3) NOTE: PLANS STILL INDICATE A CROSS OF WORK OVER
 PROPERTY LINES. THE REVISED PLANS HAVE REMOVED THE
 PROPERTY LINE BETWEEN BANK AND EAST PARKING LOT.
 RESPONSE FROM DESIGN TEAM STATED ONLY THE PHOTO-METRICS
 CROSSED PROPERTY LINES. HOWEVER BASED ON PREVIOUS
 SUBMITTED PLANS THERE WAS AN ADDITIONAL PROPERTY LINE
 SHOWN ON THE EAST SIDE OF BANK BETWEEN PARKING LOT AND
 BANK. SEE PREVIOUS PLANS.
 SEE COMMENTS FROM OTHER TRADES WHICH MAY AFFECT REVIEW
 AND SCOPE OF WORK.
  
 4) NOTE: ** NEW COMMENT**: THE DOOR SWING ON THE LOWER
 ELECTRICAL ROOM BETWEEN EXECUTIVE OFFICE #10 AND
 CONFERENCE ROOM #1 IS SHOWN SWINGING IN.
 THIS IS A LIFE SAFETY HAZARD. AN OCCUPANT/ELECTRICAL
 WORKING ON ONE OF THE ELECTRICAL PANELS COULD BE PUSHED
 INTO A LIVE ELECTRICAL PANEL BY THE DOOR. PLEASE SWING
 DOOR OUT.
 110.26, 90.4
  
 5) NOTE: PLEASE GO OVER SUBMITTED ENERGY CALCULATIONS.
 13-415.AB.5, 13-415.AB.2.2
 THE NUMBER OF EXTERIOR 400W SITE LIGHTING FIXTURES ON
 PLANS IS HIGHER THAN THE AMOUNT IN THE INPUT DATA
 REPORT OF THE SUBMITTED CALCULATIONS.
 THE NUMBER OF H/HE FIXTURES ON PLANS IS HIGHER.
 THE JAN CLOSET FIRST FLOOR DOES NOT INDICATE THE TYPE
 OF FIXTURE. ( ALSO NOTED ON PREVIOUS NOTE #17 FOR
 COMPLETING ALL LIGHTS ON PLANS).
 THE NUMBER OF G FIXTURES ON PLANS IS NOT CLEAR. ONLY
 ONE G IS SHOWN AT LOCATIONS IN WHICH THERE ARE MORE
 THAN 2,3 OR 4 FIXTURES.
 THE NUMBER OF 64W FIXTURES ON PLANS WHICH PER FIXTURE
 LEGEND IS K, B, BE, PE, AND G IS HIGHER THAN IDR.
  
 ** PLEASE SEE 13-415.AB.5 WHICH REFERENCES TABLE B FOR
 SPACE TYPES. 13-415.AB.5 INCLUDES *A* FOR INTERIOR
 ALLOWANCES. EVEN AS THERE MAY BE TWO ZONES, THERE ARE
 MORE THAN TWO SPACE TYPES. ALL SPACES IN BUILDING ARE
 NOTED AS BANKING. HOW IS THIS POSSIBLE WHEN THERE ARE
 OTHER SPACES? PLEASE EXPLAIN.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #12. IT IS TO BE
 NOTED THAT PLANS DO NOT MEET ASME-17 AS PREVIOUSLY
 GIVEN PER FBC AND NEC REFERENCE TO STATE ELEVATOR CODE
 REQUIREMENTS.
 RESPONSE WAS TO SEE ADDITIONAL LIGHT FIXTURE ADDED ON
 E3.03 HOWEVER THIS IS NOT THE ONLY REQUIRED ITEM PER
 ASME.
 CALL TO GO OVER THIS AS LIGHTING LEVELS IN LOCATIONS
 COVER BY THE CODE ARE NOT MEETING MINIMUMS.
  
 7) NOTE: ** NEW COMMENT? PANEL SCHEDULES DO INDICATE
 THE REQUIRED DEDICATED RECEPTACLE AND LIGHTING CIRCUITS
 PER NEC 620.22,23,24 ETC AND E3.03 DOES SHOW PIT DETAIL
 HOWEVER NO ELECTRICAL COULD BE LOCATED ON PLANS FOR
 GROUPING OF THE DISCONNECTING MEANS FOR THE REQUIRED
 DEDICATED CIRCUITS 620.53,620.54,620.51 FOR REQUIRED
 DISCONNECTS TO BE LOCATED IN ELEVATOR MACHINE/EQUIPMENT
 ROOM.
 PLEASE PROVIDE AN ENLARGED DETAIL OF BOTH THE ELEVATOR
 EQUIPMENT ROOM.
 **KEEP IN MIND AS A REFERENCED STANDARD AND CODE, NOTE
 #6 ABOVE NEEDS TO BE ADDRESSED.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #18 WITH RESPECT TO
 THE GENERATOR WHICH IS BEING PROPOSED TO BE LOCATED ON
 THE ROOF. THE RESPONSE MENTIONS THE ATS IS SERVICE
 ENTRANCE RATED THEREFORE BASICALLY IF THE ATS MAIN IS
 TURNED OFF THE INSTALLATION MEETS CODE AND IS SAFE.
  
 IF THE BUILDING IS UNDER GENERATOR POWER AND THERE IS
 AN EMERGENCY WHERE FIRE DEPARTMENT OR OTHER PERSONAL
 NEEDS TO SHUT DOWN THE POWER, THE ATS WILL ONLY SHUT
 OFF POWER TO SERVICE EQUIPMENT. THE GENERATOR IS STILL
 UNDER POWER AND STILL RUNNING. THE FEEDERS FROM THE
 GENERATOR TO THE ATS ARE ALSO STILL ENERGIZED AND
 RUNNING THROUGH THE BUILDING.
 ALL FEEDERS AND SERVICE ENTRANCE CONDUCTORS ENTERING
 AND RUNNING THROUGH THE STRUCTURE SHALL CONTAIN
 DISCONNECTING MEANS TO DE-ENERGIZE THESE CONDUCTORS.
 THE INTENT OF 230 AND 225 OF THE NEC GIVEN BELOW IS TO
 BE ABLE TO DE-ENERGIZE ALL CONDUCTORS IN A STRUCTURE.
  
 PLEASE SEE 230.70, 230.71, 230.72, 230.76 AND 230.79
 FOR SERVICE CONDUCTORS WHICH REQUIRE DISCONNECTING
 MEANS. THE DISCONNECTING MEANS SHALL BE RATED FOR THE
 LOAD SERVED AND BE ABLE TO BE DISCONNECTED EVEN UNDER
 POWER FAILURE. EVEN OTHER SYSTEMS SUCH AS BACK UP POWER
 SYSTEMS ARE REQUIRED TO HAVE DISCONNECTING MEANS TO
 SHUT OFF POWER.
 PLEASE SEE 225.31-225.39. THESE SECTIONS APPLY TO
 FEEDERS TO DETACHED STRUCTURES/BUILDINGS. EVEN AS THIS
 IS NOT A DETACHED BUILDING OR STRUCTURE THE INTENT OF
 225 IS THE SAME. THESE SAME SECTIONS WILL SHOW THE
 INTENT WHICH IS TO HAVE A DISCONNECTING MEANS TO
 DE-ENERGIZE ALL FEEDERS IN A STRUCTURE.
 **
 PLEASE SEE NEC 445.18 WHICH REQUIRES THE DISCONNECTING
 OF ALL POWER FROM THE UNIT. ALSO (1),(2),
 ** A MEANS OF DISCONNECTING THE PRIME MOVER SHALL BE
 PROVIDED. IT WAS STATED ON PREVIOUS REVIEW TO CALL FIRE
 MARSHAL AND THIS REVIEWER TO GO OVER THIS COMMENT.
 HOWEVER TO DATE NO CONTACT TO THIS REVIEWER WAS MADE.
 CONTACT WILL BE MADE TO THE FIRE MARSHAL FOR PROPOSED
 SCOPE OF WORK.
  
 ** AS NOTED PREVIOUSLY NO INFORMATION ON MOUNTING THE
 GENERATOR, LOCATION, OTHER STRUCTURAL INFORMATION COULD
 BE LOCATED ON ANY OTHER SHEETS. ME SHEET INDICATES THE
 GAS LINE UP TO ROOF HOWEVER THE S SHEETS DO NOT SHOW
 ANY DETAILS.
 IT WAS NOTED TO SEE COMMENTS FROM OTHER TRADES HOWEVER
 AS GENERATOR UNIT WAS NOT SHOWN ON OTHER PLANS IT MAY
 NOT HAVE BEEN NOTED BY THE BUILDING REVIEWER. AN E-MAIL
 HAS BEEN SENT TO BUILDING REVIEWER.
 COULD NOT LOCATE ANY MOUNTING DETAILS, CURBS, VIBRATION
 ISOLATORS ETC. SEE FBC CHAPTER 16 FOR WIND AND NFPA-110
 CHAPTER 7 FOR MOUNTING, LOCATIONS ETC
  
 9) NOTE: SPECS WERE SUBMITTED FOR THE GENERATOR UNIT.
 WILL THIS BE AN INSIDE UNIT AS NO SHEETS COULD BE
 LOCATED FOR THE WEATHER PROOF ENCLOSURE.
 110.3,90.7, FBC CHAPTER 16 ETC AS NOTED.
 ** AS NOTED PREVIOUSLY, ALL PRODUCT SPECIFICATIONS ARE
 REQUIRED TO CONTAIN *SHOP DRAWING REVIEW STAMPS* AND
 SIGNATURE BY THE DESIGNER OF RECORD.
  
 10) NOTE: PLEASE REVISE ROOF TOP ELECTRICAL PLANS. AN
 EXAMPLE IS NEW EXHAUST FANS ON ROOF HOWEVER NO
 ELECTRICAL INFORMATION COULD BE LOCATED NEXT TO UNIT.
 EF-1, EF-3, CIRCUIT NUMBERS? DISCONNECTS?
 408.4, 220,310.16, 430.102
  
  
  
 IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By dpalmer Date 2009-06-22 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 16:24 Sent To  
Notes
2009-06-22 13:49:41 
  
 ** DENIED PLANS **
  
 *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION
 NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE
 COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING ADDRESS WHICH HAS
 BEEN ASSIGNED IS NOTED ON TITLE BLOCKS ALONG WITH OTHER
 SUPPORTING DOCUMENTS SUCH AS ENERGY CALCULATIONS.
 8101 OKEECHOBEE BLVD.
 FBC 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL
 AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING.
 THE SUBMITTED PLANS CONTAIN WORK ON THREE SEPARATE
 PARCELS. IF THE THREE ARE NOT LEGALLY JOINED THEN IT IS
 NOT PERMITTED TO FEED LIGHTING FOR EXAMPLE LOCATED ON
 ANOTHER LEGAL PROPERTY FROM THE MAIN BUILDING. THIS MAY
 REQUIRE A UNITY OF TITLE OR ALL WORK ON OTHER PARCELS
 SHALL BE UNDER SEPARATE PERMITS AND REQUIRE ANY SITE
 ELECTRICAL SUCH AS SITE LIGHTING TO COME FROM MORE THAN
 ONE SERVICE.
 AS THE INTENT OF SCOPE OF WORK IS NOT YET KNOW SOME
 ASPECTS OF REVIEW WILL BE BASED ON THIS BEING ALL ONE
 LEGAL PROPERTY. SEE NOTES ON SITE LIGHTING WHICH WILL
 BE BELOW. IF UNDER SEPARATE PERMITS REVIEW FOR SOME OF
 THESE ITEMS MAY BE DISCARDED.
  
 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 CODES AT A MINIMUM. SOME ARE CURRENT AND OK ON
 ELECTRICAL PLANS HOWEVER SHEET A.1 CONTAINS REFERENCE
 TO THE 2002 NEC/ NFPA-70. PLEASE KNOW AS OF DECEMBER 8,
 2006 THE STATE OF FLORIDA ADOPTED THE 2005 NEC/NFPA-70.
 ANOTHER CODE WHICH NEEDS TO BE REFERENCE ON PLAN IS THE
 2003 NFPA-75.
 SEE NOTES BELOW WITH RESPECT TO IT ROOM AS NOTED ON
 PLANS.
 NFPA-75 2003 IS ADOPTED PER FAC 69A-3.012
 ALSO THERE ARE OTHER DESIGNS ON PLANS WITHOUT CODE
 REFERENCES SUCH AS THE GENERATOR. ( NFPA-110)
  
 2007 FBC W/ 2009 REVISIONS
 2002 NFPA-110
 2005 NFPA-70
 2006 NFPA-101
 2003 NFPA-75
 2002 NFPA-72
  
 ** THESE ARE CODES REQUIRED BY THE ELECTRICAL REVIEW AT
 THIS TIME. SOME ARE NOTED AS THEY EXIST ON PLANS.
  
  
 4) NOTE: LANDSCAPE ARCHITECT: PLEASE SEE FLORIDA
 STATUTES 481.319 FOR REQUIRED CERTIFICATE OF
 AUTHORIZATION. PLEASE CONFIRM WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 ** PLEASE ALSO BE SURE TO COORDINATE ALL SITE LIGHTING
 WITH THE MEP DESIGN TEAM AND SEE COMMENTS ABOVE WITH
 RESPECT TO SEPARATE LEGAL PROPERTIES. THERE ARE
 CONFLICTS ON LANDSCAPE PLANS COMPARED TO ELECTRICAL
 SHEETS.
  
