Plan Review Details - Permit 09060005
Plan Review Stops For Permit 09060005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 10:41 Rev Time 0.50
Received By jwitmer Date 2009-07-08 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By jwitmer Date 2009-06-19 Time 13:53 Rev Time 0.77
Received By jwitmer Date 2009-06-19 Time 13:00 Sent To  
Notes
2009-06-19 14:03:50BUILDING PLAN REVIEW
 PERMIT: 09060005
 ADD: 1801 S FLAGLER DR UNIT 1411
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) SHEET # 1 MISCELLANEOUS NOTE#1 INDICATES THIS TO BE
 A R-4 OCCUPANCY WHEREAS IN THE LISTED ON THE SAME SHEET
 CONSTRUCTION INFORMATION INDICATES A R2 OCCUPANCY.
 TABLE 803.5.
  
 3) SHEET 4 INDICATES THE USE OF SOFFITS BUT THERE IS NO
 INFORMATION AS TO MATERIALS, FRAMING OR ATTACHMENT TO
 THE DECK ABOVE? ADDITIONAL INFORMATION REQUIRED
 106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-11 Cont ID  
Sent By dpalmer Date 2009-08-11 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2009-08-11 Time 14:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 12:10 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 12:10 Sent To  
Notes
2009-07-04 12:10:18 
 ** DENIED PLANS 2ND REVIEW **
 SOME NOTES FROM PREVIOUS REVIEW STILL NOT ADDRESSED.
 SOME NEW NOTES BASED ON SOME INFORMATION SHOWN NOT ON
 PREVIOUS PLANS.
 AS STATED ON PREVIOUS REVIEW, IF THERE ARE QUESTIONS OR
 COMMENTS OR IF THERE ARE ANY NOTES NOT TYPED IN A CLEAR
 MANNER PLEASE CALL. NO CONTACT WAS MADE FROM LAST
 REVIEW AND IT APPEARS PERHAPS SOME NOTES WERE NOT
 UNDERSTOOD.
  
 1) NOTE: AS THE SCALE IS VERY SMALL AND THERE IS A LOT
 OF ITEMS SHOWN ON PLANS. AS STATED ON PREVIOUS REVIEW
 PLANS ARE CONGESTED. CIRCUITING IS NOT CLEAR. SOME
 ITEMS STILL DO NOT INDICATE CIRCUITING. SEE REDLINED
 PLANS. OTHERS SUCH AS CIRCUIT 2A, 9B, 7B AND 12A ARE
 STATED AS GENERAL LIGHTING. PLEASE SEE COMMENTARY FROM
 THE 2005 NEC IN 408.4. THESE NEED TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. LIVING ROOM
 LTS/RECEPTS, KITCHEN LIGHTS ETC OR OTHER DESIGNATION.
 408.4, 210.52, 210.11 ETC
  
 2) NOTE: MINIMUM OF TWO SMALL APPLIANCE CIRCUITS IS
 REQUIRED PER 210.52B1, 210.11C1, 220.53. LIGHTING
 CIRCUIT 7B IS SHOWN CONNECTED TO RECEPTACLE IN ONE AREA
 WHICH IS NOT PERMITTED.
 THE KITCHEN PLANS ARE NOT CLEAR.
  
 3) NOTE: PLEASE SEE GUEST BATH. THIS ROOM SHOWS THE
 CIRCUIT TO GFI AS 5B. THIS IS SHOWN AS A BEDROOM
 CIRCUIT ON PANEL SCHEDULE WITH #14AWG AND 15AMP
 BREAKER. THIS IS NOT PERMITTED. PLEASE SEE 210.11C3 AS
 BATH GFI CIRCUITS/RECEPTACLES ARE ONLY PERMITTED TO BE
 CIRCUITED ONE OF TWO WAYS. IN EITHER CASE THEY ARE ALSO
 REQUIRED TO BE 20AMP AND #12.
  
 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE
 MISSING FOR WALL SPACES. SEE ONE SET OF PLANS WHICH ARE
 REDLINED.
 WALL IN MASTER BEDROOM, WALL IN OTHER GUEST ROOM.
  
 5) NOTE: PLEASE SEE S1 AND S2 NOTES ON PLANS. THE
 SYMBOL LEGEND STATES S 1 AND S2 ARE SMOKE ALARMS, YET
 THE NOTES STATE S2 IS A SMOKE DETECTOR WHICH IS NOT THE
 SAME. S2 NOTE ALSO STATES ONLY TO BE INTERCONNECTED
 WHEN WITHIN 20FT OF COOKING APPLIANCES.
  
 A) ALL SMOKE DETECTION DEVICES WHETHER OR NOT SMOKE
 ALARMS OR DETECTORS ARE REQUIRED TO BE INTERCONNECTED
 IN THIS R OCCUPANCY.
 B) ALL SHALL BE CIRCUITED SINGLE STATION INTERCONNECTED
 AND ON ONE OF THE ARC FAULT PROTECTED CIRCUITS PER
 210.12. SINCE S2 OUTSIDE SLEEPING ROOM IS REQUIRED TO
 BE INTERCONNECTED WITH THE S1 UNITS, THIS MUST ALSO BE
 ON THE SAME AFCI CIRCUIT.
  
