Plan Review Details - Permit 09060076
Plan Review Stops For Permit 09060076 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2009-12-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-12-08 |
Time |
15:14 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2009-12-08 |
Time |
15:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-10-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-10-01 |
Time |
15:57 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2009-10-01 |
Time |
15:30 |
Sent To |
|
|
Notes |
2009-10-01 15:48:04 | BUILDING PLAN REVIEW | | PERMIT: 09060076 | | ADD: 1335 OKEECHOBEE RD SUITE# 1000 | | CONT: ATLANTIC GENERAL CONTRACTING | | TEL: (561)434-4171 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | NO CHANGE IN INFORMATION! | | | | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC | | BUILDING WITH 2009 SUPPLEMENTS. PLEASE UPDATE PLANS TO | | ALSO INCLUDE THE 2007 EXISTING BUILDING CODE, CHAPTER | | 10 ADDITIONS (MEZZANINE ADDING FUEL LOADS) . | | | | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | 2007 FL BUILDING CODE, EXISTING BUILDING, ADDING A | | MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED | | CHAPTERFOR ADDITIONS. | | B) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING) | | AS DEFINED IN CHAPTER 5, TABLE 503, CHAPTER 6, TABLE | | 601. | | C) PLANS INDICATE THERE IS A FIRE SPRINKLER SYSTEM, IS | | IT A REQUIRED SYSTEM FOR AREA INCREASES IN THE | | BUILDING? | | D) PLANS INDICATE THE OCCUPANCY TYPE TO BE A STORAGE | | OCCUPANCY, S1 OR S2? | | | | 3) THE PLAN INDICATES THE MEZZANINE LEVEL OCCUPANCY | | SHALL BE USED FOR STORAGE. | | | | 3A) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. | | IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, | | PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F | | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR | | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT | | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD | | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY | | AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE | | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER | | SQ FT.THE | | COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT | | RECORD OF THE BLDG DEPT. | | | | 3B) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART | | OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS | | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE | | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON | | PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & | | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A | | CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. | | SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, | | REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. | | | | 4) NO PLANS WERE SUBMITTED FOR THE STRUCTURAL FRAMING | | OF THE MEZANINE NOR STAIRWAY OR FOR LOADING OF THE | | MEZZANINE LEVEL. | | 106.3.5 MINIUMUM PLAN CRITERIA FOR COMMERCIAL | | BUILDINGS. | | NOT HAVING BUILDING INFORMATION TYPE , FIRE RETARDANT | | CONSTRUCTION MAY ALSO BE A FACTOR WITH A PLYWOOD FLOOR. | | | | 5) PLANS INDICATE THE BUILDING HAS FIRE SPRINKLER | | SYSTEM ALREADY BUT NO PLANS WERE SUBMITTED FOR FIRE | | SPRINKLERS BENEATH THE MEZZANINE LEVEL. | | | | 6) GUARD RAILS, PLEASE PROVIDE COMPLIANCE WITH: | | 618.4.6.1 RAILINGS, STAIR-RAILINGS AND OTHER SIMILAR | | SAFEGUARDS SHALL BE DESIGNED TO RESIST A LOAD OF 50 | | POUNDS PER LINEAL FOOT (74 KG/M) OR A CONCENTRATED LOAD | | OF 200 POUNDS (690 N) APPLIED IN ANY DIRECTION AT THE | | TOP OF SUCH BARRIERS AT ANY LOCATION ON THE SAFEGUARD, | | WHICHEVER CONDITION PRODUCES THE MAXIMUM STRESSES. THE | | REACTIONS AND STRESSES CAUSED BY THE ABOVE REFERENCED | | UNIFORM AND CONCENTRATED LOADS SHALL BE CONSIDERED NOT | | BE ACTING SIMULTANEOUSLY. | | | | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, | | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE | | NOT PART OF THIS REVIEW. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-06-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-06-19 |
Time |
16:00 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2009-06-19 |
Time |
15:08 |
Sent To |
|
|
Notes |
