Plan Review Details - Permit 09060087
Plan Review Stops For Permit 09060087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-06 Cont ID  
Sent By jgomez Date 2009-10-05 Time 17:01 Rev Time 0.00
Received By jgomez Date 2009-10-05 Time 14:49 Sent To PC
Notes
2009-10-06 10:34:43PLANS APPROVED FOR STORAGE ROOM ONLY AS SHOWN ON PLANS.
 ROOM CAN'T BE USED AS LIVING AREA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By jgomez Date 2009-07-13 Time 09:33 Rev Time 0.00
Received By jgomez Date 2009-07-13 Time 09:32 Sent To  
Notes
2009-07-13 10:35:18RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0 OF 2007 FLORIDA RESIDENTIAL CODE.
 NOTE: MAKE SURE ALL INFORMATION IS PROVIDED AND ALL
 SIGNATURES ARE PROVIDED.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE VALUE TO INCLUDE ALL MATERIALS, LABOR,
 OVERHEAD AND PROFIT AND ALL PROFESSIONAL FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF. AND, CLEARLY MARK SPECIFIC APPROVED
 ASSEMBLY AND BASE SHEET FASTENING OPTION. PROVIDE RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. IF PRODUCT APPROVAL SUBMITTED REQUIRES
 CALCULATIONS TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
 NOTE: ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C". HAVE THIS IN CONSIDERATION WHEN PROVIDING THE RAS
 117 CALCULATIONS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 C) SHUTTERS FOR WINDOWS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE AND CLEARLY MARK SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C", NOT "B". REVISE PLANS DESIGN CRITERIA AND WINDOWS/
 DOORS DESIGN PRESSURES AS REQUIRED.
  
 6- INFORMATION ON ARCHITECT'S LETTER PROVIDED DOESN'T
 MATCH INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH.
 NOTE: LETTER IS NOT REQUIRED. PLANS SHALL BE OF
 SUFFICIENT CLARITY TO PROVIDE ALL THE INFORMATION.
  
 7- PLANS TO SHOW MINIMUM STUCCO THICKNESS AS REQUIRED
 BY TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE.
  
 8- PLANS TO SPECIFY TWO LAYERS OF WATER RESISTANT
 BARRIERS AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA
 RESIDENTIAL CODE FOR STUCCO ON FRAMED CONSTRUCTION.
  
 9- WALLS SECTION SPECIFIES T-111 WHILE ELEVATIONS
 SPECIFY STUCCO FINISH. CLARIFY AS REQUIRED TO MATCH.
  
 10- PROVIDE ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 OF 2007 FLORIDA RESIDENTIAL CODE. VENTILATION
 SPECIFIED ON WALL SECTION DOESN'T PROVIDE CROSS
 VENTILATION. REVISE AS REQUIRED.
  
 11- SPECIFY HOW LONG ARE THE 1/2" ANCHORS BOLTS
 SPECIFIED ON WALL SECTION TO VERIFY COMPLIANCE WITH
 UPLIFT LOADS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 12- REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON WALL
 SECTION TO COMPLY WITH SEC. R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. NEED TO SPECIFY RING SHANK NAILS IN
 ALL ZONES.
  
 13- WALL SECTION IS MISSING SPECIFICATIONS FOR WALL
 INSULATION.
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS.
  
 14- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 15- SURVEY SUBMITTED NEEDS SURVEYOR'S ORIGINAL
 SIGNATURE (NOT COPY OR RUBBER STAMP SIGNATURE) AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By dpalmer Date 2009-09-28 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2009-09-28 Time 10:00 Sent To P
Notes
2009-09-28 10:00:32SHALL NOT BE USED AS A DWELLING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 08:07 Sent To  
Notes
2009-06-19 08:07:22 
 ** DENIED PLANS *
  
