Plan Review Details - Permit 09050539
Plan Review Stops For Permit 09050539
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-05 Cont ID  
Sent By rmcdouga Date 2009-06-05 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2009-06-05 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-01 Cont ID  
Sent By rmcdouga Date 2009-06-01 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2009-06-01 Time 09:35 Sent To  
Notes
2009-06-01 09:36:002007 FBC /ASCE 7-05
 INSTALL (4) ACCORDION SHUTTERS
  
 DENIED BY BUILDING
  
 1) THE WALL PRESSURES THAT ARE SPECIFIED FOR THE
 OPENINGS ARE INCORRECT. THEY WILL BE HIGHER THAN
 INDICATED FOR 140 MPH, EXPOSURE C AND MEAN ROOF HEIGHT
 OF 20 FEET. SEE 2007 FBC R TABLES R301.2(2) AND
 R301.2(3). PLEASE CORRECT INSTALLATION SCHEDULE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-01 Cont ID  
Sent By rmcdouga Date 2009-06-01 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 08:28 Sent To  
Notes
2009-05-29 08:28:48TO MISC 1