 NFPA-72 11.8.3,11.5.1, NEC 210.12.
  
  
  
 ** ONLY NOTED FOR INFORMATION. LOW VOLTAGE SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT. MAY
 USE THESE PLANS AS A REFERENCE FOR TURN AROUND PERMIT.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By dpalmer Date 2009-06-17 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2009-06-17 Time 15:16 Sent To  
Notes
2009-06-17 15:16:45 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2003 FOR THIS CODE)
 2002 NFPA-72
 2006 NFPA-1
 2005 NFPA-70 ( PLANS DO NOT GIVE YEAR)
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WITHOUT THE
 MECHANICAL SHADED OVER THE ELECTRICAL DETAILS. SOME
 ITEMS ARE NOT CLEAR TO BE REVIEWED FOR CODE COMPLIANCE.
 THE KITCHEN PLANS FOR EXAMPLE ARE VERY CONGESTED AND
 NOT EASILY READ FOR CODE COMPLIANCE VERIFICATION OF
 210.52C1-5 FOR EXAMPLE.
 FBC 106.1.1 FOR CLARITY AND QUALITY OF SUBMITTED PLANS.
 NEC, 300,210,ETC
  
 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES. PER THE SYMBOL LEGEND THE PLANS
 STATE THERE IS GOING TO BE SMOKE DETECTORS. SMOKE
 DETECTORS ARE DEVICE WHICH DETECT HOWEVER DO NOT SOUND
 AN ALARM. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE
 SUBMIT MORE DETAILS ON THE COMPLETE SYSTEM SHOWING THE
 HORNS, STROBES PANEL OR SOUNDING DEVICES TO ALERT THE
 OCCUPANT.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
 ** PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE ALARMS. IF
 THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AN ALARM
 PLEASE ADJUST PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE BE SURE TO SEE 210.4B FOR ANY DEVICES
 OR SINGLE YOKE BEING FED FROM MORE THAN ONE CIRCUIT.
 THIS MAY BE THE DISHWASHER/DISPOSAL WHICH WOULD REQUIRE
 A TWO POLE BREAKER. IT IS NOT CLEAR AT THIS TIME IF
 THIS IS THE SAME YOKE OR NOT.
  
 5) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOAD UNDER
 THE 2005 NEC IS NOW CONSIDERED A CONTINUOUS LOAD WHICH
 REQUIRES 125% TO BE FIGURED INTO THE CALCULATIONS.
  
 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE
 LOAD CALCULATIONS ARE NOT FROM THE CURRENT EDITION OR
 EVEN PREVIOUS EDITION OF THE NEC. IN FACT PLANS STATE
 202.32, 202.30. THERE IS NO SECTION 202 LOCATED IN
 NFPA70. EVEN IF THESE WERE MISPRINTS TO BE
 220.30,220.32, THE CURRENT EDITION OF THE NEC WHICH IS
 THE ADOPTED 2005 DOES NOT CONTAIN THESE SECTIONS.
 PLEASE SEE NEW CODE WHICH WENT INTO AFFECT DECEMBER 8TH
 2006.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS EACH
 OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS SHALL BE
 FIGURED AT 1500VA FOR EACH. NO LOAD IS SHOWN IN THE
 LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLE
 CIRCUIT.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-08-12 Cont ID  
Sent By mawillia Date 2009-08-12 Time 11:10 Rev Time 0.00
Received By mawillia Date 2009-08-12 Time 10:54 Sent To B
Notes
2009-08-12 11:09:44*****APPROVED*****
  
 PLAN SHEETS 6 & 7 WERE STAMPED, INITIALED, AND DATED;
 SHEET 2 WAS PREVIOUSLY FIRE-STAMPED ON 7/20/2009.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-07-20 Cont ID  
Sent By mawillia Date 2009-07-20 Time 13:25 Rev Time 0.00
Received By mawillia Date 2009-07-20 Time 13:06 Sent To  
Notes
2009-07-20 13:21:42*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAS
 BEEN SATISFIED; PLAN SHEET 2 WAS STAMPED, INITIALED,
 AND DATED - HOWEVER SHEETS 6 & 7 ARE TO FIRE-STAMPED
 WHEN THE ELECTRICAL EXAMINER'S COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By mawillia Date 2009-06-18 Time 13:53 Rev Time 0.00
Received By mawillia Date 2009-06-18 Time 13:17 Sent To  
Notes
2009-06-18 13:52:56*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION. ADD COMMENT TO SHEET 2 (OF SEVEN).
  
 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101
 SHALL BE REFERENCED. AMEND ELECTRICAL NOTE #1 AND FIRE
 PROTECTION NOTE #1 ON SHEET 7 (OF SEVEN).
  
 3. THE SMOKE DETECTOR / SMOKE ALARM DEVICES AREN'T
 READILY VISIBLE DUE TO CLARITY OF PLANS AS SHOWN ON
 SHEET 6 (OF SEVEN).
  