 5) NOTE: PLEASE SUBMIT A COMPLETE SET OF PLANS. THE
 PLANS MAKE NOTE AND REFERENCES TO FIRE ALARMS PLANS
 HOWEVER NO FA SHEETS COULD BE LOCATED IN THE SUBMITTED
 SETS. THE PLANS STATE FIRE ALARM SYSTEM BY OTHERS
 HOWEVER IF THE FA IS A REQUIRED SYSTEM THEN THE BASE
 DESIGN MUST BE SHOWN AT THIS TIME.
 PLEASE SEE FS 633 AS ALL BASE BUILDING PLANS SHOWING
 MINIMUM DESIGNS FOR FIRE AND LIFE SAFETY SHALL BE PART
 OF THE BASE BUILDING DESIGN INTENT.
  
 6) NOTE: AS NOTED FOR COMMENT #4 ABOVE, IF THERE IS A
 FIRE ALARM SYSTEM PLEASE BE SURE TO SEE FBC
 11-4.28.1,.2 AND .3 FOR MINIMUM HEIGHTS, LEVELS,
 LOCATIONS ETC FOR ADA COMPLIANCE.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS. THE GENERATOR WILL BE
 UNDER A SEPARATE PERMIT HOWEVER IT IS VERY IMPORTANT TO
 SEE COMMENTS BELOW WITH RESPECT TO THE LOCATION OF THE
 UNIT AND THE NG LINE IN THE BUILDING.
 THE SPECS FOR THE ATS ARE REQUIRED AT THIS TIME AS IT
 NOTES BEING SERVICE ENTRANCE RATED AND ONE OF THE
 MAINS. THERE WILL BE COMMENTS BELOW WITH RESPECT TO
 FEEDERS AND SHUT DOWN OF POWER.
 ** IF A PRODUCT IS NOT KNOWN THEN PLEASE PROVIDE SPECS
 ON A CODE COMPLIANT ITEM AT THIS TIME. 110.3,90.7,
 230.70,71, ETC
 THE PRODUCT MAY ALWAYS BE REVISED AT A LATER DATE.
  
 8) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN
 COMPLIANCE WITH THE FBC CHAPTER 13. THE FOLLOWING WILL
 BE NOTED FOR EXAMPLES OF NONE COMPLIANCE AND IS **
 NOT** ALL POSSIBLE ITEMS. THE INPUT DATE REPORT WILL BE
 NOTED AS IDR.
 AS THE FIXTURE LEGEND IS NOT YET COMPLETE THERE ARE
 ITEMS WHICH CAN NOT BE CONFIRMED AS BEING CODE
 COMPLIANT AT THIS TIME.
 13-415.AB.5. PLEASE ALSO NOTE, IT IS NOT PERMITTED TO
 USE MORE THAN ONE METHOD FOR CALCULATIONS.
  
 FOR EXAMPLE: PLEASE COORDINATE ALL EXTERIOR LIGHTING ON
 PLANS WITH THE IDR. THE IDR ONLY INDICATES TWO TYPES OF
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS CONTAIN
 MANY OTHER FIXTURES. WHERE ARE ALL THE SITE LIGHTING
 FIXTURES WHICH ARE SHOWN AS 400W MH?
  
 FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTS ON THE PLANS
 ARE NOTED AS METHOD *B* YET A METHOD *A* FLA-COM WAS
 SUBMITTED. THERE IS A LARGE DESIGN INCONSISTENCY.
 THE TOTAL WATTAGE ON THE FLA-COM INTERIOR IS IN EXCESS
 OF 18,000 WATTS YET THE PLANS STATE THE TOTAL INTERIOR
 DESIGN WATTAGE IS LESS THAN 7000WATTS. HOW IS THIS
 POSSIBLE?
 THE PLANS CONTAIN FIXTURES AND WATTAGE TYPE NOT ON THE
 IDR. PLEASE BE SURE TO GO OVER PLANS FOR ALL FIXTURES.
 ANOTHER EXAMPLE ON THE INTERIOR LIGHTING IS THE *J*
 FIXTURE. THE PLANS AND THE FIXTURE LEGEND CONTAIN
 REFERENCES TO THE FUTURE FIXTURE HOWEVER THERE IS NO
 ALLOWANCE FIGURED INTO THE SPACE BY SPACE ON PLANS OR
 THE IDR OF THE FLA-COM REPORT.
  
 FOR EXAMPLE: PLEASE SEE THE NOTES BELOW FOR WATER
 HEATERS/ LOADS. THE EXAMPLE HOWEVER FOR CHAPTER 13
 COMPLIANCE IS THE FACT THE IDR IS COMPLETELY BLANK
 UNDER *PIPING*. THE BUILDING CONTAINS ELECTRICAL HWH
 WHICH THEN ALSO CONTAIN PIPING FOR HOT WATER. PLEASE
 SEE SECTION 13-411.AB.2.
  
 ** THESE ARE A FEW EXAMPLES ONLY. THERE ARE OTHERS,
 PLEASE GO OVER ALL COMPONENTS AND SEE POSSIBLE COMMENTS
 FROM OTHER TRADES FOR ITEMS SUCH AS ROOFING
 INSULATIONS.
  
 9) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR
 WORST CASE FEEDERS AND WORST CASE BRANCH CIRCUITS.
 PLEASE SEE 13-413.AB.1.1, .1.2
  
 10) NOTE: PLEASE SEE NOTE #2 ON SHEET E3.03 WHICH
 STATES CONDUCTORS #10 AND SMALLER SHALL BE THHN AND
 LARGER THAN #1 TO BE THWN. PLEASE BE AWARE THAT THE
 SITE LIGHTING FOR EXAMPLE INDICATES CONDUCTORS TO BE
 #10. DEPENDING ON COMMENT #9 ABOVE THIS MAY CHANGE
 HOWEVER BASED ON NOTES AND PANEL SCHEDULE IF #10 AWG
 CONDUCTORS ARE INSTALLED TO SITE LIGHTING THE PLANS DO
 NOT STATE THEY NEED TO BE THWN.
 PLEASE SEE LISTING FOR THHN AND THWN. THE W IS FOR WET
 LOCATIONS, ALL UNDERGROUND PIPING AND WIRING TO SITE
 LIGHTING IS CONSIDERED A WET LOCATION. THIS IS VERY
 SPECIFIC IN THE NEC.
 THEREFORE ALL CONDUCTORS INCLUDING THOSE SMALL THAN #10
 IN WET LOCATIONS SHALL BE RATED AS SUCH. THWN IS ONLY
 ONE CHOICE.
 110.3, 300.5, 310.9, 310.8B ETC.
  
 11) NOTE: PLEASE SUBMIT PHOTO-METRICS SHOWING MINIMUM
 LEVELS FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY
 CONDITIONS. PLEASE SEE NFPA-101 7.8.1.3 AS THE STAIR
 LEVELS NEED TO MEET 10FT CANDLES UNDER NORMAL AND IS
 PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS.
 PLEASE KNOW THAT ROOMS SUCH AS THE MAIN ELECTRICAL ROOM
 AND ELEVATOR EQUIPMENT ROOM SHALL CONTAIN BATTERY BACK
 UP FIXTURES OF SOME KIND. 700.12F, 700.16.
 THIS NEEDS TO COORDINATE WITH COMMENT #17 BELOW.
  
 12) NOTE: PLEASE SEE NEC AND FBC WHICH BOTH MAKE
 REFERENCE TO ASME-17 2004 FOR ELEVATOR CODES. THIS
 OFFICE DOES NOT REVIEW FOR CODE COMPLIANCE FOR ASME
 HOWEVER IT SHOULD BE NOTED THAT FOR INFORMATION THERE
 ARE SOME ITEMS ON PLANS WHICH DO NOT MEET MINIMUM ASME
 CODES. THERE WILL BE SOME ITEMS NOTED BELOW IN OTHER
 COMMENTS FOR NEC/ FBC REQUIREMENTS HOWEVER THESE ARE
 FOR INFORMATION ONLY.
 THE INTENT IS TO PROVIDE INFORMATION WHICH MAY HELP TO
 NOT DELAY THE PROJECT WHEN IT COMES TIME FOR ELEVATOR
 INSPECTIONS.
  
 ** PLEASE CHECK THE ELEVATOR PIT LIGHTING REQUIREMENTS,
 THE SINGLE FIXTURE SHOWN MOST LIKELY DOES NOT GIVE THE
 NEW LEVELS REQUIRED FOR FT CANDLES IN PIT. ( 10FT
 CANDLES MIN)
 ** PLEASE CHECK THE LIGHTING AT SILLS/LANDINGS IN
 HALLWAYS, 10FT CANDLES MINIMUM.
 ** PLEASE CHECK LIGHTING IN ELEVATOR EQUIPMENT ROOMS.
 19 FT CANDLES MINIMUM.
  
 13) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING.
 THERE ARE SOME ITEMS ON PLANS WHICH DO NOT SHOW
 CIRCUITING AT THIS TIME. PLEASE SEE CORRIDOR #4, EXIT
 SIGN, PLEASE SEE LIGHTING IN ELEVATOR EQUIPMENT ROOM
 AND MAIN ELECTRICAL ROOM.
 PANELS SCHEDULE SHALL ALSO BE SPECIFIC. MAY NOTA STATE
 *LIGHTING OR RECEPTACLES* IN GENERAL. MAY USE ALPHA OR
 NUMERIC DESIGNATIONS. IT WOULD BE *LIGHTING
 101,102,103* ETC.
 408.4, 310.16, 220.12,220.42
 THESE ARE A FEW EXAMPLES
  
 14) NOTE: PLEASE SEE NEC 620.23 FOR REQUIRED DEDICATED
 CIRCUIT FOR ROOM LIGHTING.
  
 15) NOTE: PLEASE PROVIDE CLARITY FOR THE SYSTEM WHICH
 IS GOING TO FEED THE ELEVATOR EQUIPMENT ROOM. PER FBC
 3006.2 WHICH REQUIRES A DEDICATED SYSTEM. SHEET E1.02
 STATES TO SEE ME1.01 FOR UNIT TO BE FED FROM CONDENSING
 UNIT. HOWEVER ME1.01 SHOWS MORE THAN ONE CU.
 THE SYSTEM SHALL BE DEDICATED. PANEL SCHEDULE IS NOT
 SPECIFIC.
 408.4, 310.16, 220 ETC LOADS AND OTHER ITEMS NEED TO BE
 DETERMINED.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 16) NOTE: PLEASE SHOW A SYSTEM IN COMPLIANCE WITH FBC
 CHAPTER 13, 13-415.AB.1.1,.1.2, .1.3 AND .1.4. THE
 PLANS CONTAIN MANY NOTES THAT A SYSTEM NOTES AS TIMED
 SCHEDULING IS TO BE PROVIDED HOWEVER NO SYSTEM IS
 SHOWN.
 NEED TO SHOW SYSTEM.
 NEED TO SHOW ZONES FOR AREAS OVER SQ FT PERMITTED.
 NEED TO SHOW SYSTEM FOR EACH FLOOR AS THE CODE DOES NOT
 PERMIT A SINGLE CONTROL FEEDING MORE THAN ONE FLOOR.
 NEED TO SHOW LOCATIONS OF ALL OVER RIDES AND/OR
 ALTERNATE LOCATIONS MEETING EXCEPTIONS FOR PILOT
 LIGHTS.
 PLEASE BE SURE TO INCLUDE TIME FOR BACK UP OF EXTERIOR
 PROGRAMMING ON ASTRONOMICAL TIME CLOCK.
 SEE NOTES FOR OTHER FIXTURES WHICH PER PLANS ONLY SHOW
 A SINGLE POLE SWITCH FOR CONTROL. BREAK ROOM FOR
 EXAMPLE INDICATES SOME SORT OF FIXTURE YET NO CONTROLS
 FOR AUTOMATIC SHUT OFF AS REQUIRED PER
 13-415.AB.1.1,.1.3 AND *BREAK ROOMS* UNDER .1.2.
  
 ** THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED
 FOR CODE COMPLIANCE. SEE NOTES FOR FIXTURES ALSO.
  
 17) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS AND
 COMPLETE A FIXTURE LEGEND SHOWING MINIMUM CODE
 COMPLIANCE AT THIS TIME.
 FOR EXAMPLE: SD FIXTURES ON PLANS YET NOTHING ON
 FIXTURE LEGEND.
 FOR EXAMPLE: FIXTURE DL IS NOTED AS BEING 208V, YET THE
 PLANS INDICATE THIS CIRCUITED TO A 277/480V PANEL.
 FOR EXAMPLE: ONE OF THE ITEMS WHICH IS CONFUSING IS THE
 *R* IN THE SMALL CIRCLE ON PLANS LOCATED AT MANY OF THE
 FIXTURES. THE SYMBOL LEGEND DOES NOT LIST THIS ITEM.
 THE *R* IS LOCATED NEXT TO NUMEROUS RECESSED TYPE
 FIXTURES SO ONE WOULD ASSUME THAT PERHAPS THIS WAS FOR
 RECESSED LIGHTS. HOWEVER PLEASE SEE THE BREAK ROOM FOR
 EXAMPLE AS ONE LOCATION WHICH INDICATES LIGHTING
 FIXTURES AS *R* WITH NO OTHER DESIGNATION. IS *R* A
 FIXTURE TYPE ? OR SOME OTHER DESIGNATION.
 REVIEW FOR ITEMS SUCH AS LIGHTING PERFORMANCE
 CALCULATIONS, REQUIRED CONTROLS, LOAD CALCULATIONS,
 CIRCUITING ETC CAN NOT BE DETERMINED AT THIS TIME.
  
 ** THERE ARE MORE ITEMS, PLEASE COMPLETE ALL FIXTURES
 AND COORDINATE ALL.
  
 18) NOTE: PLEASE EXPLAIN HOW THE POWER FROM THE
 GENERATOR WILL BE SHUT DOWN IN AN EMERGENCY. THE MAINS
 ARE TURNED OFF BY FIRE PERSONNEL, THE GENERATOR WILL
 AUTOMATICALLY TURN ON PLACING HOT 277/480V FEEDERS
 INSIDE THE BUILDING TO MANY PANELS.
 PLEASE KEEP IN MIND THAT ALL DISCONNECTING MEANS SHALL
 BE RATED FOR LOAD SERVED PER 230.76,230.79.
 PLEASE GO OVER LOCATION OF UNIT WITH ALL TRADES
 INCLUDING FIRE MARSHAL.
 PLEASE SEE 445.18, AS THE FUEL SOURCE SHALL BE SHUT
 DOWN AND IN CLOSE PROXIMITY TO THE MAIN ELECTRICAL
 ROOM. PLANS WOULD ALSO CONTAIN THE GAS LINE INSIDE THE
 BUILDING.
 THERE ARE SEVERAL ITEMS WHICH COULD CREATE A LIFE
 SAFETY AND FIRE HAZARD AS THE GENERATOR WOULD STILL RUN
 AFTER TURNING OFF MAINS.
 ** PLEASE CALL TO GO OVER AND PLEASE CONTACT THE FIRE
 MARSHAL.
 PLEASE SEE NFPA-110 FOR LOCATIONS PER CHAPTER 7.
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO THE 100KW GENERATOR SHOWN ON SOME PLANS HOWEVER NO
 SPECIFIC STRUCTURAL DETAILS ON ROOF LOADS ETC ARE
 SHOWN.
  
 19) NOTE: PLEASE BE SURE TO STATE ON PLANS THAT THE
 BACK UP SYSTEM PROVIDED IS AN * OPTIONAL STAND-BY
 SYSTEM* ONLY. 702, 700, 701
 FBC 106.1.1 FOR CLARITY AND INFORMATION ON PLANS.
  
 20) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2
 WHICH REQUIRES ALL OCCUPANCY SENSORS TO BE OF FAIL SAFE
 TYPE FOR ANY LIGHTING WHICH IS PART OF THE REQUIRED
 EGRESS.
 THE PLANS SHOW THAT LIGHTING IN AREAS SUCH AS STAIRS
 AND OTHER LOCATIONS MAY OR MAY NOT BE THROUGH THE
 LIGHTING CONTROL PANEL. WHAT IS THE DESIGN INTENT?
 PLEASE SEE 13-415.AB.1 FOR CHAPTER 13 COMPLIANCE AS
 WELL AS SECTIONS NOTED ABOVE.
 ARE THERE GOING TO BE PROPOSED NIGHT LIGHTS? IF SO
 PLEASE SHOW ON PLANS.
 PLEASE KEEP IN MIND NOT ALL FIXTURES WILL BE CONSIDERED
 NIGHT LIGHTS.
  
 21) NOTE: PLEASE SEE 2003 NFPA-75 AND 2005 NEC FOR IT
 ROOM. THIS REQUIRES SEPARATION FROM OTHER AREAS. PLANS
 SHOW FILE/STORAGE AREA AS PART OF THE SEPARATED AREA.
 PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT ROOM. IF
 THIS IS INDEED AS IT ROOM AS DEFINED IN 645.4 AND
 NFPA-75 THEN ALL THE ITEMS IN 645.4 ( 1-5) MUST BE MET.
 FOR EXAMPLE: 645.10 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL ELECTRICAL FEEDING EQUIPMENT ALONG WITH AIR
 CONDITIONING EQUIPMENT.
 IF THIS IS NOT GOING TO BE AN IT ROOM, THEN NO WIRING
 METHODS PER NEC 645 ARE PERMITTED IN THIS LOCATION.
 PLEASE PLACE NOTES ON PLANS ACCORDINGLY.
  
 22) NOTE: PLEASE SEE FBC 1020.1.1,.1.2 WHICH UNDER THE
 2004 FBC WAS SECTION 1019. OTHER SYSTEMS SUCH AS
 SECURITY SYSTEMS WHICH ARE NOTED ON PLANS ARE NOT
 PERMITTED IN THE STAIRWAYS.
 PLANS INDICATE RECEPTACLES ALONG WITH A NOTE #14 FOR
 SECURITY SYSTEM/OTHER DEVICES TO BE LOCATED IN STAIRS.
 THIS IS NOT PERMITTED.
 ONLY SYSTEMS PERTAINING TO THE STAIR AND EXIT ENCLOSURE
 WHICH ARE A REQUIRED SYSTEM.
  
 23) NOTE: NOTED, LOW VOLTAGE SYSTEMS SUCH AS PHONE,
 CATV, ACCESS CONTROLS ETC SHALL BE UNDER SEPARATE
 PERMIT(S) ALONG WITH THE SITE LIGHTING, GENERATOR AND
 OTHERS AS NOTED BY TRADES.
  
 24) NOTE: PLEASE SEE 250.6,250.24 ETC. THE RISER
 INDICATES *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE
 FIRST MEANS OF DISCONNECT. THIS IS NOT PERMITTED. AS
 THE FIRST MEANS OF DISCONNECT IS REQUIRED TO BE BONDED
 TO THE GROUNDED CONDUCTOR, AS SHOWN THIS WOULD PARALLEL
 THE NEUTRAL (GROUNDED ) CONDUCTOR THUS CREATING
 OBJECTIONABLE CURRENTS.
 PLEASE CALL TO GO OVER IF NEEDED.
  
 25) NOTE: PLEASE KNOW THAT SIGNED, DATED AND SEALED
 WIND LOAD CALCULATIONS WILL BE REQUIRED FOR SITE
 LIGHTING POLES. ALL CALCULATIONS SHALL INCLUDE THE EPA
 ( EFFECTIVE PROJECTED AREA) OF FIXTURES.
 * THIS MAY BE PART OF THE PERMIT FOR SITE LIGHTING.
  
 26) NOTE: PLEASE SHOW THE PHOTO-METRIC LEVELS FOR ALL
 AREAS SURROUNDING THE ATM ( AUTOMATED TELLER MACHINES)
 PER FS 655.962.
  
 27) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN
 PER 422.13. PLEASE SEE 2005 NEC HANDBOOK AS ELECTRIC
 STORAGE TYPE WATER HEATERS ARE NOW CONSIDERED
 CONTINUOUS LOADS. THESE SHALL BE FIGURED INTO SERVICES
 AND FEEDERS AT 125%.
  
 28) NOTE: PLEASE SEE 422.11, 422.13. SECTION 422.13
 REQUIRES THE MINIMUM OVER CURRENT PROTECTION TO BE
 FIGURED AT 125%. HOWEVER 422.11 REQUIRES THE MAXIMUM
 OVER CURRENT PROTECTION TO BE 150%.
 BASED ON THE PANEL SCHEDULES THE WATER HEATERS ARE BOTH
 SHOWN AS 4.5KW UNITS ON 277480V PANELS. THE OCP SHOWN
 IS TOO HIGH. THE 30AMP OCP WOULD BE OK IF THESE WERE ON
 A 208, OR 240V SYSTEM.
  
 29) NOTE: PLEASE KNOW: ANY AND ALL PRODUCT APPROVAL AND
 SPECS SHOULD CONTAIN *SHOP DRAWING* REVIEW STAMPS ON
 THE COVER SHEETS. THE PLANS AND DOCUMENTS ARE SCANNED
 FOR FILE STORAGE HOWEVER THE BACK OF SHEETS AND
 DOCUMENTS WHICH ARE ESSENTIALLY BLANK ARE NOT SCANNED.
 EVEN IF THESE BACK OF DOCUMENTS WERE SCANNED, THE STAMP
 AND SIGNATURE WOULD BE ON BLANK SHEETS.
 ** PRODUCT APPROVALS
 ** SPEC SHEETS
 ETC.
  
 30) NOTE: PER BUILDING OFFICIAL, ONE SET OR MORE OF
 SUBMITTED PLANS/DOCUMENTS MAY BE RETAINED BY THIS
 OFFICE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2010-01-28 Cont ID  
Sent By efabian Date 2010-01-28 Time 14:09 Rev Time 0.00
Received By efabian Date 2010-01-28 Time 14:09 Sent To  
Notes
2010-01-28 14:10:14PASSED - REFERENCE ENG REVIEW - 2

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2009-10-13 Cont ID  
Sent By efabian Date 2009-10-13 Time 14:22 Rev Time 0.50
Received By efabian Date 2009-10-13 Time 13:56 Sent To  
Notes
2009-10-13 14:21:36FAILED
  
 1. PLEASE PROVIDE 40 SCALE PLANS OF THE TWO PROPOSED
 FUTURE CONNECTIONS SHOWN (WEST OF PROPOSED BANK) ON
 MASTER PLAN SHEET 2
  
 2. LOCATION OF PROPOSED 4" DDCV TO BANK BUILDING SHOULD
 BE AT PROPERTY LINE NEAREST TO TAP AND NOT ADJACENT TO
 BUILDING AS SHOWN.
  
 3. PLEASE PROVIDE DOCUMENTS PREVIOUSLY REQUESTED FROM
 7-21-2009 PLAN REVIEW-COMMENTS.
  
 PLAN REVIEWER:
  
 EMERY P. FABIAN
 PROJECT COORDINATOR, ENGINEERING SERVICES
 494-1078
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-07-21 Cont ID  
Sent By efabian Date 2009-07-21 Time 09:34 Rev Time 0.00
Received By efabian Date 2009-07-21 Time 09:33 Sent To  
Notes
2009-07-21 09:52:28FAILED
  
 THE CURRENT CIVIL ENGINEERING PLANS OF THIS PLANS SET
 WERE SUBMITTED CONCURRENTLY AND TOGETHER WITH THE
 BUILDING PLANS 2 MONTHS AGO. PLAN REVIEW BY ENGINEERING
 SERVICES (ES) IS PENDING A FORMAL SUBMITTAL TO
 ENGINEERING SERVICES (ES), WHICH SHALL INCLUDE ALL
 PERTINENT (ES) DOCUMENTS/APPLICATION AND (ES) FEES
 PRIOR TO PLAN REVIEW. THE ENGINEER OF RECORD (EOR) HAS
 ACKNOWLEDGED AND CONFIRMED THIS AS PENDING, AND A CIVIL
 PLANS - PLAN REVIEW SHALL FOLLOW ONCE (EOR) HAS
 SATISFIED THESE REQUIREMENTS.
  
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status P Date 2009-12-30 Cont ID  
Sent By efabian Date 2009-12-30 Time 09:32 Rev Time 3.00
Received By efabian Date 2009-12-30 Time 09:32 Sent To  
Notes
2009-12-30 10:18:55FORMAL SUBMITTAL ACCEPTED AND PASSED
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION REQUIRED FOR
 SITE DEVELOPMENT APPROVAL PRIOR TO COMMENCEMENT OF SITE
 WORK:
  
 1. A COPY OF PERMIT ISSUED BY SOUTH FLORIDA WATER
 MANAGEMENT DISTRICT (SFWMD) AND
  
 2. COPY OF GEOTECHNICAL REPORT INCLUDING STORM WATER
 QUALITY CALCULATIONS AND
  
 3. FDEP NOTICE OF INTENT (NOI) FORM 62-621.300(4)(B)
 AND
  
 4. APPROVED MATERIALS LIST (AML) PER CWPB ENGINEERING
 SERVICES AND SHOP DRAWINGS
  
 5. EROSION CONTROL AND LAND STABILIZATION BOND PER
 ORDINANCE 4060-07 AS IT PERTAINS TO THE EPA'S STORM
 WATER POLLUTION PREVENTION PLAN'S (SWPPP) GUIDELINES.
 THE BOND AMOUNT SHALL BE AT A RATE OF 110% OF THE TOTAL
 OF THE SITE DEVELOPMENT PORTION OF THE CERTIFIED COST
 ESTIMATE PROVIDED BY THE PROJECT CIVIL ENGINEER.
  