2009-06-19 16:26:31 | BUILDING PLAN REVIEW | | PERMIT: 09060076 | | ADD: 1335 OKEECHOBEE RD SUITE# 1000 | | CONT: ATLANTIC GENERAL CONTRACTING | | TEL: (561)434-4171 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC | | BUILDING WITH 2009 SUPPLEMENTS. PLEASE UPDATE PLANS TO | | ALSO INCLUDE THE 2007 EXISTING BUILDING CODE, CHAPTER | | 10 ADDITIONS (MEZZANINE ADDING FUEL LOADS) . | | | | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | 2007 FL BUILDING CODE, EXISTING BUILDING, ADDING A | | MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED | | CHAPTERFOR ADDITIONS. | | B) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING) | | AS DEFINED IN CHAPTER 5, TABLE 503, CHAPTER 6, TABLE | | 601. | | C) PLANS INDICATE THERE IS A FIRE SPRINKLER SYSTEM, IS | | IT A REQUIRED SYSTEM FOR AREA INCREASES IN THE | | BUILDING? | | D) PLANS INDICATE THE OCCUPANCY TYPE TO BE A STORAGE | | OCCUPANCY, S1 OR S2? | | | | 3) THE PLAN INDICATES THE MEZZANINE LEVEL OCCUPANCY | | SHALL BE USED FOR STORAGE. | | | | 3A) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. | | IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, | | PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F | | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR | | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT | | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD | | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY | | AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE | | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER | | SQ FT.THE | | COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT | | RECORD OF THE BLDG DEPT. | | | | 3B) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART | | OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS | | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE | | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON | | PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & | | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A | | CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. | | SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, | | REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. | | | | 4) NO PLANS WERE SUBMITTED FOR THE STRUCTURAL FRAMING | | OF THE MEZANINE NOR STAIRWAY OR FOR LOADING OF THE | | MEZZANINE LEVEL. | | 106.3.5 MINIUMUM PLAN CRITERIA FOR COMMERCIAL | | BUILDINGS. | | NOT HAVING BUILDING INFORMATION TYPE , FIRE RETARDANT | | CONSTRUCTION MAY ALSO BE A FACTOR WITH A PLYWOOD FLOOR. | | | | 5) PLANS INDICATE THE BUILDING HAS FIRE SPRINKLER | | SYSTEM ALREADY BUT NO PLANS WERE SUBMITTED FOR FIRE | | SPRINKLERS BENEATH THE MEZZANINE LEVEL. | | | | 6) GUARD RAILS, PLEASE PROVIDE COMPLIANCE WITH: | | 618.4.6.1 RAILINGS, STAIR-RAILINGS AND OTHER SIMILAR | | SAFEGUARDS SHALL BE DESIGNED TO RESIST A LOAD OF 50 | | POUNDS PER LINEAL FOOT (74 KG/M) OR A CONCENTRATED LOAD | | OF 200 POUNDS (690 N) APPLIED IN ANY DIRECTION AT THE | | TOP OF SUCH BARRIERS AT ANY LOCATION ON THE SAFEGUARD, | | WHICHEVER CONDITION PRODUCES THE MAXIMUM STRESSES. THE | | REACTIONS AND STRESSES CAUSED BY THE ABOVE REFERENCED | | UNIFORM AND CONCENTRATED LOADS SHALL BE CONSIDERED NOT | | BE ACTING SIMULTANEOUSLY. | | | | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, | | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE | | NOT PART OF THIS REVIEW. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2009-12-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-12-03 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-12-03 |
Time |
17:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-10-10 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-10-10 |
Time |
08:14 |
Sent To |
|
|
Notes |
2009-10-10 08:14:49 | ** DENIED** | | | | 1) NOTE: NEW LIGHTING AND EXISTING LIGHTING APPEAR TO | | MEET REQUIRED MINIMUMS HOWEVER NEW LIGHTING DOES NOT | | INDICATE HOW OR WHERE THESE WILL BE CONTROLLED? | | FBC 13-415.AB.1.1,.1.2 | | NO CIRCUITING ON PLANS TO SHOW WHERE LIGHTS WOULD BE | | FED. SEE 700.12F FOR UNIT EMERGENCY LIGHT FIXTURES TO | | LOCAL LIGHTING BRANCH CIRCUIT. | | | | ** THE ABOVE COULD HAVE BEEN A PROVISO HOWEVER AS THERE | | ARE STILL BUILDING REVIEW COMMENTS THIS SHEET COULD NOT | | BE STAMPED OR GIVEN A PROVISO AT THIS TIME. | | | | **IMPORTANT** | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-06-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-06-18 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-06-18 |
Time |
14:11 |
Sent To |
|
|
Notes |