 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK
 INCLUDING DESIGN COST, LABOR MATERIALS ETC EVEN IF ANY
 OF THESE ARE OWNER SUPPLIED SHALL BE INCLUDED. THE
 VALUE ON APPLICATION IS LOW PER MINIMUM PER SQ FT COST
 PER ICC TABLES. THIS IS ALSO A PROJECT WHICH HAS
 ALREADY BEEN BUILT. 4X FEE HAS BEEN ADDED AND FEE WILL
 INCREASE ONCE VALUE PER ICC TABLES HAVE BEEN ASSESSED.
 FBC 108.3
  
 2) NOTE: SERVICE ENTRANCE CONDUCTORS DO NOT MEET
 MINIMUM REQUIRED FOR SERVICER SHOWN. RISER SHOWS #2
 WITH A 200AMP MAIN AND A 60AMP MAIN. THE LOAD
 CALCULATIONS ALONE EXCEED THE RATINGS.
 PLEASE INCREASE SERVICE, METER CAN ETC.
 90.7,90.8,110.3,310.16,310.15B6, 220.87, 240.4 ETC
 ** PLEASE ALSO EXPLAIN WHY THE LOAD CALCULATIONS STATE
 LOAD FOR PANELS B AND C WHEN THERE IS ONLY A PANEL A
 AND B IDENTIFIED.
  
 3) NOTE: PLEASE SHOW THE NEW MAIN AIC RATINGS PER 110.9
  
 4) NOTE: PLEASE INCLUDE THE GROUNDING ELECTRODE SYSTEM
 REQUIRED AT THE DETACHED STRUCTURE PER 250.50,250.32
  
 5) NOTE: PLEASE INCLUDE THE MEANS OF DISCONNECT PER
 225.31-225.39.
  
 6) NOTE: PLEASE SHOW LOCATION OF SERVICE EQUIPMENT ON
 PLANS ALONG WITH THE SERVICE EQUIPMENT ON THE DETACHED
 STRUCTURE.
 240.24,110.26
  
 7) NOTE: PLANS NEED TO SHOW COMPLIANCE WITH 210.8A2
  
 ** THIS APPEARS TO BE A BUILDING BEING SET UP FOR
 LIVING AREA. PLEASE KNOW A HOLD WILL BE PLACED ON PCN
 FOR NO LIVING SPACE AND SUBJECT TO FURTHER INSPECTIONS.
 THIS IS THE THIRD BUILDING BEING CONSTRUCTED BY THIS
 CONTRACTOR AS *AS-BUILT* FOR THIS SAME PURPOSE.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-16 Time 09:50 Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 09:50 Sent To  
Notes
2009-09-22 09:50:34GAVE TO DEWWY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-13 Cont ID  
Sent By jgomez Date 2009-07-13 Time 10:39 Rev Time 0.00
Received By jgomez Date 2009-06-04 Time 15:50 Sent To  
Notes
2009-06-05 15:50:17R-14

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 11:03 Rev Time 0.00
Received By kstevens Date 2009-09-28 Time 11:03 Sent To Z
Notes
2009-09-28 11:03:39NEW SHEETS/RESTAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-16 Cont ID  
Sent By kstevens Date 2009-06-16 Time 10:22 Rev Time 0.00
Received By kstevens Date 2009-06-16 Time 10:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By ajones Date 2009-10-01 Time 15:29 Rev Time 0.00
Received By ajones Date 2009-10-01 Time 15:29 Sent To B
Notes
2009-10-01 15:31:02NO KITCHEN SHAL BE INSTALLED NOR STRUCTURE SHALL BE
 PERMITTED AS A DWELLING UNIT OR RENTAL.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-06-26 Cont ID  
Sent By mcruz Date 2009-06-26 Time 12:43 Rev Time 0.00
Received By mcruz Date 2009-06-26 Time 12:18 Sent To  
Notes
2009-06-26 12:43:42**AS NOTED ON PLANS, NO 220 V CONNECTIONS AND/OR
 KITCHED SHALL NOT BE INSTALLED. STRUCTURE SHALL NOT BE
 CONVERTED INTO A DWELLING UNIT OR RENTAL.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED IN R14