 TYPE OF SURETY BONDS ACCEPTED ARE A.) LETTER OF CREDIT
 B.) BOND ISSUED BY A FLORIDA CERTIFIED SURETY COMPANY
 C.) CERTIFIED BANK OR FINANCIAL INSTITUTION CHECK.
  
 THESE ITEMS ARE REQUIRED PRIOR TO THE TIME OF A
 SCHEDULED AND CONFIRMED PRECONSTRUCTION MEETING WITH
 ENGINEERING SERVICES AND CONTINGENT UPON APPROVAL OF
 COMMENCEMENT OF ANY SITE DEVELOPMENT WORK.
  
 PLEASE ADDRESS ANY QUESTIONS TO THE PLAN REVIEWER
 BELOW:
  
 EMERY P. FABIAN
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-822-1200
 FAX: 561-494-1116
 EMAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-12-18 Cont ID  
Sent By mawillia Date 2009-12-18 Time 15:33 Rev Time 0.00
Received By mawillia Date 2009-12-18 Time 14:26 Sent To  
Notes
2009-12-18 15:33:12*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS AS FOLLOWS: WATER & SEWER
 (3 & 7), A.1, A.3, A.5, A.6, A.7, A.11, E2.01 & E2.02,
 FA1.01 & FA1.02, AND RED-LINED FS1, FS2, & FS3 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-10-08 Cont ID  
Sent By mcarsill Date 2009-10-08 Time 16:37 Rev Time 0.00
Received By mcarsill Date 2009-10-08 Time 16:26 Sent To  
Notes
2009-10-08 16:37:52 
 1. ACCORDING TO THE PLANS, THE GENERATOR WILL BE
 SUBMITTED UNDER A SEPARATE PERMIT. HOWEVER THERE
 APPEARS TO BE SOME CODE RELATED ISSUES RELATED TO THE
 GENERATOR INSTALLATION ON THE ROOF. PLEASE ARRANGE A
 MEETING WITH THIS OFFICE, THE ELECTRICAL PLAN REVIEWER,
 AND OTHER ASSOCIATED PARTIES.
  
 2. THE EXISTING DRIVEWAY LOCATED AJACENT TO THE FIRE
 STATION CANNOT BE IMPACTED. EMERGENCY RESPONSE VEHICLES
 MUST BE ABLE TO ENTER AND EXIT THE STATION FOR ROUTINE
 AND EMERGENCY TRAFFIC. PLEASE CONTACT JEFF HALVERSON
 WITH THE CITY OF WEST PALM BEACH WITH REGARDS TO
 DEMOLITION OF ANY CURBS, STREET, DRIVEWAY, ETC,
 DIRECTLY INFRONT OF THE FIRE STATION BAYS.
  
 3. FIRE SPRINKLER DESIGN INFORMATION DRAWINGS ARE STILL
 NEEDED WITH THE PLAN SUBMITTAL. SEPARATE PLANS AND
 PERMITS REQUIRED FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEM INSTALLATION.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By mcarsill Date 2009-07-20 Time 07:30 Rev Time 0.00
Received By mcarsill Date 2009-07-20 Time 07:20 Sent To  
Notes
2009-07-20 07:30:19PB COMMUNITY BANK-NEW CORPORATE OFFICE AT OAKTON
 COMMONS
  
 1. ALL CONSTRUCTION, DEMOLITION AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. BUILDING ADRESS REQUIRED. BUILDING ADDRESS IS TO BE
 A MINIMUM OF AT LEAST 6" HIGH AND 1" WIDE THAT
 CONTRASTS TO THE BACKGROUND IT IS PLACED.
  
 3. SUITABLE ACCESS LANES AND RAODS SHALL BE PROVIDED
 DURING CONSTRUCTION.
  
 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO, DURING,
 AND AFTER CONSTRUCTION.
  
 5. SUITABLE EXITS ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 6. ELECTRICAL EQUIPMENT SHOWN IN STAIRS NOT RELATED TO
 EMERGENCY EQUIPMENT IS NOT PERMITTED.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM.
  
 8. NO FIRE SPRINKLER DRAWINGS PROVIDED. PLEASE PROVIDE
 FIRE SPRINKLER SYSTEM DRAWINGS. SEPARATE SHOP DRAWINGS
 WILL BE REQUIRED PRIOR TO INSTALLATION.
  
 9. FIRE DAMPERS TO BE DROP TESTED AFTER INSTALLATION.
  
 10. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 11. MANY KNOX-BOXES ARE SHOWN. USUALLY ONLY ONE
 KNOX-BOX IS REQUIRED.
  
 12. ANY ELECTRONIC LOCKING DEVICES SHALL COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS PER CHAPTER 7 OF THE
 FLORIDA FIRE PREVENTION CODE.
  
 13. A DIRECTIONAL EXIT SIGN APPEARS TO BE NEEDED AT
 INTERSECTION OF CORRIDOR 1 AND HALL 2.
  
 14. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING
 PARTITION.
  
 15. PLEASE PROVIDE PRESCRITPIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 16. LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT SPRINKLER CONNECTION. APPLICATIONS CAN BE
 OBTAINED FROM FIRE RESCUE.
  
 17. THE MONITORING OF THE FIRE SPRINKLER SYSTEM AND ANY
 FIRE ALARM EQUIPMENT SHALL BE PERFORMED BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 18. FIRE EXTINGUISHER TRAINING IS REQUIRED FOR
 DESIGNATED EMPLOYEES.
  
 19. SOFFITTS SHALL NOT INTERFERE WITH THE OPERATION OF
 ANY FIRE SPRIINKLER HEADS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4724 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-12-14 Cont ID  
Sent By kstevens Date 2009-12-14 Time 06:43 Rev Time 0.00
Received By kstevens Date 2009-12-14 Time 06:43 Sent To  
Notes
2009-12-14 06:44:57REVISION REQUIRED...
 PASSED/PROVISO:
 1-1/2" PIPE REQUIRED PER TABLES 402.4(3) & 402.4(22).
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 16:46 Rev Time 0.00
Received By kstevens Date 2009-09-24 Time 18:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By kstevens Date 2009-06-29 Time 09:00 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 09:00 Sent To  
Notes
2009-06-29 09:03:45DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 REQUIRED INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. - THE CORRESPONDING LENGHTS SHALL
 BE INDICATED TO VERIFY DISTANCE TO THE MOST REMOTE
 OUTLET.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-19 Cont ID  
Sent By lmartine Date 2009-11-17 Time 09:25 Rev Time 0.00
Received By lmartine Date 2009-11-17 Time 09:25 Sent To  
Notes
2009-12-01 16:55:2112/1/09 SUBMITTED REQUEST FOR EXPEDITED REVIEW
 ***********************EXPEDITED***********************
 ***
2009-11-19 09:28:19C--30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-17 Time 14:22 Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 14:22 Sent To  
Notes
2009-09-24 17:16:58PROVIDED 'EXPEDITED' REQUEST 9/24/09
2009-09-22 14:24:09C-17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-20 Cont ID  
Sent By rbrown Date 2009-07-20 Time 10:43 Rev Time 0.00
Received By rbrown Date 2009-06-04 Time 11:37 Sent To  
Notes
2009-07-20 11:32:277/20/09 REMOVED FROM COMMERCIAL PLAN TRACKING BOARD
 SLOT # C30 AND ROUTED TO EMERY FOR ENGINEERING SERVICES
 DEPT REVIEW. RB
  
2009-06-05 11:37:43C-30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2010-02-01 Cont ID  
Sent By shill Date 2010-02-01 Time 11:26 Rev Time 0.00
Received By shill Date 2010-02-01 Time 11:26 Sent To  
Notes
2010-02-01 11:29:54TRACKING # MU-2010-001612-0000
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2010-01-28 Cont ID  
Sent By rbrown Date 2010-01-28 Time 17:03 Rev Time 0.00
Received By rbrown Date 2010-01-28 Time 17:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2009-12-23 Cont ID  
Sent By shill Date 2009-12-23 Time 13:27 Rev Time 0.00
Received By shill Date 2009-12-23 Time 13:27 Sent To  
Notes
2009-12-23 13:28:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-09-26 Cont ID  
Sent By dpalmer Date 2009-06-26 Time 11:06 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-09-26 11:07:36FAILED AS NO IMPACT FEES HAVE BEEN PAID TO DATE,PLANS
 NOT STAMPED.
 REVIEW ENTERED FOR BUILDING REVIEWER.

Review Stop L LANDSCAPING
Rev No 4 Status N Date 2010-01-28 Cont ID  
Sent By eschneid Date 2010-01-28 Time 16:48 Rev Time 0.00
Received By eschneid Date 2010-01-28 Time 16:48 Sent To  
Notes
2010-01-28 16:49:06SEPARATE LANDSCAPE PERMIT SUBMITTED.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2009-12-09 Cont ID  
Sent By rkussner Date 2009-12-09 Time 10:46 Rev Time 0.00
Received By rkussner Date 2009-12-09 Time 10:46 Sent To  
Notes
2009-12-09 10:49:58***LANDSCAPE REVEIW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PLEASE ADDRESS ZONING COMMENTS.
  
 2. THE LANDSCAPE PLAN SUBMITTED FOR THE MINOR AMENDMENT
 SHALL BE CONSISTENT THE PLAN SUBMITTED FOR THE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-09-30 Cont ID  
Sent By rkussner Date 2009-09-30 Time 17:04 Rev Time 0.00
Received By rkussner Date 2009-09-30 Time 17:04 Sent To  
Notes
2009-09-30 17:16:06PALM BEACH COMMUNITY BANK
 LANDSCAPE COMMENTS
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. BALD CYPRESS (TD) IS A HARDIER TREE SPECIES THAN THE
 NEWLY PROPOSED LAUREL OAK (QL). PLEASE SWITCH BACK TO
 WHAT WAS PREVIOUSLY PROPOSED.
  
 2. LANDSCAPING SHALL BE ADDED ON BOTH SIDES OF THE
 ENTRY ROAD. THE ADDITION OF SIX (6)) LIGHTED ROYAL
 PALMS (THREE (3) ON THE WEST SIDE AND THREE (3) ON THE
 EAST SIDE) WOULD ENHANCE THE ENTIRE PROJECT. THE
 LANDSCAPE AREA BETWEEN THE HEDGE AND CURB ON THE EAST
 SIDE SHALL BE PLANTED WITH SHRUBS AND GROUND COVER
 CONSISTENT WITH WHAT IS PROPOSED ON THE WEST SIDE OF
 THE ENTRY ROAD.
  
 3. THERE APPEARS TO BE SOME CONFLICTS BETWEEN STREET
 LIGHTS AND PROPOSED TREES. THE STREET LIGHTS SHALL BE
 CENTERED BETWEEN THE TREES TO AVOID CONFLICTS.
  
 4. THE DWARF OLEANDER IS A TROUBLESOME PLANT. IT IS
 PRONE TO VARIOUS INSECTS AND DISEASE. PLEASE CONSIDER
 THE USE OF ANOTHER PLANT SPECIES.
  
 5. THE LIRIOPE ALONG THE EAST SIDE OF THE BUILDING WAS
 CHANGED TO BEAUTYBERRY BUT THE SYMBOL WAS NOT CHANGED
 ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By rkussner Date 2009-06-11 Time 12:38 Rev Time 0.00
Received By rkussner Date 2009-06-11 Time 12:38 Sent To  
Notes
2009-06-11 12:42:38***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PROVIDE SOD AND IRRIGATION IN THE RIGHT-OF-WAY,
 ADJACENT TO OKEECHOBEE BOULEVARD.
  
 2. SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULAITONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 4 THE PROPOSED LANDSCAPING ALONG THE FOUNDATION OF THE
 BUILDING IS DIFFERENT FROM WHAT WAS PREVIOUSLY
 APPROVED.
  
 5 THE APPLICANT SHALL BE REQUIRED TO LANDSCAPE ALONG
 THE EAST SIDE OF THE ACCESSWAY IN FROM OKEECHOBEE
 BOULEVARD (TRACT 'A') TO BE CONSISTENT WITH WHAT IS
 PROPOSED ALONG THE WEST SIDE OF THAT ACCESS.
  
 6. THERE ARE OVERHEAD LINES THAT RUN PARALLEL TO
 OKEECHOBEE BOULEVARD. ALL TREES TO BE INSTALLED SHALL
 CONFORM TO THE REQUIREMENTS SETFORTH IN FPL'S 'PLANT
 THE RIGHT TREE IN THE RIGHT PLACE' PUBLICATION.
  
 7. THERE ARE DESCREPANCIES BETWEEN PLANS. ALL PLANS
 MUST BE CONSISTENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-12-19 Cont ID  
Sent By rregueir Date 2009-12-19 Time 13:18 Rev Time 0.00
Received By rregueir Date 2009-12-19 Time 13:18 Sent To  
Notes
2009-12-19 13:58:10**PROVISOS**
 1. NEED PRODUCT APPROVAL FOR PRE-ENGINEERED STAND ON
 SITE PRIOR TO INSPECTION.
 2. NEED PROTECTION OF DUCT PENETRATIONS FOR EF-1 AND
 EF-3 DUCTS AT FLOOR OR SHAFT PENETRATIONS PER FBC-M
 607.5.5 OR 607.5.6.
 3. SUBMIT MANUFACTURER'S WIND RESISTANCE DATA FOR
 ROOFTOP UNITS PER FBC-M 301.12.
 4. SUBMIT COOLING LOAD CALCULATIONS PER FBC-B
 13-407.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-30 Cont ID  
Sent By rregueir Date 2009-09-30 Time 13:48 Rev Time 0.00
Received By rregueir Date 2009-09-29 Time 17:52 Sent To  
Notes
2009-09-30 13:48:02**PROVISOS**
 1. NEED PRODUCT APPROVAL FOR PRE-ENGINEERED STAND ON
 SITE PRIOR TO INSPECTION.
 2. NEED PROTECTION OF DUCT PENETRATIONS FOR EF-1 AND
 EF-3 DUCTS AT FLOOR OR SHAFT PENETRATIONS PER FBC-M
 607.5.5 OR 607.5.6.
 3. SUBMIT MANUFACTURER'S WIND RESISTANCE DATA FOR
 ROOFTOP UNITS PER FBC-M 301.12.
 4. SUBMIT COOLING LOAD CALCULATIONS PER FBC-B
 13-407.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By rregueir Date 2009-06-22 Time 11:14 Rev Time 0.00
Received By rregueir Date 2009-06-19 Time 16:54 Sent To B
Notes
2009-06-22 11:14:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1.01 AND M1.02: FILE ROOMS APPEAR TO BE
 INCIDENTAL USE AREAS IN ACCORDANCE WITH FBC-B 508.2. IN
 FULLY SPRINKLERED BUILDINGS, THIS ROOM REQUIRES SMOKE
 PARTITIONS IN ACCORDANCE WITH 508.2.2.1. SHOW THE
 TRANSFER AIR OPENING TO BE PROTECTED WITH SMOKE DAMPER
 IN ACCORDANCE WITH FBC-710.7. NOTE: THIS CONDITION
 WOULD APPLY TO ALL INCIDENTAL USE AREAS.
  
 2. PAGE M1.01: EXHAUST DUCTS FOR EF-3 MISSING SIZE.
 PROVIDE MISSING INFORMATION IN ACCORDANCE WITH FBC-M
 501.1.
  
 3. M1.01: FLOOR PLAN SHOWS EF-3 WITH 500 CFM WHILE
 EXHAUST GRILLS AND FAN SCHEDULE CALL FOR 400 CFM.
 PLEASE COORDINATE NOTES AND PLANS IN ACCORDANCE WITH
 FBC-M 501.1 AND FBC-B 106.1.1.
  
 4. M1.01: RTU-2 AND RTU-3 SUPPLY RISERS SHOW DUCT SMOKE
 DETECTORS ON ONE BRANCH ONLY. THIS LEAVES THE OTHER
 BRANCH NOT COVERED BY DUCT SMOKE DETECTOR. THE
 DETECTORS SHALL BE LOCATED TO SAMPLE THE ENTIRE AIRFLOW
 IN ACCORDANCE WITH FBC-M 606.3.
  
 5. M1.01: EF-1, EF-2 AND EF-3 ARE SHOWN WITH THE
 EXHAUST DUCT ON THE DISCHARGE SIDE OF THE FAN LOCATED
 IN THE RETURN AIR PLENUM CEILING. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN
 ACCORDANCE WITH FBC-M 601.5.
  
 6. M1.01: PROVIDE GRAVITY OPERATED OR MOTORIZED DAMPER
 ON EXHAUST DUCTS TO SHUT WHEN SPACES ARE NOT IN USE PER
 FBC-B 13-409.AB.3.3.
  
 7. M2.01 CONTAINS MOUNTING DETAILS FOR RTUS, FANS AND
 CURBS. THESE DETAILS ARE IN CONFLICT WITH CURB/UNIT
 ATTACHMENT DETAILS ON PAGE S401. PLEASE COORDINATE
 PLANS AND DETAILS AND DEMONSTRATE COMPLIANCE WITH FBC-M
 301.12.
  
 8. M2.01: PLAN CONTAINS INSTALLATION DETAIL FOR FIRE
 DAMPERS. NO PARTICULAR BRAND/MAKE OF FIRE DAMPER IS
 SPECIFIED ON PLANS. FIRE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER???S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC-M 607.2.
  
 9. PROVIDE MANUFACTURER???S DATA SHOWING ALL OUTDOOR
 APPLIANCES SUCH AS RTUS, EXHAUST FANS AND CONDENSING
 UNITS ARE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE
 WITH FBC-M 301.12. SEE COMMENT ABOVE AS MANUFACTURERS
 INSTALLATION DATA FOR WIND RESISTANCE MAY BE IN
 CONFLICT WITH MECHANICAL AND STRUCTURAL DETAILS ON
 PLANS.
  
 10. ME1.01: PLAN SHOWS CONDENSING UNITS INSTALLED ON
 ROOF STAND. NO DETAIL FOR THIS ROOF STAND COULD BE
 FOUND FOR THIS STAND. IS THIS A SITE BUILT OR
 PRE-ENGINEERED STAND? PROVIDE DETAIL FOR SITE BUILT
 STAND OR PRODUCT APPROVAL FOR PRE-ENGINEERED STAND,
 DEMONSTRATING COMPLIANCE WITH WIND RESISTANCE
 REQUIREMENTS OF FBC-M 301.12.
  
 11. P1.01 SHOWS CONDENSATE PUMPS OUTSIDE THE BUILDING
 TO DISPOSE OF CONDENSATE FROM AC-1 AND AC-2. SHOW ON
 PLANS WHERE THESE PUMPS WILL DISCHARGE THE CONDENSATE
 PER FBC-M 307.2.1. ALSO, ELECTRICAL PLANS DO NOT SHOW
 ANY POWER FOR THE PUMPS AT THE PROPOSED LOCATIONS.
 PLEASE CLARIFY THE DESIGN INTENT FOR CONDENSATE
 DISPOSAL FOR THESE UNITS.
  
 12. PROVIDE DETAIL SHOWING EXTERIOR BLOCK WALL FINISH
 ABOVE CEILING. NO SUCT DETAIL COULD BE FOUND IN
 ARCHITECTURAL PLANS. THIS IS A PLENUM SPACE. WALL SHALL
 BE INSULATED AND LINED WITH AN APPROVED AIR BARRIER IN
 ACCORDANCE WITH FBC-M 603.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-12-14 Cont ID  
Sent By kstevens Date 2009-12-14 Time 06:56 Rev Time 0.00
Received By kstevens Date 2009-12-14 Time 06:56 Sent To  
Notes
2009-12-14 06:58:30REVISION REQUIRED
  
 PASSED/PROVISO:
  
 SHT. IR-1 SHOW THE LOCATION OF THE REQUIRED CONTROLLER
 & RAIN SENSOR. FS 373.62 & APPENDIX F PART II "J".

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 16:46 Rev Time 0.00
Received By kstevens Date 2009-09-24 Time 18:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By kstevens Date 2009-06-29 Time 08:59 Rev Time 0.00
Received By kstevens Date 2009-06-25 Time 16:57 Sent To  
Notes
2009-06-29 09:20:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 FBC-2007 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS SIGNED & SEALED BY MICHAEL SIPULA. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(6) & FS 481.2055.
  
 2. SHT A.1 TOILET ROOM 5 SHALL BE ADAPTABLE. PLEASE
 INDICATE ON PLANS. SECTION 11-4.1.3(11).
  
 3. SHT A.1 THE SINKS IN THE BREAK ROOM & THE CEO BAR
 SHALL BE ACCESSIBLE. SECTION 11-4.24. PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH ALL SUBSECTIONS.
  
 4. SHT A.1 SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND LAV IN THE ACCESSIBLE STALLS. THE LAV CAN
 NOT BE IN THE CLEAR FLOOR SPACE OF THE WATER CLOSET.
 SEE FIGURE 11-30E.
  
 5. PLEASE SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S
 A. 11-4.16.3 HEIGHT
 B. 11-4/16/5 FLUSH CONTROLS (SHT A.8 DETAILS C & D SHOW
 THE FLUSH CONTROLS ON THE WRONG SIDE).
 ___LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE (TR/1 & TR/2)
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 6. SHT A.8 THE ACCESSIBLE STALL IN TR/2 2ND FLOOR
 LOBBY/TOILET AREA DOES NOT COMPLY WITH SECTION
 11-4.17.3 OR FIGURE 30E. THE LAV CAN NOT BE IN THE 5FT
 WIDE CLEAR FLOOR SPACE.
  
 SHT A.8 PLEASE SHOW THE ACCESSIBLE W/C'S TO BE 18
 INCHES OFF THE WALL TO THE CENTERLINE OF THE FIXTURE.
 FIGURE 30E. LAVS TO BE MINIMUM 15 INCHES OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE
 30 INCH DIMENSION OF THE CLEAR FLOOR SPACE. 11-4.19.3.
  
 7. SHTS P1.01 & P2.01 FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
  
  
 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 REQUIRED INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. - THE CORRESPONDING LENGHTS SHALL
 BE INDICATED TO VERIFY DISTANCE TO THE MOST REMOTE
 OUTLET.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2010-01-28 Cont ID  
Sent By eschneid Date 2010-01-28 Time 16:49 Rev Time 0.50
Received By eschneid Date 2010-01-28 Time 16:49 Sent To  
Notes
2010-01-28 16:50:48PASSED W/PROVISOS:
  
 1) PRIOR TO C.O. - TURN LANES @ BENOIST FARMS TO BE
 INSTALLED.
  
 2) PRIOR TO C.O. - LANDSCAPE AND SITE WORK COMPLETED
 AND FINALED.
  
 3) PRIOR TO C.O. - PARK AND RIDE SIGNS TO BE INSTALLED.
 APPROVED UNDER SEPARATE PERMIT.
  
 4) PRIOR TO C.O. - EASEMENTS SHALL BE GRANTED TO THE
 CITY FOR THE WATER METERS W/IN BANK TRACT.
  
 5) DRIVE-THRU LIGHTS SHALL BE RECESSED OR FLUSH MOUNTED
 UNDER THE CANOPY.

Review Stop Z ZONING
Rev No 3 Status F Date 2009-12-08 Cont ID  
Sent By eschneid Date 2009-12-08 Time 19:08 Rev Time 2.00
Received By eschneid Date 2009-12-08 Time 19:08 Sent To  
Notes
2009-12-08 19:42:36FAILED
  
 REVISED NOTE: THE PLANS SHOW WORK ON 3 PARCELS - BANK,
 COMMERCIAL AND ENTRY ROAD - EACH HAVING A DISTINCT PCN.
 PER ROBERT BROWN, ASSISTANT CONSTRUCTION SERVICES
 DIRECTOR, A SEPARATE BUILDING PERMIT IS REQUIRED FOR
 THE SITE AND LANDSCAPE WORK ON EACH PARCEL (SAME SET OF
 PLANS MAY BE USED FOR ALL THREE PERMITS). ZONING WILL
 NOT APPROVE THE PERMIT FOR THE BANK BUILDING UNTIL THE
 PERMITS FOR THE SITE WORK AND LANDSCAPE ARE SUBMITTED.
  
 NOTE: THE PLANS (FLOOR PLANS, ELEVATIONS, FOUNDATION)
 FOR THE BANK ITSELF ARE OK FOR ZONING. ONCE COMMENTS
 1A, 1E, AND SEPARATE SITE AND LANDSCAPE PERMITS ARE
 SUBMITTED, ZONING CAN APPROVE THE PERMIT FOR THE BANK
 BUILDING.
  