2009-06-18 14:19:19 | | | ** DENIED PLANS * | | | | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE | | FOLLOWING MINIMUM CODES. | | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL | | PLANS. | | 2007 FBC W/ 2009 AMENDMENTS. | | 2006 NFPA-101 | | 2002 NFPA-72 | | 2006 NFPA-1 | | 2005 NFPA-70 | | | | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 | | | | | | 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR | | LIGHTING PERFORMANCE CALCULATIONS. | | | | 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, | | AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. ONLY IF | | THERE IS FIRE ALARM PANEL AND/OR ANY DEVICES TO BE | | INSTALLED. | | | | 4) NOTE: PLEASE PROVIDE LIGHTING FOR NORMAL AND | | EMERGENCY EGRESS FOR STAIRS. SHOW NEW OR EXISTING TO | | MEET NFPA- 101 2006, 7.8.1.3, 7.9.1.2, .2.2 | | FAC 61G15-33.004 | | | | 5) NOTE: NEW LIGHTING CONTROLS SHALL MEET PRESCRIPTIVE | | 13-415.AB.1.1,.1.2, .1.3 | | | | 6) NOTE: VALUE FOR SCOPE OF WORK SHALL BE APPLICABLE TO | | SCOPE. THE PREVIOUS PERMIT FOR THIS SCOPE WHICH WAS | | NEVER ISSUED WAS SUBSTANTIALLY HIGHER. PLEASE SEE FBC | | 108.3 AS ADOPTED FOR VALUATION SHALL INCLUDE ALL LABOR, | | MATERIALS, DESIGN COST AND EQUIPMENT WHETHER OR NOT ANY | | OF THESE ARE OWNER SUPPLIED. | | | | 7) NOTE: PLEASE PROVIDE LICENSING FOR KC HUBBARD AND | | ASSOCIATES. * DESIGNERS NOT LICENSED UNDER FS 481 OR | | 471 ARE NOT PERMITTED TO DESIGN COMMERCIAL WORK PER | | 481.229. | | THIS HAS BEEN CONFIRMED WITH THE PROSECUTING ATTORNEY | | FOR THE FLORIDA BOARD OF ARCHITECTS. PLANS MAY BE | | RETAINED. | | | | | | | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-12-04 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-12-04 |
Time |
12:57 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-12-04 |
Time |
12:49 |
Sent To |
|
|
Notes |
2009-12-04 12:56:03 | *****APPROVED***** | | | | THE COMMENT(S) FROM THE PREVIOUS REVIEW HAVE BEEN | | ADDRESSED; PLAN SHEET A1 STAMPED, INITIALED, AND DATED. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2009-10-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-10-16 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-10-16 |
Time |
13:26 |
Sent To |
|
|
Notes |
2009-10-16 13:32:03 | *****PARTIAL APPROVAL***** | | | | | | THE APPROPIATE PLAN SHEET TO BE FIRE-STAMPED WHEN THE | | PREVIOUS BELOW COMMENT AS WELL AS THE OTHER EXAMINERS' | | COMMENTS HAVE BEEN ADDRESSED: | | | | 3. EFFECTIVE DECEMBER 31ST, 2008: NFPA 101, LIFE SAFETY | | CODE, 2006 EDITION SHALL BE REFERENCED. ADD CODE | | REFERENCE TO THE APPROPIATE SHEET | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-06-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-06-22 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-06-22 |
Time |
13:13 |
Sent To |
|
|
Notes |
2009-06-22 13:22:08 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2. HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE | | SPRINKLER AND FIRE ALARM DEVICES. SPRINKLERS ARE SHOWN, | | HOWEVER PROTECTION NEEDED ABOVE AND BELOW THE MEZZANINE | | FLOOR. | | | | 3. EFFECTIVE DECEMBER 31ST, 2008: NFPA 101, LIFE SAFETY | | CODE, 2006 EDITION SHALL BE REFERENCED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-11-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-11-17 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-11-17 |
Time |
16:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-09-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-09-30 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-09-30 |
Time |
08:50 |
Sent To |
|
|
Notes |
2009-09-30 08:51:13 | SENT TO BOB #10. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-06-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-06-22 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-06-03 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2009-10-05 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-10-05 |
Time |
10:58 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-10-05 |
Time |
10:58 |
Sent To |
|
|
Notes |
2009-10-05 10:58:59 | APPROVED 690 SQ. FT. OF STORAGE MEZZANINE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2009-06-08 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-06-08 |
Time |
14:33 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-06-08 |
Time |
14:33 |
Sent To |
|
|
Notes |
2009-06-08 14:40:29 | FAILED | | | | 1) THIS PERMIT IS FOR THE "COMPLETION OF MEZZANINE" | | THAT WAS ORIGINALLY SUBMITTED UNDER PERMIT NO. | | 08010311. PERMIT NO. 08010311 WAS NEVER ISSUED. | | | | 2) NO SHOP DRAWINGS, SPECIFICATIONS, ETC. WERE | | SUBMITTED WITH THIS PERMIT APPLICATION. | | | | 3) THE DRAWINGS INDICATE THAT THE MEZZANINE IS | | PLUS/MINUS 650 SQ. FEET. DUE TO THE PARKING | | REQUIREMENTS FOR THE AUSTRALIAN TRADE CENTER, THE EXACT | | SIZE OF THE MEZZANINE IS REQUIRED. | | | | 4) THE DIMENSIONS THAT ARE LISTED FOR THE MEZZANINE | | SHOW A MEZZANINE OF 715 SQ. FEET ONCE THE STAIRS AND | | LANDING ARE NOT INCLUDED. RECTIFY THE DIFFERING SQ. | | FEET AND SHOW ACCURATE DIMENSIONS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
|