2009-06-03 11:43:58 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. THE PERMIT APPLICATION AND PERMIT DOCUMENTS STATE |
| THAT THE ROOF TILES ARE NO LONGER MADE. HOWEVER, THE |
| APPLICATION DOES NOT PROPOSE AN INSTALLATION. PERMIT |
| DOCUMENTS ARE INCOMPLETE; PLEASE PROVIDE COMPLETE |
| DOCUMENTATION REGARDING THE PROPOSED REPAIR. EXISTING |
| TILES MAY BE REINSTALLED FBC EB 611.5 BUT MUST NOT BE |
| CRACKED OR BROKEN (AND WOULD REQUIRE A PRE INSPECT OF |
| TILES TO BE REINSTALLED). POLYPRO 160 WAS PROVIDED AS |
| METHOD OF TILE ATTACHMENT, BUT NO INFORMATION REGARDING |
| THE TILE TO BE INSTALLED WAS PROVIDED, EXCEPT TH |
| REFERENCE TO GORY TILE ON SECTION D. OTHER DOCUMENTS |
| STATE THAT THIS IS NOT AVAILABLE. SCOPE OF WORK IS NOT |
| CLEAR FBC*106. |
| |
| 2. FBC EB 611.1.1, NOT MORE THAN 25 PERCENT OF TOTAL |
| ROOF AREA OR ROOF SECTION OF ANY EXISTING BUILDING |
| SHALL BE REPAIRED IN ANY 12 MONTH PERIOD UNLESS THE |
| ENTIRE ROOFING SYSTEM OR ROOF SECTION CONFORMS TO THE |
| REQUIREMENTS OF THIS CODE. PROVIDE INFORMATION |
| REGARDING THE EXISTING ROOF OR ROOF SECTION TO SHOW |
| COMPLIANCE. |
| |
| |
| |
| |
| |
| |