2009-06-03 10:30:07 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| 108.3 CITY AMENDMENTS TO FBC. |
| THEREFORE, OWES $135.78. |
| |
| 3- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED |
| FOR ROOF SHINGLES. NOA 05-1115.08 SUBMITTED EXPIRED ON |
| 04/22/08. AND NOA 07-1120.14 SUBMITTED WAS SUPERSEDED |
| BY MIAMI-DADE COUNTY. SEE ATTACHED COPY FROM MIAMI DADE |
| COUNTY WEBSITE. NEED TO PROVIDE TWO COPIES OF CURRENT |
| SHINGLES PRODUCT APPROVAL. |
| |
| 4- COMMENTS TO FLAT ROOF NOA 09-0224.01 SUBMITTED: |
| A) MARK WHICH APPROVED ASSEMBLY IS GOING TO BE |
| INSTALLED. |
| |
| B) MARK WHICH BASE SHEET FASTENING OPTION IS GOING TO |
| BE INSTALLED. |
| |
| C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| LIMITATION #7. |
| NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE |
| USED IN THIS AREA. |
| |
| D) ACCORDING TO GENERAL LIMITATION #7 ON SHEET #31 OF |
| NOA SUBMITTED, THE RAS 117 CALCULATIONS NEED TO BE |
| SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. PROVIDE |
| SIGNED AND SEALED CALCULATIONS. |
| |
| E) CLARIFY WHY THIS NOA WAS REVIEWED AND APPROVED BY |
| THE ENGINEER LUIS LOPEZ. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |