Plan Review Details - Permit 09050455
Plan Review Stops For Permit 09050455
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By mawillia Date 2009-06-22 Time 12:55 Rev Time 0.00
Received By mawillia Date 2009-06-22 Time 11:48 Sent To  
Notes
2009-06-22 12:22:52*****APPROVED*****
  
  
 THE APPROPIATE SHEETS OF THE FIRE ALARM PLAN (FA-1 THRU
 FA-4) WERE STAMPED, INITIALED, AND DATED; READY FOR
 PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-27 Cont ID  
Sent By mawillia Date 2009-05-27 Time 14:14 Rev Time 0.00
Received By mawillia Date 2009-05-27 Time 11:33 Sent To  
Notes
2009-05-27 13:43:11*****DENIED*****
  
  
 THE SUBMITTED ELECTRICAL SHEETS, WHICH WERE INCLUDED IN
 MASTER PERMIT # 08090611, DO NOT REVEAL SUFFICIENT
 INFORMATION (I.E. NUMBER OF DEVICES, ADDRESSES OF THE
 DEVICES, ETC.) FOR FIRE ALARM EXAMINATION AND/OR
 REVIEW. THERE ARE ALSO REVISIONS TO THESE SHEETS WHICH
 ARE PERTINENT TO PERMIT # 08090611, NOT THE APPLIED
 FIRE ALARM PERMIT OF 09050455.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-22 Cont ID  
Sent By mawillia Date 2009-06-22 Time 12:19 Rev Time 0.00
Received By mawillia Date 2009-06-19 Time 12:22 Sent To  
Notes
2009-06-19 12:24:37****ROUTED TO FIRE BOX*****