 1) REPEAT COMMENT: PROVIDE PROOF THAT THE FOLLOWING
 CONDITIONS FROM ORDINANCE NO. 4162-08 HAVE BEEN MET:
 (PLEASE NOTE THAT ACKNOWLEDGING THE COMMENT IS NOT THE
 SAME AS PROVIDING THE EVIDENCE THAT THE CONDITION IS
 SATISFIED)
  
 A. THE DEVELOPER SHALL INSTALL A TRAFFIC SIGNAL AT THE
 INTERSECTION OF OKEECHOBEE BOULEVARD AND BENOIST FARMS
 ROAD, UPON MEETING THE WARRANTS IDENTIFIED IN THE
 LATEST EDITION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). THE TRAFFIC DATA SHALL BE COLLECTED
 DURING PEAK SEASON OR ADJUSTED TO PEAK SEASON
 CONDITIONS BASED ON PALM BEACH COUNTY CRITERIA FOR TWO
 (2) CONSECUTIVE YEARS AFTER THE FINAL CERTIFICATE OF
 OCCUPANCY FOR THE OAKTON COMMONS CPD IS ISSUED. PRIOR
 TO THE ISSUANCE OF THE FIRST BUILDING PERMIT FOR THE
 FIRST COMMERCIAL BUILDING WITHIN THE OAKTON COMMONS CPD
 FOLLOWING THE ADOPTION OF THIS ORDINANCE, THE DEVELOPER
 SHALL PROVIDE WRITTEN VERIFICATION FROM THE PALM BEACH
 COUNTY ENGINEERING AND PUBLIC WORKS DEPARTMENT THAT ANY
 REQUIRED BOND HAS BEEN POSTED AND A PUBLIC FACILITIES
 AGREEMENT HAS BEEN EXECUTED WITH THE COUNTY. IF A BOND
 AND/OR PUBLIC FACILITIES AGREEMENT IS NOT REQUIRED,
 THEN IT SHALL BE STATED IN THE WRITTEN VERIFICATION
 FROM PALM BEACH COUNTY.
  
 B. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR ANY NEW BUILDING(S) WITHIN THE OAKTON COMMONS CPD,
 THE DEVELOPER SHALL PROVIDE THE FOLLOWING EXCLUSIVE
 TURN LANES AT THE PROJECT ACCESS DRIVEWAYS, WHERE NOT
 EXISTING, WHICH SERVICE THE NEW BUILDING(S) FROM THE
 REQUIRED TURN LANE(S):
  
 1. EXCLUSIVE WEST BOUND RIGHT-TURN LANE ALONG
 OKEECHOBEE BOULEVARD, ONTO THE PROJECT ACCESS AT THE
 INTERSECTION OF BENOIST FARMS ROAD.
 2. EXCLUSIVE EAST BOUND LEFT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE PROJECT ACCESS AT THE INTERSECTION
 OF BENOIST FARMS ROAD.
 3. WEST BOUND RIGHT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE WESTERN PROJECT ACCESS LOCATION.
 4. NOTWITHSTANDING THE FOREGOING PROVISIONS, IF
 CONSTRUCTION OF THE TURN LANE(S) IS INCLUDED IN THE
 FLORIDA DEPARTMENT OF TRANSPORTATION/PALM BEACH COUNTY
 CONTRACT TO WIDEN OKEECHOBEE BOULEVARD, THE CITY SHALL
 NOT DELAY THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 SOLELY BECAUSE THE FDOT/COUNTY ROAD CONTRACTOR HAS NOT
 COMPLETED INSTALLATION OF THE TURN LANE(S) PRIOR TO THE
 DEVELOPER'S REQUEST FOR THE CERTIFICATE OF OCCUPANCY.
  
 C. THE DEVELOPER SHALL PROVIDE THE CITY'S PLANNING AND
 ZONING DEPARTMENT DOCUMENTATION FROM PALM BEACH COUNTY
 OR THE FLORIDA DEPARTMENT OF TRANSPORTATION THAT THE
 EXCLUSIVE TURN LANE(S) HAS BEEN BUILT TO THE APPLICABLE
 STANDARDS OR EVIDENCE THAT THE CONSTRUCTION OF THE TURN
 LANE(S) IS INCLUDED IN THE CONTRACT TO WIDEN OKEECHOBEE
 BOULEVARD AND WILL BE CONSTRUCTED BY FDOT/COUNTY'S
 CONTRACTOR.
  
 D. PROOF PROVIDED
  
 E. PRIOR TO THE SUBMITTAL OF THE FIRST BUILDING PERMIT
 FOR THE COMMERCIAL POD, THE DEVELOPER SHALL RECORD AN
 EASEMENT TO ALLOW FOR JOINT USE OF THE COMMERCIAL
 PARKING FOR PARK AND RIDE PURPOSES. THE EASEMENT
 LANGUAGE SHALL BE REVIEWED AND APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT AND THE OFFICE OF THE CITY
 ATTORNEY PRIOR TO RECORDATION.
  
 2) REPEAT COMMENT: PROVIDE PROOF THAT THE FOLLOWING
 CONDITIONS FROM THE APRIL 23, 2009, BANK MINOR
 AMENDMENT APPROVAL LETTER HAVE BEEN MET: (PLEASE NOTE
 THAT ACKNOWLEDGING THE COMMENT IS NOT THE SAME AS
 PROVIDING THE EVIDENCE THAT THE CONDITION IS SATISFIED)
  
 A. CONDITION MET
  
 B. THE EAST SIDE OF THE ENTRY ROAD WITHIN TRACT A SHALL
 BE PLANTED WITH MATERIAL CONSISTENT WITH THE LANDSCAPE
 PROPOSED ON THE WEST SIDE OF THE ENTRY ROAD. THE
 SPECIFIC MATERIAL SHALL BE APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO INSTALLATION AND REFLECTED
 ON THE LANDSCAPE PLANS. **THE LANDSCAPE PLANS SUBMITTED
 WITH THE MINOR AMENDMENT ADDRESSES THIS CONDITION, BUT
 THE PLANS SUBMITTED AS PART OF THE BUILDING PERMIT DO
 NOT MATCH THE MINOR AMENDMENT PLANS.**
  
 3) REPEAT COMMENT: THERE ARE A NUMBER OF DISCREPANCIES
 AMONG THE LATEST PLANS APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT AND THE SITE, LANDSCAPE AND CIVIL
 PLANS SUBMITTED AS PART OF THE PERMIT. ADDITIONALLY,
 THERE ARE DISCREPANCIES AMONG THE PLANS SUBMITTED AS
 PART OF THE PERMIT. ALL PLANS SHALL BE INTERNALLY
 CONSISTENT AS WELL AS BE CONSISTENT WITH THE PLANS
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT. SAMPLE
 OF INCONSISTENCIES IDENTIFIED BELOW:
  
 A. CORRECTED
  
 B. THE LANDSCAPE PLAN SHOWS DIFFERENT LANDSCAPE AROUND
 THE BUILDING AND THE SIGN THAN WHAT WAS APPROVED BY
 PLANNING AND ZONING. ADDITIONALLY, THERE ARE CHANGES ON
 THE EAST, NORTH AND WEST SIDES OF THE SITE AND DUE TO
 THE RELOCATED WATER MAIN. THESE CHANGES REQUIRE THE
 APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT.
 **THE LANDSCAPE PLANS SUBMITTED WITH THE MINOR
 AMENDMENT ADDRESSES THIS CONDITION, BUT THE PLANS
 SUBMITTED AS PART OF THE BUILDING PERMIT DO NOT MATCH
 THE MINOR AMENDMENT PLANS.**
  
 C. CORRECTED
  
 D. CORRECTED
  
 E. CORRECTED
  
 F. CORRECTED
  
 4) NOTE THAT CHANGES TO THE PLANS WILL REQUIRE A NEW
 MINOR AMENDMENT APPROVAL BY THE PLANNING AND ZONING
 DEPARTMENT. **A MINOR AMENDMENT WAS SUBMITTED. THE
 LANDSCAPE PLANS SUBMITTED WITH THE PERMIT DO NOT MATCH
 THE MINOR AMENDMENT LANDSCAPE PLANS (LANDSCAPE COUNTS
 AND LAYOUT). THE STRIPING ON THE EAST SIDE OF THE DRIVE
 AISLE ON SP.1 DOES NOT MATCH THE MINOR AMENDMENT SITE
 AND CIVIL PLANS.**
  
 5) ADEQUATELY ADDRESSED
  
 6) CORRECTED
  
 7) CORRECTED
  
 8) REPEAT COMMENT: THE LANDSCAPE PLAN SHALL SHOW THE
 TREES THAT WILL BE RELOCATED INTO THE 50 FOOT NATURAL
 AREA BUFFER ADJACENT TO RIVERWALK. THE SITE WAS CLEARED
 DUE TO EXCESSIVE EXOTICS AND THUS NOW IS NO LONGER IN A
 NATURAL BUFFER STATE. **THE LANDSCAPE PLANS SUBMITTED
 WITH THE MINOR AMENDMENT ADDRESSES THIS COMMENT, BUT
 THE PLANS SUBMITTED AS PART OF THE BUILDING PERMIT DO
 NOT MATCH THE MINOR AMENDMENT PLANS.**
  
 9) CORRECTED PLEASE NOTE THAT AN IRRIGATION PERMIT IS
 REQUIRED.
  
 10) CORRECTED
  
 11) ADEQUATELY ADDRESSED
  
 12) CORRECTED
  
 13) CORRECTED
  
 14) PLEASE NOTE THE FOLLOWING REQUIREMENTS PRIOR TO THE
 FINAL CERTIFICATE OF OCCUPANCY FOR THE BANK:
  
 A. THE REQUIRED PARK AND RIDE SIGNAGE SHALL BE
 INSTALLED. NOTE: THESE SHALL BE SHOWN ON THE SIGN
 PERMIT.
  
 B. EASEMENTS SHALL BE GRANTED TO THE CITY FOR THE WATER
 METERS WITHIN THE PARCEL BOUNDARIES.
  
 C. SUBMITTED WITH MINOR AMENDMENT
  
 15) ADEQUATELY ADDRESSED
  
 16) CORRECTED
  
 17) REPEAT COMMENT: TWO LIGHT POST LOCATIONS ALONG THE
 PARKING NORTH OF THE FIRE STATION CONFLICT WITH TREE
 LOCATIONS. **THE LANDSCAPE PLANS SUBMITTED WITH THE
 MINOR AMENDMENT ADDRESSES THIS COMMENT, BUT THE PLANS
 SUBMITTED AS PART OF THE BUILDING PERMIT DO NOT MATCH
 THE MINOR AMENDMENT PLANS.**
  
 18) CORRECTED
  
 19) PLEASE NOTE THAT THE NEW GENERATOR WILL REQUIRE A
 SEPARATE PERMIT. ADDITIONALLY, THE GENERATOR AND THE
 MOUNT MAY NOT EXCEED THE HEIGHT OF THE MANSARD ROOF.
 DETAILS AND CROSS-SECTIONS NEED TO BE PROVIDED AT THE
 TIME OF THE GENERATOR PERMIT.
  
 20) CORRECTED
  
 21) NEW COMMENT: THE PAVING AND DRAINAGE PLANS
 (SPECIFICALLY SHEET 5 OF 7) SHOW A DIFFERENT ENTRY ROAD
 CONDITION (WIDTH AND ALIGNMENT), WEST LINE OF
 CONSTRUCTION (PHASE LINE) AND PHYSICAL ELEMENTS THAN
 THE SITE AND LANDSCAPE PLANS. THIS OCCURS ON BOTH THE
 MINOR AMENDMENT AND BUILDING PERMIT PLANS.
  
 22) NEW COMMENT: THE EGRESS WALKWAYS FROM THE DOORS ON
 THE NORTH SIDE OF THE BUILDING ARE NOT SHOWN ON THE
 PAVING PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-10-01 Cont ID  
Sent By eschneid Date 2009-10-01 Time 16:57 Rev Time 2.00
Received By eschneid Date 2009-10-01 Time 16:57 Sent To  
Notes
2009-10-01 16:58:35FAILED
  
 NOTE: THE PLANS SHOW WORK ON 3 PARCELS - BANK,
 COMMERCIAL AND ENTRY ROAD - EACH HAVING A DISTINCT PCN.
 PER ROBERT BROWN, ASSISTANT CONSTRUCTION SERVICES
 DIRECTOR, A SEPARATE BUILDING PERMIT IS REQUIRED FOR
 THE WORK ON EACH PARCEL. ZONING WILL NOT APPROVE THE
 PERMITS FOR THE BANK BUILDING AND BANK PARCEL SITE WORK
 UNTIL THE PERMITS FOR THE SITE WORK AND LANDSCAPE ON
 THE ENTRY ROAD TRACT AND THE COMMERCIAL TRACT ARE
 SUBMITTED.
  
 1) REPEAT COMMENT: PROVIDE PROOF THAT THE FOLLOWING
 CONDITIONS FROM ORDINANCE NO. 4162-08 HAVE BEEN MET:
  
 A. THE DEVELOPER SHALL INSTALL A TRAFFIC SIGNAL AT THE
 INTERSECTION OF OKEECHOBEE BOULEVARD AND BENOIST FARMS
 ROAD, UPON MEETING THE WARRANTS IDENTIFIED IN THE
 LATEST EDITION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). THE TRAFFIC DATA SHALL BE COLLECTED
 DURING PEAK SEASON OR ADJUSTED TO PEAK SEASON
 CONDITIONS BASED ON PALM BEACH COUNTY CRITERIA FOR TWO
 (2) CONSECUTIVE YEARS AFTER THE FINAL CERTIFICATE OF
 OCCUPANCY FOR THE OAKTON COMMONS CPD IS ISSUED. PRIOR
 TO THE ISSUANCE OF THE FIRST BUILDING PERMIT FOR THE
 FIRST COMMERCIAL BUILDING WITHIN THE OAKTON COMMONS CPD
 FOLLOWING THE ADOPTION OF THIS ORDINANCE, THE DEVELOPER
 SHALL PROVIDE WRITTEN VERIFICATION FROM THE PALM BEACH
 COUNTY ENGINEERING AND PUBLIC WORKS DEPARTMENT THAT ANY
 REQUIRED BOND HAS BEEN POSTED AND A PUBLIC FACILITIES
 AGREEMENT HAS BEEN EXECUTED WITH THE COUNTY. IF A BOND
 AND/OR PUBLIC FACILITIES AGREEMENT IS NOT REQUIRED,
 THEN IT SHALL BE STATED IN THE WRITTEN VERIFICATION
 FROM PALM BEACH COUNTY.
  
 B. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR ANY NEW BUILDING(S) WITHIN THE OAKTON COMMONS CPD,
 THE DEVELOPER SHALL PROVIDE THE FOLLOWING EXCLUSIVE
 TURN LANES AT THE PROJECT ACCESS DRIVEWAYS, WHERE NOT
 EXISTING, WHICH SERVICE THE NEW BUILDING(S) FROM THE
 REQUIRED TURN LANE(S):
  
 1. EXCLUSIVE WEST BOUND RIGHT-TURN LANE ALONG
 OKEECHOBEE BOULEVARD, ONTO THE PROJECT ACCESS AT THE
 INTERSECTION OF BENOIST FARMS ROAD.
 2. EXCLUSIVE EAST BOUND LEFT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE PROJECT ACCESS AT THE INTERSECTION
 OF BENOIST FARMS ROAD.
 3. WEST BOUND RIGHT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE WESTERN PROJECT ACCESS LOCATION.
 4. NOTWITHSTANDING THE FOREGOING PROVISIONS, IF
 CONSTRUCTION OF THE TURN LANE(S) IS INCLUDED IN THE
 FLORIDA DEPARTMENT OF TRANSPORTATION/PALM BEACH COUNTY
 CONTRACT TO WIDEN OKEECHOBEE BOULEVARD, THE CITY SHALL
 NOT DELAY THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 SOLELY BECAUSE THE FDOT/COUNTY ROAD CONTRACTOR HAS NOT
 COMPLETED INSTALLATION OF THE TURN LANE(S) PRIOR TO THE
 DEVELOPER'S REQUEST FOR THE CERTIFICATE OF OCCUPANCY.
  
 C. THE DEVELOPER SHALL PROVIDE THE CITY'S PLANNING AND
 ZONING DEPARTMENT DOCUMENTATION FROM PALM BEACH COUNTY
 OR THE FLORIDA DEPARTMENT OF TRANSPORTATION THAT THE
 EXCLUSIVE TURN LANE(S) HAS BEEN BUILT TO THE APPLICABLE
 STANDARDS OR EVIDENCE THAT THE CONSTRUCTION OF THE TURN
 LANE(S) IS INCLUDED IN THE CONTRACT TO WIDEN OKEECHOBEE
 BOULEVARD AND WILL BE CONSTRUCTED BY FDOT/COUNTY'S
 CONTRACTOR.
  
 D. PROOF PROVIDED
  
 E. PRIOR TO THE SUBMITTAL OF THE FIRST BUILDING PERMIT
 FOR THE COMMERCIAL POD, THE DEVELOPER SHALL RECORD AN
 EASEMENT TO ALLOW FOR JOINT USE OF THE COMMERCIAL
 PARKING FOR PARK AND RIDE PURPOSES. THE EASEMENT
 LANGUAGE SHALL BE REVIEWED AND APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT AND THE OFFICE OF THE CITY
 ATTORNEY PRIOR TO RECORDATION.
  
 2) PROVIDE PROOF THAT THE FOLLOWING CONDITIONS FROM THE
 APRIL 23, 2009, BANK MINOR AMENDMENT APPROVAL LETTER
 HAVE BEEN MET:
  
 A. CONDITION MET
  
 B. THE EAST SIDE OF THE ENTRY ROAD WITHIN TRACT A SHALL
 BE PLANTED WITH MATERIAL CONSISTENT WITH THE LANDSCAPE
 PROPOSED ON THE WEST SIDE OF THE ENTRY ROAD. THE
 SPECIFIC MATERIAL SHALL BE APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO INSTALLATION AND REFLECTED
 ON THE LANDSCAPE PLANS. PLEASE NOTE THAT THE RESPONSE
 PROVIDED WITH THE RESUBMITTAL IS INADEQUATE. THERE ARE
 AREAS IN THE ENTRY ROAD TRACT THAT CAN SUPPORT
 LANDSCAPE AND WOULD NOT INTERFERE WITH THE HEDGE AND
 SOD PLANTED ON THE FIRE STATION SITE. THESE SHALL BE
 PLANTED AS OUTLINED IN THE LANDSCAPE REVIEW COMMENTS.
  
 3) REPEAT COMMENT: THERE ARE A NUMBER OF DISCREPANCIES
 AMONG THE LATEST PLANS APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT AND THE SITE, LANDSCAPE AND CIVIL
 PLANS SUBMITTED AS PART OF THE PERMIT. ADDITIONALLY,
 THERE ARE DISCREPANCIES AMONG THE PLANS SUBMITTED AS
 PART OF THE PERMIT. ALL PLANS SHALL BE INTERNALLY
 CONSISTENT AS WELL AS BE CONSISTENT WITH THE PLANS
 APPROVED BY THE PLANNING AND ZONING DEPARTMENT. SAMPLE
 OF INCONSISTENCIES IDENTIFIED BELOW:
  
 A. CORRECTED
  
 B. THE LANDSCAPE PLAN SHOWS DIFFERENT LANDSCAPE AROUND
 THE BUILDING AND THE SIGN THAN WHAT WAS APPROVED BY
 PLANNING AND ZONING. ADDITIONALLY, THERE ARE CHANGES ON
 THE EAST, NORTH AND WEST SIDES OF THE SITE AND DUE TO
 THE RELOCATED WATER MAIN. THESE CHANGES REQUIRE THE
 APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT.
  
 C. CORRECTED
  
 D. CORRECTED
  
 E. THE PARKING DETAIL ON SHEET 6 OF 7 DOES NOT MATCH
 THE SIZE OF THE PARKING SPACES ON THE SITE PLAN
 (10'X20' VS 9'X18'). THIS DETAIL NOW CONFLICTS WITH THE
 DETAIL ON SHEET SP.1. PLEASE NOTE THAT NEITHER DETAIL
 SHOWS THE CONDITION WITH THE WHEEL STOPS. THE WHEEL
 STOPS SHALL BE LOCATED TWO (2) FEET FROM THE END OF THE
 SPACE. THE HC LOGO SHALL BE LOCATED TWO (2) FEET FROM
 THE OPEN END OF THE PARKING SPACE. THERE SHALL BE 12
 INCHES DIMENSIONED ON THE INSIDE OF THE DOUBLE
 STRIPPING (HARD TO DISTINGUISH THAT THE 16 INCHES SHOWN
 ON PLANS IS TO THE CENTER LINE OF EACH DOUBLE STRIP).
  
 F. CORRECTED
  
 4) NOTE THAT CHANGES TO THE PLANS WILL REQUIRE A NEW
 MINOR AMENDMENT APPROVAL BY THE PLANNING AND ZONING
 DEPARTMENT.
  
 5) ADEQUATELY ADDRESSED
  
 6) CORRECTED
  
 7) CORRECTED
  
 8) THE LANDSCAPE PLAN SHALL SHOW THE TREES THAT WILL BE
 RELOCATED INTO THE 50 FOOT NATURAL AREA BUFFER ADJACENT
 TO RIVERWALK. THE SITE WAS CLEARED DUE TO EXCESSIVE
 EXOTICS AND THUS NOW IS NO LONGER IN A NATURAL BUFFER
 STATE.
  
 9) CORRECTED PLEASE NOTE THAT AN IRRIGATION PERMIT IS
 REQUIRED.
  
 10) REPEAT COMMENT: CORRECTLY SHOW THE TRANSITION
 BETWEEN THE PARKING AND THE PRESERVE AREA ON THE SITE
 AND LANDSCAPE PLANS FOR THE LIMITS OF WORK. THERE SEEM
 TO BE CONTRADICTIONS WITH THE DETAIL AND THE LIMITS OF
 WORK (PHASE LINE). THE CIVIL PAVING AND DRAINAGE PLANS
 MAKE NO REFERENCE TO A "D" CURB BEING INSTALLED. IT IS
 ONLY SHOWN ON THE DETAIL. THIS HAS THE POTENTIAL OF THE
 "D" CURB NOT BEING INSTALLED IN THE FIELD BY THE
 CONTRACTOR. ADDITIONALLY, WHILE THE DETAILS ON THE
 CIVIL AND LANDSCAPE PLANS SHOW THE CURB, SOD AND SLOPE
 THAT WILL SEPARATE THE NORTHERN DRIVE AISLE FROM THE
 PRESERVE AREA, THIS IS SHOWN ON PHASE II AND THUS
 CREATES CONFUSION IF WILL BE INSTALLED AS PART OF THE
 PHASE I WORK. THIS NEEDS TO BE CLEARLY STATED AND SHOWN
 ON THE PLANS.
  
 11) ADEQUATELY ADDRESSED
  
 12) REPEAT COMMENT: CALL OUT THE CURBS AS "D" CURBS ON
 THE CIVIL PLANS. SEE COMMENT 10 ABOVE.
  
 13) CORRECTED
  
 14) PLEASE NOTE THE FOLLOWING REQUIREMENTS PRIOR TO THE
 FINAL CERTIFICATE OF OCCUPANCY FOR THE BANK:
  
 A. THE REQUIRED PARK AND RIDE SIGNAGE SHALL BE
 INSTALLED. NOTE: THESE SHALL BE SHOWN ON THE SIGN
 PERMIT.
  
 B. EASEMENTS SHALL BE GRANTED TO THE CITY FOR THE WATER
 METERS WITHIN THE PARCEL BOUNDARIES.
  
 C. TWO (2) COPIES OF THE FINAL REVISED ARCHITECTURAL
 PLANS, REFLECTING THE FOOTPRINT CHANGE APPROVED ABOVE,
 SHALL BE PROVIDED TO THE PLANNING AND ZONING DEPARTMENT
 PRIOR TO THE CERTIFICATE OF OCCUPANCY FOR THE BANK
 BUILDING.
  
 15) ADEQUATELY ADDRESSED
  
 16) NEW COMMENT: NO DETAILS WERE PROVIDED FOR THE NEW
 RETAINING WALL SURROUNDING THE LANDSCAPE AREA AT THE
 TERMINUS OF THE ENTRY DRIVE.
  
 17) NEW COMMENT: TWO LIGHT POST LOCATIONS ALONG THE
 PARKING NORTH OF THE FIRE STATION CONFLICT WITH TREE
 LOCATIONS.
  
 18) NEW COMMENT: THE CHANGE TO THE HC PARKING SPACE
 LAYOUT AT THE FRONT ENTRANCE OF THE BUILDING REQUIRES
 THE APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT.
  
 19) NEW COMMENT: PLEASE NOTE THAT THE NEW GENERATOR
 WILL REQUIRE A SEPARATE PERMIT. ADDITIONALLY, THE
 GENERATOR AND THE MOUNT MAY NOT EXCEED THE HEIGHT OF
 THE MANSARD ROOF. DETAILS AND CROSS-SECTIONS NEED TO BE
 PROVIDED AT THE TIME OF THE GENERATOR PERMIT.
  