 4. INDICATE THE TYPE OF DEVICE THAT IS/ARE BEING AND OR
 WILL BE USED IN THE LIVING UNIT. BE ADVISED THAT SMOKE
 DETECTORS (SD) ARE TIED INTO THE BUILDING'S FIRE ALARM
 SYSTEM, WHEREAS SMOKE ALARMS (SA) SHALL SOUND ONLY
 WITHIN THE DWELLING UNIT AND SHALL NOT ACTUATE THE
 BUILDING FIRE ALARM SYSTEM, UNLESS OTHERWISE PERMITTED
 BY THE AUTHORITHY HAVING JURISDICTION (AHJ).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-26 Cont ID  
Sent By lmartine Date 2009-08-26 Time 09:28 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 09:25 Sent To  
Notes
2009-08-26 09:30:46DUCT REVISION
2009-08-26 09:28:42GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-29 Cont ID  
Sent By lmartine Date 2009-07-29 Time 09:01 Rev Time 0.00
Received By lmartine Date 2009-07-29 Time 09:01 Sent To  
Notes
2009-07-29 09:02:10B-2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 09:35 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 09:35 Sent To  
Notes
2009-07-01 09:36:14WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 15:26 Rev Time 0.00
Received By rregueir Date 2009-06-02 Time 10:56 Sent To PC
Notes
2009-06-02 10:56:12TO B12
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-08-31 Cont ID  
Sent By rregueir Date 2009-08-31 Time 16:44 Rev Time 0.00
Received By rregueir Date 2009-08-31 Time 16:44 Sent To  
Notes
2009-08-31 16:44:57REVISED DUCT LAYOUT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 09:27 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 16:28 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 16:26 Sent To  
Notes
2009-07-13 16:28:52PREVIOUS COMMENTS ADDRESSED. PLANS NOT STAMPED DUE TO
 FAILED ELECTRICAL REVIEW AND MECHANICAL BEING ON THE
 SAME PAGE. MECHANICAL STAMPS WILL BE APPLIED TO PLANS
 ONCE ELECTRICAL REVIEW IS PASSED UNLESS SEPARATE SHEETS
 ARE SUBMITTED FOR EACH TRADE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 15:25 Rev Time 0.00
Received By rregueir Date 2009-06-19 Time 15:23 Sent To PC
Notes
2009-06-19 15:25:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE SHOW CFM QUANTITIES FOR EACH SUPPLY REGISTER
 ON PLANS IN ACCORDANCE WITH FBC-M 603.1
  
 2. NO BATHROOM EXHAUST IS SHOWN ON PLANS. EXHAUST IS
 REQUIRED IN THE BATHROOM PER FBC-EB 709.1 AND FBC-M
 402.3.1.
  
 3. NOTE #4 ON PAGE 6 CALLS FOR WASHER AND DRYER BUT NO
 SUCH APPLIANCES COULD BE FOUND ON PLANS. PLEASE CLARIFY
 IN ACCORDANCE WITH FBC-B 106.1.1.
  
 4. SOME DUCT SIZES PROPOSED ON PAGE 6 WILL NOT FIT
 BASED ON THE SIZES OF SOFFITS SHOWN ON PAGE 3. PLEASE
 COORDINATE FLOOR PLANS TO ASSURE THE REQUIRED VOLUMES
 OF AIR CAN BE DELIVERED TO EACH SPACE IN ACCORDANCE
 WITH FBC-M 603.1.
  
 5. PLEASE ENSURE PLANS ARE PROPERLY SIGNED, SEALED AND
 DATED IN ACCORDANCE WITH FS 481.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By kstevens Date 2009-07-10 Time 16:41 Rev Time 0.00
Received By kstevens Date 2009-07-10 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 09:29 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 09:29 Sent To  
Notes
2009-06-17 09:40:00DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 1 OF 7 GENERAL NOTES #1. THE PLANS FOR ALL
 APPLICATIONS FOR PERMIT ON OR AFTER MARCH 1 2009 SHALL
 BE DESIGNED TO THE FBC-2007 W/2009 SUPPLEMENTS. PLANS
 SHOW THE DESIGN TO BE UNDER THE FBC-2004 CODE. PLEASE
 UPDATE CYCLE. SECTIONS 106.1.1 & 110.1.2.
  
 2. THE ADDRESS OF RECORD ON THE STATE OF FLORIDA DEPT
 OF PROFESSIONAL REGULATION, (DBPR), 7711 BROOKFIELD
 ROAD, CHEVY CHASE MD. MOST SHEETS HAVE A DIFFERENT
 ADDRESS, 1801 S FLAGLER DRIVE, WEST PALM BEACH. PLEASE
 ADD THE ADDRESS OF RECORD TO ALL SHEETS CONTAINING THE
 LOCAL ADDRESS. FAC 61G1-16.004(1) & FS 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-04 Cont ID  
Sent By eschneid Date 2009-06-04 Time 15:27 Rev Time 0.25
Received By eschneid Date 2009-06-04 Time 15:26 Sent To  
Notes
***NONE***