Plan Review Details - Permit 09060067
Plan Review Stops For Permit 09060067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-11-05 Time 14:37 Rev Time 0.77
Received By jwitmer Date 2009-11-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2009-10-05 Time 09:11 Sent To FIRE
Notes
2009-10-05 09:46:27BUILDING PLAN REVIEW
 PERMIT: 09060067
 ADD: 6882 N JOG RD
 CONT:WEST CONSTRUCTION
 TEL: (561)248-3868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6882 N JOG RD. PAVILION TYPE II-B 685 SQ FT.
  
 1-3) COMPLIED.
 NEW COMMENTS:
  
 4) WITHIN THE NOA SUBMITTED FOR THE ALUMINUM STANDING
 METAL ROOF PANEL SYSTEM (NOA 09-0610.10) PLEASE REVIEW
 THE MAXIMUM SPAN FOR THE METAL DECK, THE NOA LIMITATION
 OF 5FT. O. C., WHEREAS THE PRE-ENGINEERED SPANS
 INDICATE SPANS OF 5'-9", 6'-01/2" & 6'-31/2". SHEET 5
 OF 6 UNDER THE HEADING OF GENERAL LIMITATIONS PLEASE
 REVIEW LIMITATION # 2 UNDER RATIONAL ANALYSIS.
  
 5) ALSO UNDER THE PERMIT APPLIED FOR NO ROOFING
 CONTRACTOR HAS SIGNED ON PLEASE REVIEW FL S S 489.113
 (3) (G) NO GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR
 CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OR
 HERSELF OUT TO BE, OR ADVERTISE HIMSELF OR HERSELF TO
 BE A ROOFING CONTRACTOR UNLESS HE OR SHE IS CERTIFIED
 OR REGISTERED AS A ROOFING CONTRACTOR.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-03 Cont ID  
Sent By jwitmer Date 2009-06-03 Time 11:15 Rev Time 0.75
Received By jwitmer Date 2009-06-03 Time 10:30 Sent To  
Notes
2009-06-03 11:12:12BUILDING PLAN REVIEW
 PERMIT: 09060067
 ADD: 6882 N JOG RD
 CONT:WEST CONSTRUCTION
 TEL: (561)248-3868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B
 5,600 SQ FT
 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B
 1,200 SQ FT
 6882 N JOG RD. PAVILION TYPE II-B 685 SQ FT.
  
 THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE
 PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND
 ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE
 INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING,
 AND SEPERATE TRACKING OF INSPECTIONS.
  
 THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE
 ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT
 NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION.
  
 1) , 1ST UNDER PERMIT APPLICATION. THE RESPONSE
 COMMENTS INDICATE THIS TO BE A PAVILION, TO BE PART OF
 THIS PERMIT WE DO NEED INFORMATION AS FAR AS COMPONENTS
 AND CLADDING YOU INDICATE THIS IS A PRE-ENGINEERED
 CANOPY, EITHER IT HAS GONE THROUGH THE MANUFACTURED
 BUILDING PROGRAM WITH THE STATE AND IS APPROVED AS A
 MANUFACTURED MODULAR BUILDING PROGRAM WITH STATE
 APPROVED PLANS OR IT WILL NEED PRODUCT APPROVALS FOR
 THE ROOFING ASSEMBLY. WITHOUT PLANS THIS AREA WILL BE
 EXEMPTED FROM THE PERMIT AND PLANS TO BE SUBMITTED
 UNDER A SEPERATE PERMIT.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE
 FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS
 FOR RATED WALLS BEING BUILDINGS AND OPENING
 PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS,
 NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS
 PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004
 FL 3778-R1
 IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING
 SUBSHEATHING DECK. 1507.4.1.
  
 2) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS
 ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART
 OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE
 ADDITONAL INFORMATION, 106.1..2. 106.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
  
 3) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE
 A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT
 INFORMATION, TO BE PART OF THIS PERMIT WE DO NEED
 INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY.
 WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE
 PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE
 PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, IS
 THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL BE
 REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE
 AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE
 GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 09:06 Rev Time 0.00
Received By jwitmer Date 2009-10-05 Time 09:06 Sent To  
Notes
2009-10-05 09:07:12NO ELECTRICAL SHEETS WERE SUBMITTED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By mawillia Date 2009-11-09 Time 15:48 Rev Time 0.00
Received By mawillia Date 2009-11-09 Time 15:40 Sent To B
Notes
2009-11-09 15:47:06*****APPROVED******
  
 PLAN SHEET C-3 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-05 Cont ID  
Sent By mawillia Date 2009-10-05 Time 11:05 Rev Time 0.00
Received By mawillia Date 2009-10-05 Time 10:46 Sent To  
Notes
2009-10-05 11:04:33*****DENIED*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. PROVIDE SITE PLAN INDICATING LOCATION OF THE
 PROPOSED PAVILION.
  
 3. NFPA 101, LIFE SAFETY CODE, 2006 AND NFPA 1, UNIFORM
 FIRE CODE, 2006 SHALL BE REFERENCED.
  
 4. IN INSTALLING/ERECTING THE PROPOSED PAVILION, IN NO
 WAY SHALL THE PROPOSED SCOPE OF WORK HINDER, INTERFERE,
 OR OBSTRUCT FIRE DEPARTMENT VEHICULAR RESPONSE AND/OR
 ACCESIBILITY TO WATER SUPPLIES AND FIRE HYDRANTS
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-27 Cont ID  
Sent By shill Date 2009-10-27 Time 09:48 Rev Time 0.00
Received By shill Date 2009-10-27 Time 09:48 Sent To  
Notes
2009-10-27 09:49:42C 13
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2009-09-30 Time 10:28 Sent To  
Notes
2009-09-30 10:28:32SENT TO J. WITMER'S DESK. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2009-10-05 Time 09:08 Sent To  
Notes
2009-10-05 09:09:10INCOMING 9/24/09 TO JW DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-06-12 Cont ID  
Sent By rregueir Date 2009-06-12 Time 14:53 Rev Time 0.00
Received By rregueir Date 2009-06-12 Time 14:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-29 Cont ID  
Sent By eschneid Date 2009-10-29 Time 16:52 Rev Time 0.15
Received By eschneid Date 2009-10-29 Time 16:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-01 Cont ID  
Sent By eschneid Date 2009-10-01 Time 13:56 Rev Time 0.10
Received By eschneid Date 2009-10-01 Time 13:54 Sent To B
Notes
2009-10-01 14:24:56FAILED
  
 1) PLEASE PROVIDE A SITE PLAN THAT SHOWS THE LOCATION
 OF THE PROPOSED PAVILION.
  
 2) PLEASE NOTE THAT PLANS SUBMITTED AS PART OF THE
 ORIGINAL ZONING APPROVAL DO NOT SHOW A FIXED PAVILION
 STRUCTURE. REVISED PLANS SHALL BE SUBMITTED TO THE
 ZONING DIVISION FOR APPROVAL PRIOR TO THIS PERMIT BEING
 APPROVED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.