 20) NEW COMMENT: PROVIDE DETAILS AS TO THE HEIGHT OF
 THE CONDENSING UNITS AND STANDS FROM THE ROOF AND
 PROVIDE A CROSS-SECTION TO VERIFY THAT THE OVERALL
 HEIGHT DOES NOT EXCEED THE HEIGHT OF THE MANSARD ROOF.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-16 Cont ID  
Sent By eschneid Date 2009-06-16 Time 08:32 Rev Time 2.50
Received By eschneid Date 2009-06-16 Time 08:32 Sent To  
Notes
2009-06-17 11:31:47FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 NOTE: THE PLANS SHOW WORK ON 3 PARCELS - BANK,
 COMMERCIAL AND ENTRY ROAD - EACH HAVING A DISTINCT PCN.
 PER ROBERT BROWN, ASSISTANT CONSTRUCTION SERVICES
 DIRECTOR, A SEPARATE BUILDING PERMIT IS REQUIRED FOR
 THE WORK ON EACH PARCEL.
  
 1) PROVIDE PROOF THAT THE FOLLOWING CONDITIONS FROM
 ORDINANCE NO. 4162-08 HAVE BEEN MET:
  
 A. THE DEVELOPER SHALL INSTALL A TRAFFIC SIGNAL AT THE
 INTERSECTION OF OKEECHOBEE BOULEVARD AND BENOIST FARMS
 ROAD, UPON MEETING THE WARRANTS IDENTIFIED IN THE
 LATEST EDITION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). THE TRAFFIC DATA SHALL BE COLLECTED
 DURING PEAK SEASON OR ADJUSTED TO PEAK SEASON
 CONDITIONS BASED ON PALM BEACH COUNTY CRITERIA FOR TWO
 (2) CONSECUTIVE YEARS AFTER THE FINAL CERTIFICATE OF
 OCCUPANCY FOR THE OAKTON COMMONS CPD IS ISSUED. PRIOR
 TO THE ISSUANCE OF THE FIRST BUILDING PERMIT FOR THE
 FIRST COMMERCIAL BUILDING WITHIN THE OAKTON COMMONS CPD
 FOLLOWING THE ADOPTION OF THIS ORDINANCE, THE DEVELOPER
 SHALL PROVIDE WRITTEN VERIFICATION FROM THE PALM BEACH
 COUNTY ENGINEERING AND PUBLIC WORKS DEPARTMENT THAT ANY
 REQUIRED BOND HAS BEEN POSTED AND A PUBLIC FACILITIES
 AGREEMENT HAS BEEN EXECUTED WITH THE COUNTY. IF A BOND
 AND/OR PUBLIC FACILITIES AGREEMENT IS NOT REQUIRED,
 THEN IT SHALL BE STATED IN THE WRITTEN VERIFICATION
 FROM PALM BEACH COUNTY.
  
 B. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR ANY NEW BUILDING(S) WITHIN THE OAKTON COMMONS CPD,
 THE DEVELOPER SHALL PROVIDE THE FOLLOWING EXCLUSIVE
 TURN LANES AT THE PROJECT ACCESS DRIVEWAYS, WHERE NOT
 EXISTING, WHICH SERVICE THE NEW BUILDING(S) FROM THE
 REQUIRED TURN LANE(S):
  
 1. EXCLUSIVE WEST BOUND RIGHT-TURN LANE ALONG
 OKEECHOBEE BOULEVARD, ONTO THE PROJECT ACCESS AT THE
 INTERSECTION OF BENOIST FARMS ROAD.
 2. EXCLUSIVE EAST BOUND LEFT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE PROJECT ACCESS AT THE INTERSECTION
 OF BENOIST FARMS ROAD.
 3. WEST BOUND RIGHT-TURN LANE ALONG OKEECHOBEE
 BOULEVARD, ONTO THE WESTERN PROJECT ACCESS LOCATION.
 4. NOTWITHSTANDING THE FOREGOING PROVISIONS, IF
 CONSTRUCTION OF THE TURN LANE(S) IS INCLUDED IN THE
 FLORIDA DEPARTMENT OF TRANSPORTATION/PALM BEACH COUNTY
 CONTRACT TO WIDEN OKEECHOBEE BOULEVARD, THE CITY SHALL
 NOT DELAY THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 SOLELY BECAUSE THE FDOT/COUNTY ROAD CONTRACTOR HAS NOT
 COMPLETED INSTALLATION OF THE TURN LANE(S) PRIOR TO THE
 DEVELOPER'S REQUEST FOR THE CERTIFICATE OF OCCUPANCY.
  
 C. THE DEVELOPER SHALL PROVIDE THE CITY'S PLANNING AND
 ZONING DEPARTMENT DOCUMENTATION FROM PALM BEACH COUNTY
 OR THE FLORIDA DEPARTMENT OF TRANSPORTATION THAT THE
 EXCLUSIVE TURN LANE(S) HAS BEEN BUILT TO THE APPLICABLE
 STANDARDS OR EVIDENCE THAT THE CONSTRUCTION OF THE TURN
 LANE(S) IS INCLUDED IN THE CONTRACT TO WIDEN OKEECHOBEE
 BOULEVARD AND WILL BE CONSTRUCTED BY FDOT/COUNTY'S
 CONTRACTOR.
  
 D. THE DEVELOPER SHALL RECORD, IN THE PUBLIC RECORDS OF
 PALM BEACH COUNTY, ALL REQUIRED CROSS ACCESS AND CROSS
 PARKING AGREEMENTS WITHIN THE OAKTON COMMONS CPD PRIOR
 TO THE ISSUANCE OF THE FIRST BUILDING PERMIT.
  
 E. PRIOR TO THE SUBMITTAL OF THE FIRST BUILDING PERMIT
 FOR THE COMMERCIAL POD, THE DEVELOPER SHALL RECORD AN
 EASEMENT TO ALLOW FOR JOINT USE OF THE COMMERCIAL
 PARKING FOR PARK AND RIDE PURPOSES. THE EASEMENT
 LANGUAGE SHALL BE REVIEWED AND APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT AND THE OFFICE OF THE CITY
 ATTORNEY PRIOR TO RECORDATION.
  
 2) PROVIDE PROOF THAT THE FOLLOWING CONDITIONS FROM THE
 APRIL 23, 2009, BANK MINOR AMENDMENT APPROVAL LETTER
 HAVE BEEN MET:
  
 A. THE LANDSCAPE PLANS SUBMITTED WITH THE BUILDING
 PERMIT SHALL INCLUDE A NOTE THAT THE PUBLIC
 RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK SURFACES AND
 REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN SPACE AREAS
 ADJACENT TO OKEECHOBEE BOULEVARD SHALL BE SODDED AND
 IRRITATED.
  
 B. THE EAST SIDE OF THE ENTRY ROAD WITHIN TRACT A SHALL
 BE PLANTED WITH MATERIAL CONSISTENT WITH THE LANDSCAPE
 PROPOSED ON THE WEST SIDE OF THE ENTRY ROAD. THE
 SPECIFIC MATERIAL SHALL BE APPROVED BY THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO INSTALLATION AND REFLECTED
 ON THE LANDSCAPE PLANS.
  
 3) THERE ARE A NUMBER OF DISCREPANCIES AMONG THE LATEST
 PLANS APPROVED BY THE PLANNING AND ZONING DEPARTMENT
 AND THE SITE, LANDSCAPE AND CIVIL PLANS SUBMITTED AS
 PART OF THE PERMIT. ADDITIONALLY, THERE ARE
 DISCREPANCIES AMONG THE PLANS SUBMITTED AS PART OF THE
 PERMIT. ALL PLANS SHALL BE INTERNALLY CONSISTENT AS
 WELL AS BE CONSISTENT WITH THE PLANS APPROVED BY THE
 PLANNING AND ZONING DEPARTMENT. SAMPLE OF
 INCONSISTENCIES IDENTIFIED BELOW:
  
 A. THE PHASE LINE ON THE SITE AND CIVIL PLANS
 INCORRECTLY DO NOT INCLUDE THE LANDSCAPE AREA AT THE
 TERMINATION OF THE ENTRY DRIVE AND THE AREA BY THE TURN
 AROUND.
  
 B. THE LANDSCAPE PLAN SHOWS DIFFERENT LANDSCAPE AROUND
 THE BUILDING AND THE SIGN THAN WHAT WAS APPROVED BY
 PLANNING AND ZONING.
  
 C. THE CIVIL PLANS SHOW THE WATER MAIN EAST OF THE
 BUILDING DIFFERENT THAN THE APPROVED PLANS AND THE
 SUBMITTED LANDSCAPE PLANS. ADDITIONALLY, THE LOCATION
 OF THE WATER MAIN ON THE CIVIL PLANS HAS IT PASS UNDER
 A TREE.
  
 D. THE LOCATION OF THE LIGHT POLES ON THE SOUTH SIDE
 OF THE BUILDING AND IN THE PARKING ROW NORTH OF THE
 BUILDING DIFFER ON THE SITE PLAN AND THE LANDSCAPE AND
 LIGHTING PLANS.
  
 E. THE PARKING DETAIL ON SHEET 6 OF 7 DOES NOT MATCH
 THE SIZE OF THE PARKING SPACES ON THE SITE PLAN
 (10'X20' VS 9'X18').
  
 F. THE CIVIL PLANS SHOW AN ARC ON THE WEST SIDE OF THE
 ENTRY ROAD WITH A MODIFIED SIDEWALK THAT IS NOT SHOWN
 ON ANY OTHER PLANS NOR ON ANY APPROVED PLANS.
  
 4) NOTE THAT CHANGES TO THE PLANS WILL REQUIRE A NEW
 MINOR AMENDMENT APPROVAL BY THE PLANNING AND ZONING
 DEPARTMENT.
  
 5) NO INFORMATION WAS PROVIDED ON THE PAVERS USED IN
 VARIOUS AREAS OF THE SITE.
  
 6) THE SIGNS AND AWNINGS WILL REQUIRE SEPARATE PERMITS
 - NOTE THAT THE ELEVATIONS SHOW THE AWNINGS LABELED AS
 METAL, WHILE THE DATA CHART CALLS THEM OUT AS METAL
 FRAME WITH CANVAS. THE ELEVATIONS SHALL BE CORRECTED.
  
 7) THE LANDSCAPE PLANS ARE MISSING THE REQUIRED
 CALCULATIONS, EX. XERISCAPE TABLE, PLANT NUMBER
 COMPLIANCE LIST, ETC.
  
 8) THE LANDSCAPE PLAN SHALL SHOW THE TREES THAT WILL BE
 RELOCATED INTO THE 50 FOOT NATURAL AREA BUFFER ADJACENT
 TO RIVERWALK. THE SITE WAS CLEARED DUE TO EXCESSIVE
 EXOTICS AND THUS NOW IS NO LONGER IN A NATURAL BUFFER
 STATE.
  
 9) PROVIDE IRRIGATION FOR THE RELOCATED TREES INTO THE
 NATURAL AREA LISTED IN #8 ABOVE.
  
 10) CORRECTLY SHOW THE TRANSITION BETWEEN THE PARKING
 AND THE PRESERVE AREA ON THE SITE AND LANDSCAPE PLANS
 FOR THE LIMITS OF WORK. THERE SEEM TO BE CONTRADICTIONS
 WITH THE DETAIL AND THE LIMITS OF WORK (PHASE LINE).
  
 11) WHAT ARE THE LIMITS OF THE CIVIL WORK? THE WATER
 AND SEWER PLANS SEEM TO INDICATE THAT LINES FOR THE
 ENTIRE OAKTON COMMONS CPD WILL BE INSTALLED AT THIS
 TIME, WHILE THE PAVING AND DRAINAGE PLANS SEEM TO ONLY
 APPLY TO THE BANK AND ENTRYWAY PARCELS.
  
 12) CALL OUT THE CURBS AS "D" CURBS ON THE CIVIL PLANS.
  
 13) WHAT IS THE 10" SCH 80 PVC LINE AT THE SOUTHWEST
 CORNER OF THE BUILDING? IT MAY NOT BE LOCATED UNDER A
 TREE AS SHOWN.
  
 14) PLEASE NOTE THE FOLLOWING REQUIREMENTS PRIOR TO THE
 FINAL CERTIFICATE OF OCCUPANCY FOR THE BANK:
  
 A. THE REQUIRED PARK AND RIDE SIGNAGE SHALL BE
 INSTALLED. NOTE: THESE SHALL BE SHOWN ON THE SIGN
 PERMIT.
  
 B. EASEMENTS SHALL BE GRANTED TO THE CITY FOR THE WATER
 METERS WITHIN THE PARCEL BOUNDARIES.
  
 C. TWO (2) COPIES OF THE FINAL REVISED ARCHITECTURAL
 PLANS, REFLECTING THE FOOTPRINT CHANGE APPROVED ABOVE,
 SHALL BE PROVIDED TO THE PLANNING AND ZONING DEPARTMENT
 PRIOR TO THE CERTIFICATE OF OCCUPANCY FOR THE BANK
 BUILDING.
  
 15) AN APPROVED MINOR PLANNED DEVELOPMENT IS REQUIRED
 FOR THE ULTIMATE LANDSCAPE WITHIN THE 10 FOOT PRESERVE
 BUFFER.
  